Determining The Collector Row Distance "Z - Viessmann VITOSOL 300-T Installation Instructions Manual

Vacuum tube collector based on the heat pipe principle
Table of Contents

Advertisement

Installation on flat roofs
Accessories for one collector array
wQ Connecting pipe
wW Thermal insulation
Connection set:
wE Connecting pipe (short)
wR Connecting pipe (long)
wT Locking ring fitting (elbow 90°),
22

Determining the collector row distance "z"

When installing several collectors in series, maintain distance z (see page 20).
Example:
Würzburg is located at approx 50° latitude.
1. Determine the angle of the sun .
In Germany this angle (subject to
latitude) lies between
12° (Flensburg) and 20° (Freiburg).
Angle of the sun:
90°
23.5°
latitude
(23.5° should be accepted as con-
stant)
90°
23.5°
50° = 16.5°
18
(cont.)
wZ Support sleeve
wU U-pipe
wI Thermal insulation cap
wO Fixing screws
eP Strain relief fitting
2. Calculating dimension z:
h = 2031 mm
= 45°
= 16.5°