Summary of Contents for Endress+Hauser Proline t-mass 65 PROFIBUS DP
Page 1
Description of Device Functions Proline t-mass 65 PROFIBUS DP Thermal Mass Flow Measuring System BA114D/06/en/02.06 71021610 Valid as of version V 3.02.XX (Device software)
Device Functions Proline t-mass 65 PROFIBUS DP 1 Function matrix Proline t-mass 65 Function matrix Proline t-mass 65 The function matrix: layout and use The function matrix is a two-level construct: the groups form one level, functions the other. The groups are the highest-level grouping of the control options for the flowmeter.
Device Functions Proline t-mass 65 PROFIBUS DP 2 Group MEASURING VALUES Group MEASURING VALUES Function description MEASURING VALUES Note! The engineering unit of the measured variable shown here can be set in the SYSTEM UNITS group (→ Page 8). MASS FLOW In this function, the currently measured mass flow appears on the display.
3 Group SYSTEM UNITS Device Functions Proline t-mass 65 PROFIBUS DP Group SYSTEM UNITS Function description SYSTEM UNITS You can select the unit for the measured variable in this function group. Note! The factory settings of the system units described here apply to the local display and can differ from the units that are used to transfer the measured variables to the automation system.
Page 9
Device Functions Proline t-mass 65 PROFIBUS DP 3 Group SYSTEM UNITS Function description SYSTEM UNITS UNIT TEMPERATURE Use this function to select the unit for displaying the temperature. Options: °C (Celsius) K (Kelvin) °F (Fahrenheit) °R (Rankine) Factory setting: °C or °F (country dependent, → Page 41 ff.) UNIT DENSITY Use this function to select the unit for displaying the calculated gas process density.
4 Group QUICK SETUP Device Functions Proline t-mass 65 PROFIBUS DP Group QUICK SETUP Function description QUICK SETUP QUICK SETUP COMMISSION Use this function to start the setup menu for commissioning. Options: Factory setting: Note! You will find a flowchart of the Quick Setup Commissioning menu on Page 11.
Device Functions Proline t-mass 65 PROFIBUS DP 4 Group QUICK SETUP Quick Setup “Commissioning” If the device is equipped with a local display, the Commissioning Quick Setup menu can be used to configure all the important device parameters for standard operation quickly and easily.
Page 12
4 Group QUICK SETUP Device Functions Proline t-mass 65 PROFIBUS DP QUICK SETUP - COMMISSION Use the O or S key at the prompt “QS-COMMISSION NO” and the device access code entry appears. Enter the device access code “65” and press F; programming is enabled.
Device Functions Proline t-mass 65 PROFIBUS DP 4 Group QUICK SETUP Quick Setup “Communication” To establish cyclic data transfer, various arrangements between the PROFIBUS Master (class 1) and the slave are required which have to be taken into consideration when configuring various functions.
4 Group QUICK SETUP Device Functions Proline t-mass 65 PROFIBUS DP Data back-up with “T-DAT SAVE/LOAD” The T-DAT SAVE/LOAD function can be used to store all the settings and parameters of the device to the HistoROM/T-DAT data storage device. XXX.XXX.XX...
HOME position. • You can also disable programming in this function by entering any number (other than the defined private code). • Your Endress+Hauser service representative can be of assistance if you lose your personal code. Endress+Hauser...
Page 16
5 Group OPERATION Device Functions Proline t-mass 65 PROFIBUS DP Function description OPERATION DEFINE PRIVATE CODE Use this function to define a personal code number for enabling programming. User input: max. 4-digit number: 0 to 9999 Factory setting: Note! • If you define the personal code number = 0, the programming is always enabled.
Device Functions Proline t-mass 65 PROFIBUS DP 6 Group USER INTERFACE Group USER INTERFACE Function description USER INTERFACE ASSIGN LINE 1 Use this function to define the display value assigned to the main line (the upper line of the local display) for display during normal measuring operation.
Page 18
6 Group USER INTERFACE Device Functions Proline t-mass 65 PROFIBUS DP Function description USER INTERFACE 100% VALUE LINE 1 Use this function to define the flow value to be shown on the display as the 100% value of the variable assigned to line 1.
Page 19
Device Functions Proline t-mass 65 PROFIBUS DP 6 Group USER INTERFACE Function description USER INTERFACE DISPLAY DAMPING Use this function to enter a time constant defining how the display reacts to severely fluctuating flow variables, either very quickly (enter a low time constant) or with damping (enter a high time constant).
7 Group TOTALIZER Device Functions Proline t-mass 65 PROFIBUS DP Group TOTALIZER Function description TOTALIZER SELECT TOTALIZER Use this function to select the totalizer. Options: TOTALIZER 1 TOTALIZER 2 Factory setting: TOTALIZER 1 Note! If the PROFILE-GSD option is selected in the SELECTION GSD function, only the TOTALIZER 1 option is available in this function.
Page 21
Device Functions Proline t-mass 65 PROFIBUS DP 7 Group TOTALIZER Function description TOTALIZER UNIT TOTALIZER Note! This function is available separately for each totalizer. The selection of the current totalizer takes place in the SELECT TOTALIZER function (see Page 20).
Page 22
7 Group TOTALIZER Device Functions Proline t-mass 65 PROFIBUS DP Function description TOTALIZER MODE TOTALIZER Note! This function is available separately for each totalizer. The selection of the current totalizer takes place in the SELECT TOTALIZER function (see Page 20).
Device Functions Proline t-mass 65 PROFIBUS DP 8 Group COMMUNICATION Group COMMUNICATION Function description COMMUNICATION TAG NAME For entering a tag name for the measuring device. You can edit and read this tag name via the local display or an operating program (e.g. FieldCare).
Page 24
8 Group COMMUNICATION Device Functions Proline t-mass 65 PROFIBUS DP Function description COMMUNICATION UNIT TO BUS If this function is executed, the measured variables (AI modules) transmitted cyclically are transmitted to the PROFIBUS Master (class 1) with the system unit configured in the measuring device.
Page 25
Device Functions Proline t-mass 65 PROFIBUS DP 8 Group COMMUNICATION Function description COMMUNICATION CHANNEL Note! • This function is not available unless the AI1 -, AI2 - or AI3 - OUT VALUE option was selected in the BLOCK SELECTION function.
9 Group PROCESS PARAMETER Device Functions Proline t-mass 65 PROFIBUS DP Group PROCESS PARAMETER Function description PROCESS PARAMETER ASSIGN LOW FLOW CUT OFF Use this function to assign the switching point for the low flow cut off. Options: MASS FLOW...
Page 27
Device Functions Proline t-mass 65 PROFIBUS DP 9 Group PROCESS PARAMETER Function description PROCESS PARAMETER ZERO POINT ADJUST This function enables a zero point adjustment to be automatically carried out. The new zero point determined by the measuring system is written to the ZERO POINT function (see Page 35).
Page 28
9 Group PROCESS PARAMETER Device Functions Proline t-mass 65 PROFIBUS DP Function description PROCESS PARAMETER REFERENCE TEMPERATURE Use this function to enter a value for reference temperature with which the reference density is calculated for the corrected volume flow measurement.
Device Functions Proline t-mass 65 PROFIBUS DP 10 Group GAS MIXTURE Group GAS MIXTURE Function description GAS MIXTURE This group of functions allows the user to read the gas types and fraction (%) programmed. The mixture can be made up of 8 individual gas components from a total of 20 gases.
Page 30
10 Group GAS MIXTURE Device Functions Proline t-mass 65 PROFIBUS DP Function description GAS MIXTURE GAS TYPE 1 Use this function to view the Gas Type 1. Options: AMMONIA ARGON BUTANE CARBON DIOXIDE CARBON MONOXIDE CHLORINE ETHANE ETHYLENE HELIUM 4...
Page 31
Device Functions Proline t-mass 65 PROFIBUS DP 10 Group GAS MIXTURE Function description GAS MIXTURE GAS TYPE 3 View Gas Type 3 Note! This function is not available if NUMBER OF GAS COMPONENTS selection is < 3. Display: Gas list the same as GAS TYPE 1...
Page 32
10 Group GAS MIXTURE Device Functions Proline t-mass 65 PROFIBUS DP Function description GAS MIXTURE GAS TYPE 6 View Gas Type 6 Note! This function is not available if NUMBER OF GAS COMPONENTS selection is < 6. Display: Gas list the same as GAS TYPE 1...
Page 33
Device Functions Proline t-mass 65 PROFIBUS DP 10 Group GAS MIXTURE Function description GAS MIXTURE CHECK VALUES This function checks the entered gas mixture values. Note! This function is only available if the gas mixture fractions do not = 100%.
11 Group SYSTEM PARAMETER Device Functions Proline t-mass 65 PROFIBUS DP Group SYSTEM PARAMETER Function description SYSTEM PARAMETER POSITIVE ZERO RETURN Use this function to interrupt the flow measurement variables. For example, the output signal should be set to zero flow during operations such as pipe cleaning.
Caution! Incorrect adjustment of these parameters can have an adverse affect on the calculated flow value. Contact your Endress+Hauser service representative if you have any questions about these functions. PIPE TYPE Use this function to select the type of pipe used in the application for an insertion type sensor.
Page 36
12 Group SENSOR DATA Device Functions Proline t-mass 65 PROFIBUS DP Function description SENSOR DATA INTERNAL HEIGHT Use this function to enter the internal height of a rectangular duct for an insertion type sensor. Note! This function is not available for t-mass F type sensors or if CIRCULAR is selected in the function PIPE TYPE.
Device Functions Proline t-mass 65 PROFIBUS DP 13 Group SUPERVISION Group SUPERVISION Function description SUPERVISION ACTUAL SYSTEM Use this function to check the current system status. CONDITION Display: “SYSTEM OK” or the fault / notice message with the highest priority.
14 Group SIMULATION SYSTEM Device Functions Proline t-mass 65 PROFIBUS DP Group SIMULATION SYSTEM Function description SIMULATION SYSTEM SIMULATION FAILSAFE Use this function to set the Analog Input and Totalizer Function Blocks to their MODE defined fault response modes, in order to check whether they respond correctly.
Device Functions Proline t-mass 65 PROFIBUS DP 15 Group SENSOR VERSION Group SENSOR VERSION Function description SENSOR VERSION SENSOR TYPE Use this function to view the sensor type. Display: FLOWCELL (for t-mass F ) INSERTION (for t-mass I) SERIAL NUMBER Use this function to view the serial number of the sensor (complete measuring tube or insertion tube).
16 Group AMPLIFIER VERSION Device Functions Proline t-mass 65 PROFIBUS DP Group AMPLIFIER VERSION Function description AMPLIFIER VERSION DEVICE SOFTWARE Displays the current device software version. HARDWARE REVISION Use this function to view the hardware revision number of the amplifier.
Device Functions Proline t-mass 65 PROFIBUS DP 17 Factory settings Factory settings 17.1 SI units (not for USA and Canada) t-mass F sensor Low flow cut off, full scale value (with air at ambient conditions; without flow conditioner) Nominal diameter...
17 Factory settings Device Functions Proline t-mass 65 PROFIBUS DP Length, pressure, temperature, density, reference density Unit Unit Length Density kg/m Pressure bar a Reference density kg/m Temperature °C Units for totalizer 1 and 2 Totalizer assignment Unit Mass flow Corrected volume flow 17.2...