Gas Valve Proving - Siemens LMV50 Series Manual

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

Example
Mains
t80
Figure 30: Gas valve proving
Building Technologies

4.2.2 Gas valve proving

Gas valve proving is only active when firing on gas.
When a leak is detected, the gas valve proving function ensures that the gas valves are
not opened and that ignition is not switched on. Safety shutdown is initiated.
DW
DK
t81
t82
t83
The valve proving function can be parameterized and the time selected:
During startup (between phases 30 and 32)
During shutdown (between phases 62 and 70)
During startup and during shutdown
Basic Documentation LMV5...
4 Burner control
Step 1: t80
Evacuate the test space
With gas valve proving, first the gas valve on the burner
side is opened to bring the test space to atmospheric
pressure.
Step 2: t81
Atmospheric pressure test
After closing the gas valve, the pressure in the test space
is not allowed to rise above the switching point of pressure
switch-valve proving (e.g. gas pressure in operation x 0.5).
Step 3: t82
Fill test space
Then, the gas train is filled by opening the gas valve on the
gas network side.
Step 4: t83
Gas pressure test
After closing the gas valve, the gas pressure is not allowed
to fall below the switching point of pressure switch-valve
proving (e.g. gas pressure in operation x 0.5).
Input / output signal 1 (ON)
Input / output signal 0 (OFF)
Input, permissible signal 1 (ON) or 0 (OFF)
Pressure switch-valve proving
DW-DK
Fuel valve
V...
61/327
CC1P7550en
22.05.2018