Siemens LMV50 Series Manual page 177

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

21. Checking and
presetting the ignition
positions for firing on oil
Menu level 1
Menu level 2
Params & Display
RatioControl
22. Manual startup
Menu level 1
Menu level 2
ManualOperation
Autom/Manual/Off
23. Actuator positions
during the prepurge time
Menu level 1
Menu level 2
Params & Display
RatioControl
Β
Building Technologies
For the parameters HomePos, Prepurge position and Postpurge position, the parameter
set supplied offers presettings. These should be checked and, if necessary, adapted,
either now or during the following program stops.
There is no presetting for the ignition position. In this section, a valid setting must be
made because otherwise, the burner cannot be started up.
Menu level 3
OilSettings
Example:
Auxiliary actuator: 22.5° Air actuator: 37.6°
These values are also transferred to operating point S1 even if it has not yet been set.
To start the burner, select Autom/Manual/Off, and then Manual.
Menu level 3
If startup shall be watched, the display can be changed to Normal operation by
pressing simultaneously selection buttons «<» and «>».
The burner control stops startup in the prepurge phase (phase 24), enabling the
positions of the actuators for prepurging to be straightforwardly set.
Menu level 3
OilSettings
Note!
The prepurge position of auxiliary actuator 3 is approached in phase 32 (flue gas
recirculation (FGR)).
After the settings are made, the program stop in the prepurge position should be
replaced by the program stop of the ignition position in phase 36.
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
SpecialPositions
IgnitionPos
Menu level 4
Menu level 5
Menu level 4
Menu level 5
SpecialPositions
PrepurgePos
Menu level 6
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux1
IgnitionPosAux2
Only LMV52
IgnitionPosAux3
LMV50/LMV51.3/
IgnitionPosVSD
LMV52
Menu level 6
Menu level 6
PrepurgePosAir
PrepurgePosAux1
PrepurgePosAux2
only LMV52
PrepurgePosAux3
LMV50/LMV51.3/
PrepurgePosVSD
LMV52
177/327
CC1P7550en
22.05.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents