7.5 Actual values (X)

Measuring accuracy: Min. °1% of the measuring range (excluding the sensor error).
Definition of sensors (incl. activation / deactivation of the temperature limiter
function):
Pt100
Temperature sensor Pt100 at the input X60, internal temperature limiter
function =
Pt1000
Temperature sensor Pt1000 at the input X60, internal temperature limiter
function =
Ni1000
Temperature sensor LG-Ni1000 at the input X60, internal temperature
limiter function =
TempSensor
Temperature sensor at the input X61, internal temperature switch
function =
PressSensor
Pressure sensor at the input X61, internal temperature switch
function
Pt100Pt1000
Temperature sensor
and temperature limiter function
input X60 additionally for temperature limiter function.
Pt100Ni1000
Temperature sensor
temperature limiter function and temperature sensor
additionally for temperature limiter function
No Sensor
No actual value sensor (e.g. in the case of external predefined loads
and
without
PhysicalUnits ( ↓C / bar / °F / psi)
Parameter
SensorSelect (Pt100 / Pt1000 / Ni1000 / TempSensor / PressSensor /
Pt100Pt1000 / Pt100Ni1000 / No Sensor)
Basic Documentation LMV5...
7 Boiler controller / load controller
activated
.
activated
.
activated
.
deactivated
.
deactivated
=
.
at input X60 for temperature controller
Pt100
and
Pt100 at input X60 for temperature controller and
internal temperature limiter)
temperature sensor
Pt1000 at
LG-Ni
at input X60
.
.
CC1P7550en
22.05.2018
117/327