Viessmann Vitocal 300-G Installation And Service Instructions Manual page 35

Heat pump with electric drive, 1 and 2-stage. brine/water heat pump: 5.7 to 34.4 kw. with conversion kit to water/water heat pump: 7.5 to 45.2 kw
Table of Contents

Advertisement

Electrical connection
Plug
sXF
Terminals
Function
224.7
Circulation pump for DHW reheating
or
Control of immersion heater (in DHW
cylinder)
Immersion heater EHE 400 V~
224.7
B
X2.N
A
Fig. 28
Immersion heater EHE, power supply 3/N/PE
A
400 V/50 Hz
B
Terminals of the heat pump control unit
Plug
sXG
Terminals
Function
225.1
Heating circuit pump of the heating
circuit with mixer M2/HC2
M2
r
225.2
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer CLOSE
225.3
Mixer motor control, heating circuit
M2/HC2
M2
Signal mixer OPEN
(cont.)
L1
L2
N
L3
?
Explanation
Connection values
Output: 100 W
Voltage: 230 V~
Max. switching current: 4(2) A
Explanation
Connect a temperature limiter to restrict the maximum
temperature for underfloor heating circuits (if installed)
in series.
Connection values:
Output: 100 W
Voltage: 230 V~
Max. control current: 4(2) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
Connection values:
Output: 10 W
Voltage: 230 V~
Max. control current: 0.2(0.1) A
Installation sequence
35

Advertisement

Table of Contents
loading

Table of Contents