Electrical connection
Plug
sXS
Clamps
Function
222.2
Control of mixer motor for external
heat generator
Signal mixer OPEN
222.3
222.4
Control of external heat generators
and 1 high limit safety cut-out each
(on site, max. 70 °C), to switch off or
switch between the following compo-
nents:
Central heating:
Secondary pump, heat pump
■
Secondary pump, heat pump stage
■
2 (if installed)
External heat generator
■
DHW reheating:
Circulation pump for cylinder heat-
■
ing
or
3-way diverter valve "central heat-
■
ing/DHW heating"
High limit safety cut-out for heat pump in conjunc-
tion with an external heat source
X3.1
B
C
222.3
A
222.4
D
K1
X2.N
Fig. 26
Terminals on extension PCB
A
Move jumper from X3.1 to 222.3
B
Connection on the external heat source at termi-
C
nals for external demand
High limit safety cut-out (max. 70
D
protection
K1 Relay; sizing in accordance with the external heat
source; observe safety instructions
(cont.)
C) as heat pump
º
Explanation
Connection values
Output: 10 W
■
Voltage: 230 V~
■
Max. switching current: 0.2(0.1) A
■
Floating contact
Connection values (contact breaking capacity)
Voltage: 230 V~
■
(not suitable for safety LV)
Max. switching current: 4(2) A
■
Connections for high limit safety cut-outs for central
heating:
In series to the secondary pump (terminal 211.2 on
■
the main PCB)
In series to the secondary pump, heat pump stage 2
■
(terminal 224.3)
In series for controlling the external heat generator
■
(terminal 222.3)
Connections for high limit safety cut-outs for DHW re-
heating:
In series with the circulation pump for cylinder heating
■
or 3-way diverter valve "central heating/DHW heating"
(terminal 211.4 on main PCB)
Installation sequence
33