Siting and transport requirements
Transport
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never put weight on the top, front or side panels
of the appliance.
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
The installation room must be dry and free from
the risk of frost:
Ensure ambient temperatures between 0 and
35 °C.
Max. 70 % relative humidity (corresponds to
an absolute humidity of approx. 25 g water
vapour/kg dry air)
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
!
Please note
Overloading the floor can result in damage to
the building structure.
Observe the permissible floor load. Take the
total weight of the appliance into account.
Total weight
Type
Weight in kg
BW
301.B06
301.B08
301.B10
301.B13
301.B17
Type
Weight in kg
BWC
301.B06
301.B08
301.B10
301.B13
301.B17
!
Please note
Tilting the compressor at a steep angle inside
the heat pump can result in appliance damage.
Max. tilting angle: 45° for a very short time
Type
BWS
301.B06
301.B08
301.B10
301.B13
301.B17
To prevent the transmission of structure-borne noise,
never site the appliance above ceilings with wooden
joists, e.g. in the attic.
Minimum room volume (to EN 378)
Type
BW
301.B06
BWC
301.B08
BWS
301.B10
301.B13
301.B17
113
117
129
135
148
123
127
139
145
158
Preparing for installation
Weight in kg
Refrigerant
Minimum
charge in kg
room volume
3
in m
1.40
1.95
2.40
2.25
2.75
109
113
125
131
144
3.2
4.4
5.5
5.1
6.3