Outdoor Unit - RK(X)S25/35G2V1B9
4.6

Removal of Four Way Valve

Procedure
Step
Pull out the electronic
1
expansion valve coil.
Remove the terminal
2
cover.
Disconnect the lead
3
wires of the
compressor.
227
Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Red (U)
Yellow (V)
Blue (W)
Electronic
expansion
valve coil
(R7233)
Terminal cover
(R7234)
(R7235)