Trane Exergy P30 Installation And Operation Manual page 46

Table of Contents

Advertisement

Pos.
1
Current heating/cooling mode
● Sun = heating
● Snowflake = cooling
2
Trends
3
Alarms
4
Home view
5
Cold water in
6
Cold water out
*The values for each circuit are shown on separate lines.
If the system has a buffer tank on the cold or the warm side, the tank will be displayed
along the left or the right edge of the screen. The tank's temperature measurements
will also be displayed. Note that these buffer tanks must be enabled in the Warm
settings or the Cold settings view (see section Cold side and warm side settings)
before they are displayed.
Start delay, stop delay, and oil heating delay
The start delay and stop delay are shown in the top left corner as degree minutes.
These values can be changed. For example, if the stop delay value is 30Cmin and the
temperature is 1 degree below the setpoint, the heat pump will start to ramp down in 30
minutes. If the temperature is 10 degrees below the setpoint, the heat pump will start to
ramp down after 3 minutes. This can be speeded up by changing the Left values (time
left).
If the oil heating delay is active, the delay is displayed in minutes.
44 (64)
Item
Pos.
Item
7
Warm water out
8
Warm water in
9
Power: cooling*
10
Power consumed by the system's
compressors*
● The lowest value is the current taken
by the compressor or compressors.
11
Power: heating*
12
Compressors
EXEP01 2150EN