Minimum Clearances To Combustibles - Superior Fireplaces DRL2000 Series Installation And Operation Instruction Manual

Table of Contents

Advertisement

Innovative Hearth Products
DRL2000 & DRL3500 Series Direct-Vent Gas Fireplaces

MINIMUM CLEARANCES TO COMBUSTIBLES

Fireplace And Vent Clearances
The fireplace is approved with zero clearance to combustible materials
on all sides (Table 8), with the following exception: The unit may not
be recessed (allowance made for mantel legs / side trim in Figure 5C,
Page 16). When the unit is installed with one side flush with a wall, the
wall on the other side of the unit must not extend beyond the front edge
of the unit (Figure 5C, Page 16).
The fireplace must be mounted on a fully supported base extending
the full width and depth of the unit. The fireplace may be located on
or near conventional construction materials. However, if installed on
combustible materials, such as carpeting, vinyl tile or other combustible
material other than wood flooring, the appliance shall be installed on a
metal or wood panel extending the full width and depth of the appliance.
Hearth Extension
A hearth extension is not required with this fireplace. Any hearth extension used is for appearance only and does not have to conform to
standard hearth extension installation requirements.
Shelf Height
f i r e - p a r t s . c o m
To provide for the lowest possible shelf surface, the venting attached to the top vent should be routed in a way to minimize obstructions to
the space above the fireplace. Do not insulate the space between the fireplace and the area above it (Table 9). The minimum height from
the base of the fireplace to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Table 9.
Table 9- Combustible Shelf Height—Top Vent
(55" models require 12" of vertical rise directly off unit)
Model
35" Models
45" Models
55" Models
CLEARANCES TO COMBUSTIBLES MUST BE MAINTAINED
No combustible materials or insulation is permitted in the shaded area
between the appliance and the shelf above it.
WARNING
: CRITICAL INSTALLATION INFORMATION THAT IF NOT FOL-
LOWED CAN RESULT IN A SAFETY HAZARD!
Top Vent with one 90° Elbow *
Secure Vent
®
(using rigid elbow)
47" (1194 mm)
52" (1321 mm)
62" (1575 mm)
Table 8 - Minimum Clearances *
From Bottom of Unit to Ceiling
Front Service Clearance—
clearance immediately in front of
*
3" (77 mm) above any horizontal/inclined vent component.
** See Page 23 for clearance requirements to the nailing flange
located at each side of the unit and any screw heads adjacent to it.
*** 6" (153 mm) if optional facade is used.
Secure Flex
®
(using flex elbow)
49" (1245 mm)
54" (1372 mm)
64" (1626 mm)
:
900994-00K, 07/2021
1/2" (13 mm) to wrapper
Back ***
0" (0 mm) to Spacers
1/2" (13 mm) to wrapper
Sides
0" (0 mm) to Spacers **
Top Standoffs
0" (0 mm) to top standoffs
Floor
0" (0 mm) ***
52" (1321 mm)
3" (77 mm)—Top *
Vent
1" (26 mm)—Sides and Bottom
36" (914 mm)
viewing area(s)
Shelf Height
(see table)
The unit is
required to be a
minimum of 6"
off floor to install
optional facade.