Dynamic setpoint ver. 2
The dynamic setpoint view. X-axis: outdoor temperature, Y-axis: flow temperature.
Pos.
1
Setpoint
2
Operating mode curve
selection
3
Minimum outdoor temperature Minimum outdoor temperature limit (can be adjusted)
4
Current temperature
5
Maximum outdoor temperature Maximum outdoor temperature limit (can be adjusted)
6
Outlet temperature values for
each outdoor temperature
The values along the X-axis each indicate a specific outdoor temperature point. To
specify an outlet (flow) temperature for a given outdoor (or process) temperature point,
tap on the white box above the temperature point (Pos. 6 in the figure.)
The applicable temperature range can be changed by changing the temperature values
along the X-axis. To change a temperature value (temperature point), tap on the value.
Timed setpoint
The Timed setpoint view allows users to temporarily force a setpoint for either side
for a specific day and duration. Additionally, the On buttons along the top edge of the
screen can be used to apply a (temporary) setpoint for the primary side, the secondary
side, or both.
48 (64)
Item
Setpoint calculated based on the current outdoor temperature
(or process temperature) and curve point values
Select which side's (in the figure: primary/Heat or secondary/
Chill) values to change.
Current measured outdoor temperature
Tap to adjust each value.
Description
EXEP01 2150EN