FLOW ADJUSTMENT (REG)

1.
Turn on and generate demand in all zones to open all the dampers.
2.
Turn off the zone/damper to be adjusted.
3.
Adjust the maximum opening you want with the REG lever (I/II/III/IV).
4.
Turn on the zone and check the flow is correct.

MINIMUM AIR SETTING (A-M)

1.
Turn on and generate demand in all zones to open all the dampers.
2.
Adjust the minimum opening you want with the M-A lever (a/b/c/d).
3.
Turn on the zone and check the minimum air flow is correct.
A-M

ADVANCED SETTINGS

To access the advanced configuration menu of the Blueface zero and Think thermostats follow the following steps:
Blueface zero
Press and hold
Think
Press and hold
REG
Press and hold
ES