Every time the burner is started up, the measured residual O2 content is compared with
the O2 content of the ambient air at the end of prepurging.
This test detects offset errors of the measuring cell.
Normally, this value reads 20.9%, but it can be parameterized in the case of plants that
operate with enriched air.
Parameter
Gas: O2 Content Air
Oil: O2 Content Air
For the QGO20, the tolerance band for checking the O2 content is = ±2%.
If the O
content lies outside the tolerance band of ±2%, one of the following reactions
2
takes place, depending on the parameterization of O2Contr/Alarm.
man deact
O2 trim controller and O2 alarm are deactivated. No O2 test is made
(auto deact):
O2 Alarm / O2
O2 trim controller / O2 alarm is / are activated. If the test is negative,
Control:
safety shutdown is initiated, followed by a repetition if possible,
otherwise lockout
conAutoDeac:
O2 trim controller and O2 alarm are activated.
If the test is negative, both the O2 trim controller and the O2 alarm
are deactivated.
Caution!
For that purpose, the prepurging time of the LMV52 must be parameterized such
that the combustion chamber and the flueways will be completely purged.
The correct setting of the air's O2 content is safety-related.
Basic Documentation LMV5...
19 O2 trim control with LMV52 and PLL52
CC1P7550en
22.05.2018