2.6.5

Status and Notice Messages

The Status and Notice messages shown in Figure 2-6
are displayed during generator set operation. These
informational messages do not indicate faults.
Message
Advance Diagnostic Active
Advance Diagnostic Active Ended
Always On
Ats Exercise Active
ATS Exercise mode End Prematurely
Ats Loaded Test Active
Ats Position Source 1 selected
Ats Position Source 2 selected
ATS Test End
Ats Test Ended Prematurely
Ats Unloaded Test Active
Auto Recovery
Backup Parameter Loaded
Default Parameters Loaded
Diagnostic Exercise Active
Emergency Power System Supplying
Load
Engine Cool Down Active
Engine Start Delay Active
Engine Started
Engine Stopped
Exercise mode End
File System Error
Forced to Auto Status
Generator Running
Load Priority X Shed
Loaded Full Speed Exercise Active
Maintenance Timer Reset
Normal Power Source Unavailable
Remote Start
Unloaded Full Speed Exercise Active
Figure 2-6 Status and Notice Messages
28
Section 2 Generator Set Operation
Type
Description
Status
During any exercise mode, shutdown occurs due to any other
condition(Fault) excluding Emergency Shutdown, Main Power
Overloaded Shutdown, Low Cranking Voltage Shutdown.
Status
Advance Diagnostic mode is ended
Notice
Any of the following optional boards are connected to controller
1. LCM
2. PIM
Notice
The generator is in exercise mode.
Status
Exercise mode ends prematurely.
Status
The ATS contactor position is source2 and user places the
controller in RUN mode.
Status
The ATS contactor position is source1.
Status
The ATS contactor position is source2.
Status
ATS Test ended.
Status
ATS Test ended prematurely.
Status
Generator is started by pressing RUN Button.
Status
Unit has reset due to unexpected error.
Status
Test event log command is initiated from Site Tech.
Status
When the engine stops, status is updated.
Status
Variable speed exercise is running.
Notice
The utility power is absent and the generator is powered on.
This notice is displayed on SiteTech.
Notice
The generator is in cool down mode.
Notice
The engine start delay is active.
Status
When the engine starts, status is updated.
Status
When the engine stops, status is updated.
Status
Exercise mode ended.
Status
Parameter/event saving fails after 3 retries.
Status
Mode has changed to AUTO mode.
Notice
The engine is started and a valid engine speed has been
achieved. This notice is displayed in SiteTech.
Notice
Priority X (1- 6) load with is disconnected.
Status
Loaded full speed exercise is running.
Status
The user has reset the maintenance timer.
Notice
Utility power is unavailable.
Status
The remote start switch is pressed.
Status
Unloaded full speed exercise is running.
TP-6905 9/21