Chase Venting; Tv Recess Framing; Corner Framing - Montigo D3615 Installation & Maintenance Manual

Indoor direct vent gas fireplace
Hide thumbs Also See for D3615:
Table of Contents

Advertisement

Chase venting
At a minimum, a 120 square inch opening is required in the finished
enclosure to keep temperatures within a safe level. This can be achieved
in a variety of ways such as the few shown below.
Figure 19.b Side chase venting (6"x10") on
both sides of enclosure
Figure 19.d Front chase venting (2"x60")
on front of enclosure
The opening of the chase cannot be lower than 3" from the top of the
enclosure to prevent heat from pocketing at the top of the enclosure.
A minimum of 2" from the top of a chase vent to the ceiling is needed.
Any combination of the above examples is an acceptable chase vent
providing they add up to at least 120 square inches.
NOTE: Chase venting not required if using Cool Wall Advantage heat
diversion system.
XG0222
Figure 19.c Top chase venting (3"x40") on
top of enclosure
Minimum
2" gap
Ceiling
Figure 19.d Open top chase venting on
top of enclosure

TV recess framing

3" Min. from
ceiling
The recess MUST
be made from
Non-Combustable
materials. Maintain
4" Max
1" clearance
from venting to
Depth
combustibles.
12" min. from
fireplace opening
Figure 8.b.d Cool Wall Advantage TV recess dimensions
The recess must be made from Non-Combustable materials. Recess can
be increased beyond a 4" depth by using a 45° or 90° elbow in venting
after the minimum 3' upward distance is achieved, 1" clearance from
venting to combustibles must still be maintained.

Corner framing

A
B
Installation
Dimensions
A
B
D36
26
64⅞
3/16
D48
30
73⅜
7/16
D72
39⅝
91¾
11