Hydrostatic level measurement pressure sensor with the contitetm measuring cell condensate-resistant offering long-term stability; communication via hart, profibus pa or foundation fieldbus (72 pages)
Capacitive continuous level measurement for liquids (48 pages)
Summary of Contents for Endress+Hauser Deltapilot M FMB50
Page 1
Operating Instructions pertaining to the device. Detailed information about the device can be found in the Ope- rating Instructions and the other documentation: Available for all device versions via: – Internet: www.endress.com/deviceviewer – Smart phone/tablet: Endress+Hauser Operations App...
Deltapilot M FOUNDATION Fieldbus Order code: XXXXX-XXXXXX Ser. no.: XXXXXXXXXXXX Ext. ord. cd.: XXX.XXXX.XX Serial number www.endress.com/deviceviewer Endress+Hauser Operations App A0023555 Endress+Hauser...
A connection that has to be connected to ground prior to establishing any other the plant grounding system: This may be connections. a potential equalization line or a star grounding system depending on national or company codes of practice. Endress+Hauser...
Page 5
Indicates procedures, processes or actions that are forbidden. A0011184 Indicates additional information. A0011193 Reference to documentation A0015482 Reference to page A0015484 Reference to graphic A0015487 1. 2. , ... Series of steps Result of a sequence of actions A0018343 Visual inspection A0015502 Endress+Hauser...
The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: • Trained, qualified specialists: must have a relevant qualification for this specific function and task • Are authorized by the plant owner/operator • Are familiar with federal/national regulations Endress+Hauser...
The manufacturer is not liable for damage caused by improper or non-designated use. Verification for borderline cases: For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability.
It fulfills general safety requirements and legal requirements. It also conforms to the EC directives listed in the device-specific EC declaration of conformity. Endress+Hauser confirms this fact by applying the CE mark. Identification Product identification The following options are available for identification of the measuring device: •...
The devices comply with the applicable standards and regulations as listed in the EC Declaration of Conformity and thus comply with the statutory requirements of the EC Directives. Endress+Hauser confirms the conformity of the device by affixing to it the CE mark.
Section 8.3 "Pos. zero adjust". • The local display can be rotated in 90° stages. • Endress+Hauser offers a mounting bracket for installing on pipes or walls. ä 14, Section 4.5.6 " "Wall and pipe mounting (optional)". 4.5.1 General installation instructions •...
Page 11
– or at a point in the tank that can be affected by pressure pulses from the agitator • The calibration and functional test can be carried out more easily if you mount the device downstream of a shutoff device. • Deltapilot M must be included in the insulation for media that can harden when cold. Endress+Hauser...
Page 12
The height of the protective cap must be taken into consideration when designing the layout of the measuring point. The level zero point (E) corresponds to the position of the process isolating diaphragm. Level zero point = E; top of the probe = L. Endress+Hauser...
Page 13
2. Raise the clamping jaws (item 3). Position the extension cable (item 1) between the clamping jaws as illustrated in Figure. 3. Hold the extension cable in position (item 1) and push the clamping jaws (item 3) back down. Tap the clamping jaws gently from above to fix them in place. Endress+Hauser...
Page 14
The seal is not allowed to press on the process isolating diaphragm as this could affect the measurement result. ‣ Ensure that the seal is not touching the process isolating diaphragm. A0017743 Fig. 2: Process isolating diaphragm Seal 4.5.6 Wall and pipe mounting (optional) Mounting bracket See operating instructions. Endress+Hauser...
When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at least 5 Nm (3.69 lbf ft). Mount the cable with a bending radius (r) 120 mm (4.72 in). Routing the cable (e.g. through a pipe) You require the cable shortening kit. Endress+Hauser...
1. Check that the supply voltage corresponds to the supply voltage indicated on the nameplate. 2. Switch off the supply voltage before connecting the device. 3. Remove housing cover. 4. Guide the cable through the gland. Preferably use a twisted, shielded two-wire cable. Endress+Hauser...
Page 18
5. Connect the device in accordance with the following diagram. 6. Screw down the housing cover. 7. Switch on the supply voltage. A0029967 FOUNDATION Fieldbus electrical connection Terminals for supply voltage and signal Grounding terminal Supply voltage: 9 to 32 VDC (Power conditioner) External ground terminal Endress+Hauser...
• External ground terminal: 0.5 to 4 mm (20 to 12 AWG) 5.2.4 Cable specification • Endress+Hauser recommends using twisted, shielded two-wire cables. • Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Operating options 6.1.1 Operation without operating menu Operating options Explanation Graphic illustration Description Local operation without The device is operated ä 22 device display using the operating key Display Zero and DIP switches on the electronic insert. OUNDATION OUNDATION Endress+Hauser...
Page 21
Operating options Explanation Graphic illustration Description Remote operation via The device is operated See operating FieldCare using the FieldCare instructions operating tool. Remote operation via The device is operated See operating the NI Tool using the NI Tool. instructions Endress+Hauser...
DIP switch for locking/unlocking parameters relevant to the measured value Function of the DIP switches Switches Symbol/ Switch position labeling "off" "on" The device is unlocked. The device is locked. Parameters relevant to the measured value Parameters relevant to the measured value can be modified. cannot be modified. Endress+Hauser...
Page 23
If the LED on the electronic insert lights up briefly, the pressure applied has been accepted for position adjustment. If the LED does not light up, the pressure applied was not accepted. Observe the input limits. For error messages, see operating instructions. Endress+Hauser...
The language can always be changed even if the device is locked. Operator Display/operat. Contains parameters that are needed to configure the measured value display (selecting the values displayed, display format, display contrast, etc.). With this submenu, users can change the measured value display without affecting the actual measurement. Endress+Hauser...
Page 25
Contains all the parameters that are needed to detect and analyze operating errors. For an overview of the entire operating menu: See operating instructions. Direct access to parameters The parameters can only be accessed directly via the "Expert" user role. Endress+Hauser...
Page 26
90 mm (3.54 in) cable. The display of the device can be turned in 90° stages (see figure steps 4 to 6). Depending on the orientation of the device, this makes it easy to operate the device and read the measured values. A0028500 Endress+Hauser...
Page 27
The following table illustrates the symbols that can appear on the onsite display. Four symbols can occur at one time. Symbol Meaning Lock symbol The operation of the device is locked. To unlock the device, ä 30, Locking/unlocking operation. Endress+Hauser...
Page 28
ESC functions: – Exit the edit mode for a parameter without saving the changed value. – You are in a menu at a selection level. Each time you press the keys simultaneously, you go up a level in the menu. Endress+Hauser...
Page 29
5 0 0 0 0 0 mbar Switch to the "" symbol with the key. Use to save the new value and exit the editing mode. 5 0 0 0 0 mbar See next graphic. Endress+Hauser...
Page 30
Abort Exit the edit mode for the parameter with . Confirm 6.3.4 Operation via FieldCare See operating instructions. 6.3.5 Locking/unlocking operation See operating instructions. 6.3.6 Simulation See operating instructions. 6.3.7 Resetting to factory settings (reset) See operating instructions. Endress+Hauser...
If a pressure smaller than the minimum permitted pressure or greater than the maximum permitted pressure is present at the device, the following messages are output in succession (depending on the setting in the "Alarm behavior" (050) parameter): "S140 Working range P" or "F140 Working range P" Endress+Hauser...
• The pressure applied must be within the nominal pressure limits of the sensor. See information on the nameplate. Carrying out position adjustment Pressure is present at device. Press the "Zero" key for at least 3 s. Does the LED on the electronic insert light up briefly? Endress+Hauser...
Use the device only within the sensor range limits. Function check Carry out a post-installation and a post-connection check as per the checklist before commissioning the device. • "Post-installation check" checklist ä 17 • "Post-connection check" checklist ä 20 Endress+Hauser...
Changing the measuring mode affects the span (URV)! This situation can result in product overflow. ‣ If the measuring mode is changed, the span setting (URV) must be verified and, if necessary, reconfigured! Options: • Pressure • Level Factory setting: Pressure Endress+Hauser...
– You correct the measured value via the "Pos. zero adjust" parameter with the Setup Pos. zero adjust "Confirm" option. This means that you are assigning the value 0.0 to the pressure present. – Measured value (after pos. zero adjust) = 0.0 mbar Options • Confirm • Abort Factory setting: Abort Endress+Hauser...
ä 39 Calibration is "In height" – Calibration with reference performed by entering pressure (wet calibration), see ä 44 the density and two height-level value – Calibration without pairs. reference pressure (dry calibration), see ä 41 Endress+Hauser...
Page 37
Select the "In pressure" level mode by means of the "Level selection (024)" parameter. Menu path: Setup Extended Setup Level Level selection (024) A0030028 Fig. 7: Calibration with reference pressure – wet calibration See Table, Step 7. See Table, Step 8. Endress+Hauser...
Page 38
Menu path: Setup Extended Setup Level Process density (035) Result: The measuring range is set for 0 to 3 m (9.8 ft). The measured variables %, level, volume and mass are available for this level mode. See operating instructions "Unit before lin. (025)". Endress+Hauser...
Page 39
Menu path: Setup Extended Setup Level Unit before lin. (025) A0030030 Fig. 9: Calibration without reference pressure – dry calibration See Table, Step 7. See Table, Step 8. See Table, Step 9. See Table, Step 10. Endress+Hauser...
Page 40
Menu path: Setup Extended Setup Level Process density (035) Result: The measuring range is set for 0 to 1000 l (264 gal). The measured variables %, level, volume and mass are available for this level mode. See operating instructions "Unit before lin. (025)". Endress+Hauser...
Page 41
• Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. when the container is empty or partly filled, the measured value is not zero. For information on how to perform position adjustment, see ä 35, "Pos. zero adjust". Endress+Hauser...
Page 42
Menu path: Setup Extended Setup Level Calibration mode (027) Enter the density of the medium via the "Adjust density (034)" parameter, here "1 g/cm " (1 SGU) for example. Menu path: Setup Extended Setup Level Adjust density (034) Endress+Hauser...
Page 43
See Table, Step 7. See Table, Step 8. See Table, Step 9. See Table, Step 10. See Table, Step 11. The measured variables %, level, volume and mass are available for this level mode operating instructions "Unit before lin. (025)". Endress+Hauser...
Page 44
Fig. 13: Calibration with reference pressure – parameter, here "l" (liter) for example. wet calibration Menu path: Setup Extended Setup Level See Table, Step 8. Unit before lin. (025) See Table, Step 9. See Table, Step 10. Endress+Hauser...
Page 45
Menu path: Setup Extended Setup Level Process density (035) Result: The measuring range is set for 0 to 1000 l (264 gal). The measured variables %, level, volume and mass are available for this level mode operating instructions "Unit before lin. (025)". Endress+Hauser...
In this example, a device with a 400 mbar (6 psi) sensor is configured for the 0 to +300 mbar (4.35 psi) measuring range, i.e. 0 mbar and 300 mbar (4.35 psi) are assigned. Prerequisite: This is a theoretical calibration, i.e. the pressure values for the lower and upper range are known. Endress+Hauser...
Page 47
Press. eng. unit (125) See operating instructions Corrected press. (172) See operating instructions Pos. zero adjust (007) (Gauge pressure sensor) See operating instructions Damping switch (164) See operating instructions Damping value (017) See operating instructions Pressure af. damp (111) See operating instructions Endress+Hauser...