Run time measurement
Hide thumbs Also See for Fieldbus Levelflex M FMP43:
Table of Contents

Advertisement

Quick Links

Operating Instructions
Levelflex M FMP43
Run Time Measurement
9
BA359F/00/en/03.09
No. 71074939
Valid as of software version:
01.04.zz

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Fieldbus Levelflex M FMP43

  • Page 1 Operating Instructions Levelflex M FMP43 Run Time Measurement BA359F/00/en/03.09 No. 71074939 Valid as of software version: 01.04.zz...
  • Page 2 Commissioning via Endress+Hauser operating program In the "Commissioning" section, you learn how to switch on the instrument and check the functions. Additional information on the operation via the Endress+Hauser operating program (FieldCare) can be found in Operating Instructions BA027S/04. Æ...
  • Page 3 An overview of all the instrument functions can be found on → ä 98. An extensive description of all the instrument functions can be found in BA245F – "Description of Instrument Functions" on the CD-ROM provided. Operating Instructions can also be found on our homepage: www.endress.com Endress+Hauser...
  • Page 4 Brief overview Levelflex M FMP43 with FOUNDATION Fieldbus Endress+Hauser...
  • Page 5: Table Of Contents

    Recommended connection ....31 Contact addresses of Endress+Hauser ... 87 Degree of protection ..... . . 31 Post-connection check .
  • Page 6: Safety Instructions

    The instrument is accompanied by separate “Ex documentation”, which is an integral part of this documentation. The installation regulations, connection values and safety instructions listed in this document must be observed. • Ensure that all personnel are suitably qualified. • Measuring point requirements with regard to measurement and safety must be observed. Endress+Hauser...
  • Page 7: Notes On Safety Conventions And Icons

    Temperature resistance of the connecting cables t >85°C Indicates that the connecting cables have to withstand a temperature of 85 C at least. Safety instruction For safety instructions refer to the manual for the appropriate instrument version. Endress+Hauser...
  • Page 8: Identification

    2.1.1 Nameplate The following technical data are given on the instrument nameplate: Order No Designation according to Directive 94/9/EC (see Order Information) and designation of protection ENDRESS+HAUSER Made in Germany Serial number LEVELFLEX-M D-79689 Maulburg Order Code: Ser.-No.: IP68 / NEMA 6P...
  • Page 9 EN10204-3.1 material (316L wetted parts), inspection certificate CoC, EN 10204-3.1 material (316L wetted parts) inspection certificate *5-point, CoC, 3.1, 5-point linearity protocol, see additional spec., EN10204-3.1 material (316L wetted parts), inspection certificate Special version, to be specified Marking: 1 Tagging (TAG) 2 Bus address Endress+Hauser...
  • Page 10 You can fill in the options of the respective feature into the following table. The filled in options result in the complete order code. FMP43- complete product designation ⇓ Please enter probe length in mm or inch / 0.1 inch inch / 0.1 inch probe lenght LN → Page 14 OVP = overvoltage protection Endress+Hauser...
  • Page 11: Scope Of Delivery

    The instrument takes into account applicable standards and regulations which are listed in the EC declaration of conformity and thus meets the legal requirements of the EC Directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
  • Page 12: Installation

    Pack the measuring instrument in such a way as to protect it reliably against impact for storage and transportation. The original packing material provides the optimum protection for this. The permissible storage temperature is -20 °C to +80 °C. Endress+Hauser...
  • Page 13: Installation Conditions

    Installation Installation conditions 3.2.1 Dimensions Housing (see feature 80 in "Ordering information") - dimensions and materials Dimensions for the process connection and the probe type → ä 14. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing...
  • Page 14 - 20 °C to 149 °C (3A Class. I, USP Cl. VI) ➂ Probe (see Feature 20 in "Ordering information) Material Version Option ➂ 0.76 μm mechanically polished K, M 316L (1.4435) 0.38 μm electropolished S, T Hastelloy C22 Special version available on request process connection (example) Endress+Hauser...
  • Page 15 Process connections (see Feature 40 in "Ordering information") - Dimensions and materials Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L with the material number 1.4435 or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together und 13E0 in EN1092-1 Tab.18. The chemical composition of the two materials can be identical.
  • Page 16 • 0.38 μm electropolished Ø 42,9 NEUMO BioControl DN25 PN16* = 16 bar 30,4 30,4 1-1/2" 150lbs RF Flange ANSI B16.5* = 16 bar 17,5 • 0.76 μm 2" 150lbs RF 152,4 Flange ANSI B16.5* = 16 bar 19,1 Endress+Hauser...
  • Page 17 Levelflex M FMP43 with FOUNDATION Fieldbus Installation Process connection Designation Versions Approvals Option Thread M24 x 1.5 Accessory: weld-in adapter Weld-in adapter • 0.76 μm order number: 71041381 = 16 bar Ø 65 All metal parts used in the process in 316L (1.4435) Endress+Hauser...
  • Page 18: Installation Instructions

    Optimization options • Interference echo suppression: measurement can be optimized by electronically suppressing interference echoes. L00-FMP43xxx-17-00-00-xx-002 Note! You must ensure that the probe does not come into contact with the container wall, container bottom and tank internals. Endress+Hauser...
  • Page 19 Density [ρ] in kg/m 1000 (e.g. water) Probe diameter [d] in m 0.008 L = L (worst case) L00-FMP43xxx-16-00-00-xx-003 Bending torque [M] on rod probes 20.0 18.0 16.0 14.0 12.0 10.0 v=0.5m/s v=0.7m/s v=1.0m/s Probe length [ ] in meters L00-FMP43xxx-16-00-00-de-004 Endress+Hauser...
  • Page 20 • For mechanical reasons, the probe should be installed as vertically as possible. • The maximum mounting angle is – up to 1 m = 30° – up to 2 m = 10° – up to 4 m = 5°. L00-FMP43xxx-17-00-00-xx-006 Endress+Hauser...
  • Page 21 ≥ DN 50 / 2" metallic flange, or a metal sheet with diameter ≥ 200 mm must be mounted under the screw-in piece. metal sheet or metal flange silo roof of plastic or wood metal sheet or metal flange Wall thickness for GFK/PP < 15 mm L00-FMP4xxxx-17-00-00-en-018 Endress+Hauser...
  • Page 22 • The wall retainer can also be used for mounting in display panels. Please observe the dimensions on → ä 13 for the cutout. display plate wall ENDRESS+HAUSER Levelflex M 4 x Ø 8,5 Ø 5 ENDRESS+HAUSER Levelflex M pipe Ø...
  • Page 23: Post-Installation Check

    • Does the instrument correspond to specifications at the measuring point, including process temperature and pressure, ambient temperature, measuring range, etc.? • Are the measuring point number and labeling correct (visual inspection)? • Is the instrument adequately protected against rain and direct sunlight (→ ä 78)? Endress+Hauser...
  • Page 24: Cleaning Of The Probe

    Installation in the center of the tank • If the probe is mounted in the center of the tank, it may be necessary to use a second spray ball. The spray balls should then be mounted to the left and right of the probe. L00-FMP43xxx-17-00-00-xx-004 Endress+Hauser...
  • Page 25 4.5 Nm. • The O-rings r of the probe rod and adapter are now free accessible respectively L00-FMP43xxx-17-00-00-xx-007 changeable. The probe rod can be cleaned (autoclaved). O-ring order numbers, see → ä 86. Endress+Hauser...
  • Page 26 • screw the adapter into the container process connection together with the probe rod and tighten with 20 Nm • stick housing n with housing adapter on the adapter and bolt it with the grooved nut m - torque 20 Nm. Endress+Hauser...
  • Page 27: Wiring

    Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the FOUNDATION Fieldbus Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M standard and the desired safety concept. (e.g. FISCO). D-79689 Maulburg Order Code: Ser.-No.:...
  • Page 28 Wiring in T12 housing " Before connection please note the following: FOUNDATION Fieldbus devices are marked on the nameplate (1). The voltage is determined by the Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M FOUNDATION Fieldbus standard and the desired safety D-79689 Maulburg Order Code: concept.
  • Page 29 Levelflex M FMP43 with FOUNDATION Fieldbus Wiring Wiring with FOUNDATION Fieldbus connector " Before connection please note the following: ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg ● Foundation Fieldbus devices are marked on the Order Code: Ser.-No.: IP68 / NEMA 6P nameplate (1).
  • Page 30: Connecting The Measuring Unit

    There may be additional restrictions for instruments with an explosion protection certificate. Refer to the notes in the appropriate safety instructions (XA). Current consumption Nominal current 15 mA ≤ 15 mA Starting current Error current 0 mA FISCO/FNICO conformal compliant Polarity sensitive Endress+Hauser...
  • Page 31: Recommended Connection

    • Is the terminal assignment correct (→ ä 27 and → ä 28)? • Is the cable gland tight? • Is the FOUNDATION Fieldbus connector screwed tight? • Is the housing cover screwed tight? • If power is supplied: Is the instrument ready for operation and is the LCD display lit? Endress+Hauser...
  • Page 32: Operation

    •Chap. 5.1 Quick operation guide •Chap. 5.2 Operation with the display and operating module VU331 •Chap. 5.3 Operation with an Endress+Hauser operating program •Chap. 5.4 Operation with a FOUNDATION Fieldbus configuration program •Chap. 5.5 Operation with the handheld terminal Field Communicator 375/FC375...
  • Page 33 On-site operation Options for on-site operation •Display and operating module VU331 •Endress+Hauser operating software ("FieldCare") Parameter access by on-site operation The following parameters can be accessed by on-site operation: •Parameters of the instrument specific blocks (Sensor Block, Diagnostic Block, Display Block) •Endress+Hauser service parameters...
  • Page 34: Operation With The Display And Operating Module Vu331

    FG03 FG04 FG05 FG06 Envelope FG07 curve L00-FMRxxxxx-07-00-00-en-007 In the measured value display, the bargraph corresponds to the output. The bargraph is segmented in 10 bars. Each completely filled bar represents a change of 10% of the adjusted span. Endress+Hauser...
  • Page 35 Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Endress+Hauser...
  • Page 36 The third digit numbers the individual functions within the function group: → •tank properties •basic setup •medium property •process cond..Hereafter the position is always given in brackets (e.g. "tank properties" (002)) after the described function. Endress+Hauser...
  • Page 37 Press F to select the next function. Press O and S (= Q) once; return to previous function. Press O and S (= Q) twice; return to Group Selection. Press O and S (= Q) to return to Measured value display. Endress+Hauser...
  • Page 38: Operation With An Endress+Hauser Operating Program

    Operation with an Endress+Hauser operating program 5.3.1 FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser instruments as well as instruments from other manufacturers that support the FDT standard. The following operating systems are supported: Win2000, Windows XP and Windows Vista.
  • Page 39 Levelflex M FMP43 with FOUNDATION Fieldbus Operation Menu-guided commissioning L00-FMP4xxxx-20-00-00-en-001 Signal analysis via envelope curve L00-FMP4xxxx-20-00-00-en-007 Endress+Hauser...
  • Page 40 Operation Levelflex M FMP43 with FOUNDATION Fieldbus Tank linearisation L00-fmp-Ixxx-20-00-00-en-041 Endress+Hauser...
  • Page 41: Operation With A Foundation Fieldbus Configuration Program

    *.cff The directory names have the following meaning: •452B48: manufacturer ID of Endress+Hauser •1012: ID-Code of Levelflex M "Instrument Revision" (0C3) and "DD Revision" (0C4) can be obtained through the display and operating module VU331. For details refer to section 5.2: "Operation with the display and operating module VU331"...
  • Page 42: Operation With The Handheld Terminal Field Communicator 375/Fc375

    A FOUNDATION Fieldbus configuration tool offers two types of parameter representation: •Representation by parameter name Examples: "PAROPERATIONCODE", "PARRESET" •Representation by parameter label (identical to the labels on the display module VU331 and in an Endress+Hauser operation tool) Examples: "unlock parameter", "reset" Operation with the handheld terminal Field Communicator 375/FC375 5.5.1...
  • Page 43 CANCEL HELP Page Delete dsdmdm df das. asdas fa asas la. basic setup Levelflex M E+H_LEVELFLEX_M_XXXXXX tank properties: standard Endress+Hauser Device Revision 4 standard Block Tag Block Type Actual Mode aluminium tank RESOURCE... RES_BL... Auto plastic tank SENSOR_B... Custom bypass / pipe DIAGNOSTI...
  • Page 44: Commissioning

    • Chap. 6.6 "Blocking distance" • Chap. 6.7 "Envelope curve" • Chap. 6.8 "Basic setup with the Endress+Hauser operating program" • Chap. 6.9 "Commissioning with a FOUNDATION Fieldbus configuration tool" • Chap. 6.10 "Commissioning with the handheld terminal Field Communicator 375/FC375"...
  • Page 45 Enter "2457". Now parameters can be changed. Parameters affected Locking by the key combination affects the following parameters: • Parameters of the instrument specific blocks (Sensor Block, Diagnostic Block, Display Block) • Endress+Hauser service parameters 6.2.3 Locking parameter Locking Enter a number other than "2457" into the "unlock parameter" (0A4) function.
  • Page 46: Resetting The Instrument

    Sensorblock AI-Block 1 Input-Selector-Block Diagnoseblock AI-Block 2 Signal-Charact.-Block Display-Block PID Block Integrator-Block Endress+Hauser Service-Parameter L00-FMU4XXXX-02-00-00-YY-007 Performing the reset Resource Block, parameter RESTART; select the option "defaults". 6.3.2 Resetting the parameters of the transducer blocks " Caution! A reset may lead to impairment of the measurement. As a rule, a basic calibration is required after a reset.
  • Page 47 – "inactive": deactivates the tank map but does not delete it. It can be re-activated when required. – "active": activates the tank map. Resetting the tank map with an Endress+Hauser operating program In the function group "extended calibr." select the "cust. tank map" (055) function. Select the required option ("reset", "inactive" or "active") Resetting the tank map with a FOUNDATION Fieldbus configuration tool In the Sensor Block select the parameter PARCUSTTANKMAP (cust tank map).
  • Page 48: Basic Setup

    F = full calibr. (= span) UB = upper blocking distance setting in 006 setting in 059 D = distance (distance flange / product) SD = safety distance display in 0A5 setting in 015 = level linearisation display in 0A6 extended calibr. L00-FMP4xxxx-19-00-00-en-003 Endress+Hauser...
  • Page 49 • If the power supply fails, all preset and configured values remain safely stored in the EEPROM. " Caution! All functions are described in detail, as is the overview of the operating menu itself, in BA245F - "Description of Instrument Functions" on the CD-ROM supplied. Endress+Hauser...
  • Page 50: Commissioning By The Display And Operating Module Vu331

    Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals" (095) function. Endress+Hauser...
  • Page 51 Select the "coax probe" option when using a coaxial probe. When this setting is made, the evaluation is adapted to the high sensitivity of the coax probe. This option should, therefore, not be selected when using a rope or rod probes. Endress+Hauser...
  • Page 52 • extremly loose surfaces of bulk solids, e.g. bulk solids with low piled density when filled pneumatically. • Build-up, primarily of moist products. Note! Due to the high diffusion rate of ammonia it is recommended to use the FMP45 with gas-tight bushing for measurements in this medium. Endress+Hauser...
  • Page 53 The signal from the probe end is positive if the attachement is grounded. Only the setting "free" is permitted for the FMP43. Selection: • free • tie down isol. • tie down gnd. These settings lead to a false output signal for empty tanks.. Endress+Hauser...
  • Page 54 (034) function. If the probe is covered, a correct entry is required in the "probe length" (033) function. Selection: • free • covered Function "probe length" (033) ⇒ ENDRESS + HAUSER – Use this function, the probe length can be entered manually. Endress+Hauser...
  • Page 55 10 s. Function "empty calibr." (005) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero). E = empty calibration (= zero) L00-FMP4xxxx-14-00-06-en-008.eps Endress+Hauser...
  • Page 56 • Distance correct – meas. value correct -> continue with the next function "check distance" (051). • Distance correct – meas. value incorrect -> Check "empty calibr." (005) • Distance incorrect – meas. value incorrect -> continue with the next function "check distance" (051). Endress+Hauser...
  • Page 57 The following options are available: Options: • Distance = ok • Dist. too small • Dist. too big • Dist. unknown • Manual • Probe free distance too small distance = ok L00-FMP4xxxx-14-00-06-en-010 Endress+Hauser...
  • Page 58 Function "start mapping"(053) ⇒ ENDRESS + HAUSER – This function is used to start the interference echo suppression up to the distance entered in "range of mapping" (052). Options: • Off: no mapping is carried out • On: mapping is started Endress+Hauser...
  • Page 59 After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve ("envelope curve" (0E) function group) (→ ä 62). Return to group selection After the interference echo suppression the basic setting is finished and the instrument jumps automatically back into the group selection. Endress+Hauser...
  • Page 60: Blocking Distance

    The blocking distance is preset to 0.2 m for rod probes. The blocking distance can be reduced if the probe is mounted flush with the wall or in a nozzle, max. 50 mm in height. When using a spray ball the blocking distance may not be smaller than 50 mm. Endress+Hauser...
  • Page 61 - 20 mm - 30 mm (water-based - 40 mm DK > 7 medium) - 50 mm oils and solvents - 60 mm DK = 2 100 mm 200 mm 200 mm 80 mm 40 mm 20 mm L00-FMP43xxx-05-00-00-en-001 Endress+Hauser...
  • Page 62: Envelope Curve

    L00-FMPxxxxx-07-00-00-en-003 Endress+Hauser...
  • Page 63 This threshold depends on the location and is automatically calculated from the ideal echo curve of the probe used. The calculation of the threshold in question depends on the "Installation" customer parameter in the extended calibration function. Endress+Hauser...
  • Page 64 Vertical Zoom mode Press once more to switch to Vertical Zoom mode. is displayed. You now have the following options. • increases the vertical scale. • reduces the vertical scale. The display icon shows the current zoom factor ( L00-FMPxxxxx-07-00-00-xx-003 Endress+Hauser...
  • Page 65: Basic Setup With The Endress+Hauser Operating Program

    The set increases and shifts are retained. Only when you reactivate the "recording curve" (0E2) function the display settings return to their standard values. Basic setup with the Endress+Hauser operating program To carry out the basic setup with the operating program, proceed as follows: •...
  • Page 66 • Enter the application parameters (see chapter basic setup with "VU331"): – tank properties – medium properties – process properties l00-fmp4xxxx-20-00-00-en-002 Basic setup step 3/6: • Enter the application parameters (see chapter basic setup with "VU331"): – end of probe l00-fmp4xxxx-20-00-00-en-003 Endress+Hauser...
  • Page 67 • Enter the application parameters (see chapter basic setup with "VU331"): – probe length – probe – probe length – determine length l00-fmp4xxxx-20-00-00-en-004 Basic setup step 5/6: • Enter the application parameters (see chapter basic setup with "VU331"): – empty calibration – full calibration l00-fmp4xxxx-20-00-00-en-005 Endress+Hauser...
  • Page 68 Signal analysis via envelope curve After the basic setup, it is recommended to evaluate the measurement with the aid of the envelope curve. L00-FMP4xxxx-20-00-00-en-007 Note! In the event of severe interference echoes, installing the Levelflex at another point can optimize the measurement routine. Endress+Hauser...
  • Page 69 Level echoes are indicated as positive signals in the envelope curve. Interference echoes can be both positive (e.g. reflections from internals) and negative (e.g. nozzles). The envelope curve, the map and the differential curve are used for the evaluation. Level echoes are searched for in the differential curve. Endress+Hauser...
  • Page 70 0.00 0.20 0.40 0.60 0.80 1.00 Differential curve = Envelope curve Mapping L00-FMP40xxx-05-00-00-en-025 6.8.2 User-specific applications (operation) For details of setting the parameters of user-specific applications, see separate documentation BA245F – "Description of Instrument Functions" on the CD-ROM supplied. Endress+Hauser...
  • Page 71: Commissioning With A Foundation Fieldbus Configuration Tool

    For commissioning of the instrument with a FOUNDATION Fieldbus configuration tool you need to know the INSTRUMENT_ID, which consists of the following parts: Instrument_ID = 452B481012-XXXXXXXX whereby: 452B48 ID code for Endress+Hauser 1012 ID code for Levelflex M XXXXXXXX Instrument serial number, as printed on the nameplate 6.9.1 Fist setup Open the configuration tool and load the Instrument Descriptions (*.ffo, *.sym and - if...
  • Page 72 • You can open one of the FOUNDATION Fieldbus methods. Each method guides you automatically through a number of parameters which are required for a specific configuration task. The following sections describe the parametrization by the "basic setup" method. Open the FOUNDATION Fieldbus method "basic setup": Endress+Hauser...
  • Page 73 – by the display and operating module VU331 (see section 6.4.5) – by an Endress+Hauser operating program (see section 6.5.1) In the FOUNDATION Fieldbus configuration tool you can select from two types of parameter display: - parameter names (e.g. "PARTANKSHAPE") - label texts (e.g.
  • Page 74 – HI_LIM -> Limit value for the upper warning – LO_LIM -> Limit value for the lower warning – LO_LO_LIM -> Limit value for the lower alarm The limit values entered must be within the value range specified in the parameter group OUT_SCALE. Endress+Hauser...
  • Page 75 TARGET). However, this is only possible under the following conditions: – The function blocks are correctly connected with each other. – The parametrization of the AI Block is correct (see 6.6.4, steps 5 and 6). – The Resource Block is in operating mode AUTO. Endress+Hauser...
  • Page 76: Commissioning With The Handheld Terminal Field Communicator 375/Fc375

    (→ Chap. 6.9). The blocks should be parametrized in the following order: • the RESOURCE BLOCK • the SENSOR BLOCK (the "basic setup" method can be used for this, see chapter "basic setup") • the ANALOG INPUT BLOCKS Endress+Hauser...
  • Page 77: Maintenance

    The Endress+Hauser repair concept assumes that the measuring instruments have a modular design and that customers are able to undertake repairs themselves (see Chap. 9.4 "Spare Parts" → Page 86). Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 78: Accessories

    Welding adapter with M 24 x of 1.5 - threads for the front-concise assembly of the sensor. Material: corrosion-resistant steel 1.4435 (AISI 316L) Ø 65 Weight: 0.22 kg For details refer to BA361F/00/A6. L00-FMP43xxx-06-00-00-xx-016 • Standard Order No.: 71041381 • With 3.1 inspection certificate Order No.: 71041383 Endress+Hauser...
  • Page 79: Remote Display And Operation Fhx40

    Basic version Mounting bracket, pipe 1"/ 2" Special version, to be specified Marking: Tagging (TAG) FHX40 - Complete product designation For connection of the remote display FHX40 use the cable which fits the communication version of the respective instrument. Endress+Hauser...
  • Page 80: Commubox Fxa291

    Levelflex M FMP43 with FOUNDATION Fieldbus Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB port of a computer or laptop. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory: •...
  • Page 81: Troubleshooting

    Connect the plug Ready Display works? of the display. correctly Output current between The display is possibly defective. 3.6 …22mA ? Contact Endress+Hauser Service Communication via Service adapter Not ok Check configuration Correct configuration Communication ok? Ready does not function...
  • Page 82: System Error Messages

    A251 feedthrough lost contact in the process feedthrough replace process feedthrough Endress+Hauser...
  • Page 83 A671 linearization ch1 not linearization table is in edit mode activate linearization table complete, not usable W681 current ch1 out of range current out of range check basic setup and linearization (3.8 mA to 21.5 mA) Endress+Hauser...
  • Page 84: Application Errors

    Noise level during the Repeat empty calibr. (005) once echo) after event of echo loss the output is set to any initialization phase too more. switching on the value/current. high. Caution! power supply Before confirmation change with to the edit mode. Endress+Hauser...
  • Page 85 (slope incorrect. properties selected → error in the entire Calibration not possible. 100% → measuring range) Selection expected → Select standard → Thresholds too high 2.) actual 1.) actual t → L00-FMP4xxxx-19-00-00-en-021 Medium properties Select lower medium properties. incorrect. Endress+Hauser...
  • Page 86: Spare Parts

    Select the required spare parts (You may also use the overview drawing on the right side of the screen.) When ordering spare parts, always quote the serial number indicated on the nameplate. As far as necessary, the spare parts also include replacement instructions. Endress+Hauser...
  • Page 87: Return

    Instrument Functions 07.2007 01.04.02 Original-Software. BA359F/00/en/07.07 BA245F/00/de/07.07 71041165 71040940 BA359F/00/en/03.09 71074939 Contact addresses of Endress+Hauser Contact addresses can be found on our homepage: www.endress.com/worldwide. If you have any questions, please do not hesitate to contact your Endress+Hauser representative. Endress+Hauser...
  • Page 88: Technical Data

    Instrument Revision 04 (hex) DD Revision 02 (hex) CFF Revision 02 (hex) ITK Version 4.61 ITK-Certification Driver-No. www.endress.com / www.fieldbus.org Link-Master (LAS) cabable Link Master / Basic Instrument selectable yes; Default: Basic Devce Number VCRs Number of Link-Objects in VFD Endress+Hauser...
  • Page 89 The signal characterizer block has two sections, each 40 ms standard Characterizer with an output that is a non-linear function of the Block respective input. The non-linear function is determined by a single look-up table with 21 arbitrary x-y pairs. Endress+Hauser...
  • Page 90 Lift-off voltage Basic current max. 15 mA ≤ 15 mA In-rush current FISCO = 17,5 V = 500 mA; with overvoltage protection 273 mA = 5,5 W; with overvoltage protection 1,2 W = 5 nF = 0,01 mH FNICO Polaritätsabhängig Endress+Hauser...
  • Page 91 The measurements are carried out in accordance with EN 61298-3: temperature • Digital output (HART, PROFIBUS PA, FOUNDATION Fieldbus): – average T : 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C to +80 °C Endress+Hauser...
  • Page 92 Thick layers can dampen the signal and then reduce the measuring range. Heavy, uneven buildup, adhesion through crystallization, for example, can lead to incorrect measurement. In such instances, we recommend you use a non-contact measuring principle, or check the probe regularly for soiling. Endress+Hauser...
  • Page 93 • ASME B 16.5a - 1998 Tab. 2-2.2 F316 • ASME B 16.5a - 1998 Tab. 2.3.8 N10276 • JIS B 2220 See chapter "Dimensions" from → ä 13. Materials in contact with process ε r ≥ 1.6 Dielectric constant Endress+Hauser...
  • Page 94 See "Ordering structure" on → ä 8. Process connection See "Ordering structure" on → ä 8. Probe Note! The modular structure of the probe makes a simple possible exchanges of the process seals, the probe rod and the process coupling ring. Endress+Hauser...
  • Page 95 The measuring system meets the legal requirements of the applicable EC guidelines. These are listed in the corresponding EC Declaration of Conformity together with the standards applied. Endress+Hauser confirms successful testing of the instrument by affixing to it the CE mark. Certificates The instruments are certified for use in hazardous areas.
  • Page 96 The gap-free connections can be cleaned without residue using the usual cleaning methods. Many versions of the Levelflex M meet the requirements of 3A-Sanitary Standard No. 74. Endress+Hauser confirms this by attaching the 3A symbol. Pharma (CoC) Certificate of Compliance (CoC) •...
  • Page 97 Levelflex M FMP43 with FOUNDATION Fieldbus Technical data Endress+Hauser...
  • Page 98: Appendix

    Note! The default values of the parameters are typed in boldface. L00-FMP4xxxx-19-00-01-en-022 Endress+Hauser...
  • Page 99 . point , comma detection window measured dist. measured level application par. not modified modified reset distance unit download mode L00-FMP4xxxx-19-00-02-en-022 Endress+Hauser...
  • Page 100: Description Of Functions

    The dielectric constant (DK) of the medium has a direct impact on the degree of reflection of the high-frequency pulses. In the case of large DK values, such as for water or ammonia, there is strong pulse reflection while, with low DK values, such as for hydrocarbons, weak pulse reflection is experienced. Endress+Hauser...
  • Page 101 • with a Personal Computer, FXA291 and ToF Adapter FXA291 (USB) and the operating software "FieldCare". The FieldCare is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 102: Index

    Mediumeigenschaften ......52 Messbedingungen ......53 Endress+Hauser...
  • Page 103 Erklärung zur Kontamination und Reinigung Please reference the Return Authorization Number (RA#), obtained from Endress+Hauser, on all paperwork and mark the RA# clearly on the outside of the box. If this procedure is not followed, it may result in the refusal of the package at our facility.
  • Page 104 www.endress.com/worldwide BA359F/00/en/03.09 No. 71074939 71074939 CCS/FM+SGML 6.0/ProMoDo...

Table of Contents