4. Setting the ignition positions
The system continues the startup sequence and stops in phase 36 IgnitPos. Now, the
ignition positions can be set on menu SpecialPositions.
Then, set ProgramStop to 72 PostPPos, if operation shall immediately follow.
To readjust the ignition positions after the burner has ignited: Set ProgramStop to 44
Interv 1 or 52 Interv 2 for pilot ignition after the pilot flame has been shut down. Then,
set ProgramStop to 72 PostPPos.
5. Curve settings via manual control
The system continues the startup sequence and assumes normal operation. The first
curvepoint entered are the ignition positions and the load entered is the number of
degrees (angular rotation) of the fuel actuator.
90°
Pos.
AIR
FUEL
AUX
0 %
7550d07e/0704
Figure 78: Adjustment of the actuator positions via the load with automatically entered point
Select Man from menu Params & Display ↑ RatioControl ↑ Settings Gas or Oil ↑
Curve Param. It is now possible to follow the above curves by changing the load. A point
can be saved at every intermediate point. Than the figure of the adjustment of the
actuator positions via the load will change as follows:
90°
Pos.
0 %
7550d08e/0704
Figure 79: Adjustment of the actuator positions via the load with 2 points
Basic Documentation LMV5...
8 Display and operating unit AZL5
100 %
Load
AIR
FUEL
AUX
100 %
Load
157/327
CC1P7550en
22.05.2018