3.7 Electrical connections

A general description of the needed electrical connections is given in this section. The
actual connections should be made according to the wiring diagrams delivered with the
heat pump.
Recommended cable sizes – Europe
Model
Cable size
P30
P60
P100
P150
Recommended cable sizes – North America
Model
P30
P60
P100
P150
26 (64)
Electrical installation is to be carried out by authorized and trained
personnel only.
Before performing any work on electrical components, make sure that
there is no voltage present.
Do not connect devices that draw over 2 A of current directly to the
controller. Use a contactor instead.
3 x 10Cu + 10Cu
3 x 70Cu/35Cu
3 x 95Cu/50Cu
2 x (3 x 50Cu/25Cu)
1 x (3 x 120Cu/70Cu)
Cable size
AWG4
AWG 1
AWG 3/0
2 x AWG 3/0
Model
Cable size
2 x (3 x 95Cu/50Cu)
P220
1 x (3 x 185Cu/70Cu)
2 x (3 x 120Cu/70Cu)
P300
1 x (3 x 240Cu/95Cu)
P380
2 x (3 x 150Cu/70Cu)
P450
2 x (3 x 240Cu/120Cu)
Model
Cable size
P220
2 x AWG 300MCM
P300
2 x AWG 350MCM
P380
2 x AWG 500MCM
P450
2 x AWG 500MCM
EXEP01 2150EN