Description of connection terminals (cont'd)
Connection symbol
X50
X51
X52
Building Technologies
PIN 6
˜ Reference ground (PELV)
PIN 5
˜ Communication signal (CANL)
PIN 4
˜ Communication signal (CANH)
III
PIN 3
˜
PIN 2
˜
PIN 1
˜ Shield connection (functional earth)
PIN 6
˜ Reference ground (PELV)
PIN 5
˜ Communication signal (CANL)
PIN 4
˜ Communication signal (CANH)
III
PIN 3
˜
PIN 2
˜
PIN 1
˜ Shield connection (functional earth)
PIN 4
˜
PIN 3
˜
III
PIN 2
˜
PIN 1
˜
Basic Documentation LMV5...
12 Description of connection terminals (AC 230 V)
Description of connections
AC power supply for actuators / display
and operating unit AZL5
AC power supply for actuators / display
and operating unit AZL5
Functional earth
AC power supply from transformer to
LMV5 system
Reference ground (PELV)
AC power supply from transformer to
LMV5 system
Electrical rating
DC U ↔ 5 V, Rw = 120 ς,
level to ISO-DIS 11898
AC 12 V +10 % / -15 %,
50...60 Hz,
Fuse max. 4 A
DC U ↔ 5 V, Rw = 120 ς,
level to ISO-DIS 11898
AC 12 V +10 % / -15 %, 50...60 Hz,
Fuse max. 4 A
AC 12 V +10 % / -15 %, 50...60 Hz
AC 12 V +10 % / -15 %, 50...60 Hz
211/327
CC1P7550en