State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov Kohler strongly recommends that only factory-authorized distributors or dealers install and service the generator. Product Identification Information...
Table of Contents Product Identification Information ............Safety Precautions and Instructions .
Page 4
Table of Contents, continued 3.12 Genset Run Time Menu ..........3.13 Genset System Menu .
Page 5
Safety Precautions and Instructions Accidental Starting IMPORTANT SAFETY INSTRUCTIONS. WARNING Electromechanical equipment, including generator sets, transfer WARNING switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, maintained. To prevent accidents be Explosion. Can cause severe injury or death. aware of potential dangers and act safely.
metal surface away from the battery. To minimize the risk of fire or explosion. possibility carbon monoxide avoid sparks, do not disturb the battery Equip the compartment or nearby area poisoning. Seek medical attention if charger connections while the battery with a fully charged fire extinguisher.
Page 7
Hazardous Voltage/ Propane (LPG)—Adequate ventilation CAUTION is mandatory. Because propane is Moving Parts heavier than air, install propane gas detectors low in a room. Inspect the DANGER detectors manufacturer’s instructions. Natural Gas—Adequate ventilation is Welding the generator set. mandatory. Because natural gas rises, cause severe electrical...
Page 8
Hot Parts Notice Connecting the battery and the battery charger. Hazardous voltage will cause severe injury or death. NOTICE WARNING Reconnect battery correctly, Canadian installations only. positive to positive and negative to standby service connect the output of negative, to avoid electrical shock and the generator set to a suitably rated damage to the battery charger and transfer switch in accordance with...
Genset Model Information in this publication represents data available Spec Number at the time of print. Kohler Co. reserves the right to Serial Number change this publication and the products represented Material Number without notice and without any obligation or liability...
Page 10
Service Manual, KG2204/KG2204T Engine Mechanical TP-6902 Service Manual, Engine ECM Diagnostics TP-6903 Parts Catalog, KG2204/KG2204T Engine TP-6904 Parts Catalog, 24RCL, 30RCL, 38RCLB Generator Set TP-6908 Operation Manual, OnCuer Plus Software TP-6928 Operation/Installation Manual, RXT ATS TP-6807 Operation/Installation Manual, RDT ATS...
Visit the Kohler Co. website at KohlerPower.com. (86) 10 6518 7952 Fax: (86) 10 6518 7955 Look at the labels and decals on your Kohler product East China Regional Office, Shanghai or review the appropriate literature or documents Phone: (86) 21 6288 0500 included with the product.
Section 1 Service Views SERVICE SIDE GM90230 ADV-8641 Cooling System Detail NON-SERVICE SIDE 1. Oil check (dipstick) 17. RDC2 controller 2. Oil fill location (on valve cover) 18. Fan fuses 3. See cooling system detail 19. Cooling air inlet (remove this panel to access coolant drain) 4.
Page 14
17. Cooling air inlet (remove this panel to access coolant drain) 35. Oil cooler hoses 18. See cooling system detail 36. Oil cooler (at bottom of radiator) Figure 1-2 30RCL and 38RCLB Service Views for Maintenance Section 1 Service Views TP-6905 7/18...
Section 2 Generator Set Operation 2.1 Operating Area Notice Do not locate patios, decks, play areas, or animal WARNING shelters near the generator set. Keep items such as lawn furniture, toys, sports equipment, and all combustible materials away from the generator set exhaust outlet.
Page 16
DANGER WARNING Hazardous voltage. Will cause severe injury or death. Sulfuric acid in batteries. This equipment must be installed and Can cause severe injury or death. serviced qualified electrical Wear protective goggles personnel. clothing. Battery acid may cause blindness and burn skin. Grounding electrical equipment.
Page 17
Drive Belt. Check the belt condition of the water pump Check that there are no combustible materials near and battery charging alternator belt. the exhaust outlet. Check that the exhaust outlet is unobstructed. Exhaust System. Check for exhaust leaks and blockages.
2.3 Exercising the Generator Set The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if Operate the generator set without load every week or the temperature drops below the cooled-down every other week for 20 minutes.
Transfer Switches The Unloaded Cycle exercise runs the engine for If a Kohler Model RDT transfer switch is used, the 20 minutes in the cycle shown in Figure 2-1 and engine start contacts from the ATS must be connected described below.
2.5.4 Shutdown During Exercise Communication integrity tests. J1939, RBUS, Ethernet, and USB are monitored for messages The following advanced diagnostic operation applies to indicating that the controller and wiring are reliable. RDC2 controllers with firmware versions 5.04 and Engine speed. Engine speed is measured at low higher.
4. The time is displayed with the hour flashing. Use 3. Press the down arrow button to step to the Genset the up or down arrow key to step to the current hour System menu. and am or pm setting. 4.
Page 22
Status Overview ----> Displays 1.2 h Engine ----> ----> Metering Configuration Generator----> Date ----> Metering and Time Genset ----> Network ----> Information Information ----> Genset ----> Status Run Time Genset ----> Load ----> System Control Event Log----> ----> Status tp6810 Figure 2-2 RDC2 Main Menu Section 2 Generator Set Operation TP-6905 7/18...
Page 23
Genset ----> System Voltage: 240 V System System Freq: 60 Hz VR Voltage Adj: 240.0V System Phase: Single System Battery: 12 V See Section 2.5.8, Changing Next Exercise * Next Exercise the Exercise Setting HR:MN PM MM/DD/YY HR:MN PM MM/DD/YY Exercise Mode: Exercise Mode: None/Unloaded Full Sp/ Un-...
2.6 Faults 2.6.3 ATS Communication Errors When a Model RXT transfer switch is used, an ATS fault Selected fault conditions are shown in Figure 2-5. Fault indicates that the connection to the interface board on conditions are classified as warnings or shutdowns. If a the transfer switch has been lost.
Page 25
Fault (RDC2) Fault (OnCuer Condition Check Plus) AC Sens Loss AC Sensing AC Sensing Lost. In Auto mode, generator Contact an authorized Lost output AC sensing is lost. Detection begins 10 distributor/dealer for service. Warning seconds after crank disconnect. (1 sec.) Warning: after 1 second if no output detected Shutdwn after crank disconnect.
Page 26
Fault (RDC2) Fault (OnCuer Condition Check Plus) CoolTemp Vhi Ect Higher Coolant temperature is extremely high. Check coolant level. Shutdwn Than Check radiator and fans for Expected 2 obstruction. Contact an authorized distributor/dealer for service and provide the fault code. CoolntTemp 0 Coolant Temp 0 The ECM reported a problem with the coolant...
Page 27
Fault (RDC2) Fault (OnCuer Condition Check Plus) Genset S/N Unavailable Generator set serial number is unavailable. Contact an authorized Unaval Warning Genset Serial distributor/dealer for service. See Number section 3.11. Ground Fault Ground Fault The digital input for Ground Fault Warning is Check customer equipment Warning Warning...
Page 28
Fault (RDC2) Fault (OnCuer Condition Check Plus) PrimLoopOpn Primary Loop Ignition coil 1 voltage is below normal or Check the battery voltage. Warning Open there is an open circuit. Contact an authorized distributor/dealer for service and provide the fault code. PrimLoopSht Primary Loop Ignition coil 1 voltage is abnormal.
2.7 Model RXT Transfer Switch 2.6.5 Event Log Operation The event log displays up to 1000 controller faults and notices, starting with the most recent event. Events are The RDC2 generator set/transfer switch controller numbered 1--1000, with 1 being the most recent. Each manages automatic transfer switch (ATS) functions event is displayed with the date and time of the event, when connected to a Kohlerr Model RXT transfer switch...
2.7.2 ATS Control Sequence of 2.7.3 Time Delays Operation Time delays are factory-set to the values shown in Figure 2-8. An authorized distributor/dealer can adjust See Figure 2-8 for time delay settings. time delays using a personal computer and Kohlerr SiteTecht software.
3.2 Controls and Indicators Switch Controller Figure 3-1 illustrates the keypad, display, and indicators on the controller’s user interface. Model 24RCL, 30RCL, and 38RCLB generator sets are equipped with the RDC2 generator set/transfer switch controller. The RDC2 controls the following power system components:...
3.2.1 Controller Keypad 3.2.2 LED Indicators The Run, Off, and Auto buttons control the generator set LEDs above the RUN, OFF, and AUTO buttons indicate as described in Figure 3-2. Use the Select, Up arrow, the mode of operation as shown in Figure 3-2. and Down arrow buttons to navigate through the menus The RDC2 controller also has a set of power system and change settings, if necessary.
3.2.3 LCD Display The display contrast is adjustable. Navigate to the Genset System menu and step down to the Contrast The controller is equipped with a two-line x 16 character screen. Press the Select button, and then use the up and backlit liquid crystal diode (LCD) display with adjustable down arrow buttons to adjust the contrast.
Note: If no buttons are pushed, the controller exits the menus and returns to the generator set status Have controller setup and adjustment performed only by display after 5 minutes. an authorized Kohler distributor/dealer or authorized representative. Section 3 RDC2 Controller Operation TP-6905 7/18...
Page 35
Changing Settings on the RDC2 Controller 1. Press the Select button to enter the main menu. 8. When the correct date is shown, press the Select button. The saved date is shown. Overview ----> Press: Display: Date: 1.2 h Press: Display: 03Jan2014 2.
3.6 Controller Menus 3.7 Main Menu The following sections show the RDC2 controller menus Press the Select button once to bring up the main menu. and submenus. Use the Select button and the up and Overview is displayed. See Figure 3-7. Press the down down arrow buttons to navigate the menus as shown in arrow button to step to the next menu, Engine Metering.
3.8 Overview Menu 3.9 Engine Metering Menu The engine metering menu displays engine status information as shown in Figure 3-9. This menu displays status information only. No settings can be changed Overview ----> Active Alert from this menu. 1.2 h (if any) Eng Speed: Engine ---->...
The voltage calibration mode can be entered from the Generator Metering menu. Contact a Kohler-authorized distributor/dealer for service. The Reset Calibration menu allows you to set the voltage reading back to the original value after calibration, if necessary. See Figure 3-10.
Kohlerr SiteTecht software is required to enter manufacturer’s recommendation for changing the oil. the generator set model number and serial numbers on Refer to Section 4, Scheduled Maintenance, for a replacement controller. Contact an authorized Kohler maintenance instructions. distributor/dealer for service. After...
----> System Voltage: 240 V System A Kohler authorized distributor or dealer can adjust these settings, if necessary. If the generator set is reconnected to a different voltage or the system settings require adjustment for some other reason, see Section System Freq: 3.5 for instructions to enable editing and change the...
3.14 ATS Status Menu The ATS Status menu displays Model RXT transfer switch and source information. ATS menus appear if a Model RXT transfer switch is The voltage shown in these menus can be calibrated. connected to the generator set. If no transfer switch is Contact an authorized distributor or dealer for service if connected, or another model ATS is connected to the calibration is required.
3.15 ATS Configuration Menu Note: The ATS Configuration menu appears only if a ATS ----> Normal Freq: Model RXT transfer switch is connected. Configuration 60.0 Hz Use the ATS Configuration submenu to check the Model RXT transfer switch system settings and time delays, and change the settings, if necessary.
3.16 Date and Time Menu The date and time will typically be set at controller power-up. To change the date, time, or time format (12 hour or 24 hour), use the Date and Time menu. See Figure 3-16. Date and Date: Time 02Dec2014...
3.17 Networking Information Menus Generator Management System. RBUS is a proprietary RS-485 communication protocol. Use the networking menus to view and adjust The Networking Information menu leads to submenus communication settings for systems with remote RBUS for network and RBUS communication settings. devices such as a PIM or load management device, and for systems that use the Kohlerr OnCuer Plus Home Networking---->...
3.17.1 Networking Status Submenu If DHCP is enabled, IP parameters are not displayed. If DHCP is disabled (i.e., if a static IP address is used), the The Networking Status submenu contains settings for IP parameters are displayed. OnCuer Plus. See the OnCue Plus Software Operation Manual for information about the appropriate To enable or disable DHCP and change the IP settings, network settings for OnCue Plus.
3.17.2 Networking Configuration Note: Use the OnCue password shown on the controller display for OnCue Plus applications. Submenu (OnCue Plus Password) The networking Configuration menu includes settings For the initial OnCue Plus setup, you will be required to reset the OnCue password on the used for communication with the Kohlerr OnCuer Plus RDC2 controller, and then enter it into the OnCue Generator Management System.
3.17.3 RBUS Information Submenu Model RXT transfer switch The RBUS Information menu contains settings for Programmable Interface Module (PIM) remote modules that communicate with the RDC2 Load Shed Kit or RXT combined interface/load controller using RBUS protocol. This includes the management board following optional modules: Networking---->...
3.17.4 Remote Devices Submenu Check the status of remote devices communicating through RBUS. Device types can include: Model RXT ATS Programmable interface module (PIM) Load Shed Kit or RXT combined interface/load management board The serial numbers for the PIM and load shed kit are printed on the circuit boards inside the enclosures.
3.18 Programmable Interface A personal computer running Kohlerr SiteTecht software is required to change the input and output Module (PIM) Menus settings. Contact an authorized distributor or dealer for service. The PIM status menu displays the status of inputs and outputs connected to the programmable interface The Kohlerr OnCuer Plus Management System can be module (PIM).
3.19 Load Control Menus device adds and sheds loads based on the generator current. The Load Control menu displays the status of the load The test function cycles the relays in the order of their management inputs and outputs, and allows a test of the priority.
Section 4 Scheduled Maintenance 4.1 General Maintenance Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Install the heater before connecting it to power. Operating the heater before WARNING installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
Page 52
Do not use a soap solution containing either ammonia or Maintenance and Service Parts. Obtain maintenance chlorine because both prevent bubble formation. A successful and service parts from an authorized Kohler test depends on the ability of the solution to bubble. distributor/dealer.
4.2 Service Schedule Procedure Visually Inspect Check Change Clean Test Section System Component or Procedure Frequency General Maintenance Fluid leaks Daily Engine oil level Daily Coolant level 4.6.1 Daily Obstructions or combustible materials near Weekly exhaust outlet Leaks, hissing, and gas odor Weekly Bolts and nuts for tightness Quarterly or 20 hours...
4.3 Lubrication System 4.3.4 Oil and Filter Change WARNING 4.3.1 Oil Specifications Use oil that displays the American Petroleum Institute (API) Starburst certification mark FOR GASOLINE ENGINES on the container. Do not use straight-weight oils recommended for industrial or stationary engines. Accidental starting.
Page 55
[Torque = 25 Nm (18.4 ft. lbs.)]. 3. Fill with oil. Use 5W-30 for oil selection and Figure 4-2 for oil capacity. Model Oil Capacity, L (qt.) 4.2 (4.4) 24RCL, 30RCL, and 38RCLB Figure 4-2 Oil Capacity TP-6905 7/18 Section 4 Scheduled Maintenance...
4.4 Air Cleaner WARNING Accidental starting. 1. Air Cleaner Cover Can cause severe injury or death. GM90280 Disconnect the battery cables before Figure 4-3 Air Cleaners working generator set. Remove the negative (--) lead first 1. Release the retaining clips to open the cover and when disconnecting the battery.
Check the exhaust gas color. If the exhaust is blue or D Light-headedness, dizziness black, contact your local authorized Kohler distributor/ D Physical fatigue, weakness in dealer. joints and muscles D Sleepiness, mental fatigue, Visually inspect for exhaust leaks (blowby).
Remove Block Heater Engine Model dirt and other debris from the pressure cap and filler 24RCL, 30RCL, 38RCLB 13.2 (3.5) 13.7 (3.6) neck. The pressure cap raises the boiling point of the coolant, enabling higher operating temperatures. If...
softened water to inhibit rust/corrosion and prevent Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the freezing. The coolant capacity is shown in generator set or equipment connected to the set, disable the Figure 4-5.
Page 60
Model Spark Plug Gap 24RCL 0.9–1.0 mm (0.036–0.040 in.) 15. Use a torque wrench to tighten each spark plug to 30RCL and 38RCLB 0.7--0.8 mm (0.028--0.030 in.) the torque shown in Figure 4-9. Figure 4-6 Spark Plug Gap Model Spark Plug Torque 24RCL 18 Nm (13.3 ft.
Page 61
Problem/Condition Means of Identification Possible Cause/Solution Gap-bridged spark Built-up deposits and gap between Oil or carbon fouling. Clean and regap the spark plug electrodes closing. plug. Oil-fouled spark plug Wet, black deposits on the insulator shell, Excessive oil entering combustion chamber through bore, and electrodes.
4.8 Battery Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator Consult battery manufacturer’s instructions set installation or maintenance. Remove all jewelry before regarding battery care and maintenance. servicing the equipment.
4.8.1 Checking Electrolyte Level Temperature Correction C F Check the electrolyte level of batteries with filler caps 71.1 + .032 monthly. Remove filler caps and verify that electrolyte + .030 level reaches bottom of filler holes. Refill as necessary 65.6 + .028 EXAMPLE NO.
4.9 Storage Procedure 4. Check the engine coolant protection; see Section 4.6. DANGER Note: Use antifreeze capable of withstanding the lowest possible temperatures. 5. Keep spark plugs in their holes or seal spark plug holes with suitable threaded metal plugs. Hazardous voltage.
If the procedures in this manual do not explain how to in the event of a fault in the wiring between the generator correct the problem, contact an authorized Kohler and the load. If the circuit breaker trips, reduce the load distributor/dealer.
Battery connections reversed or poor. Check the connections. crank. Blown fuse(s). Replace the fuse. Contact an authorized Kohler distributor/dealer for service if fuse blows repeatedly. Generator set is OFF. Press the RUN button to start the engine or press AUTO to allow remote starting.
5.6 Controller Troubleshooting Figure 5-2 contains basic troubleshooting information for the RDC2 controller. Problem Possible Cause Corrective Action Controller LCD Low or no battery voltage. Check connections. display is off. Check generator set battery. See Figure 5-1. Controller display Backlight turns off after about 1 minute with no Backlight will turn on when a button is pressed or backlight is off.
(2 bytes) est. estimated Canadian Electrical Code KBus Kohler communication protocol E-Stop emergency stop cert. certificate, certification, certified kilogram etc. et cetera (and so forth) cubic feet per hour exh. exhaust...
Page 70
kg/cm kilograms per square normally closed remote terminal unit centimeter National Electrical Code room temperature vulcanization kilogram-meter NEMA National Electrical read/write kg/m kilograms per cubic meter Manufacturers Association Society of Automotive kilohertz NFPA National Fire Protection Engineers Association kilojoule scfm standard cubic feet per minute newton meter kilometer...
Page 72
KOHLER CO., Kohler, Wisconsin 53044 Phone 920-457-4441, Fax 920-459-1646 TP-6905 7/18c For the nearest sales/service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com E 2014, 2015, 2016, 2018 by Kohler Co. All rights reserved.