Viessmann Vitocal 300-G Installation And Service Instructions Manual page 31

Heat pump with electric drive, 1 and 2-stage. brine/water heat pump: 5.7 to 34.4 kw. with conversion kit to water/water heat pump: 7.5 to 45.2 kw
Table of Contents

Advertisement

Electrical connection
Connecting the temperature limiter, part no. 7151728,
7151729
B
to the mixer extension kit
A
N
?
B
M
C
1~
Fig. 25
Connect plug
to the extension kit.
A
Temperature limiter
B
Heating circuit pump M3/HC3
C
Plug
sYF
Terminals
Function
214.1
External hook-up, heating/cooling cir-
cuits:
Central heating demand, heating cir-
cuit M2/HC2
M2
214.2
External hook-up, heating/cooling cir-
cuits:
Central cooling demand, heating cir-
cuit M2/HC2
M2
214.3
External hook-up, heating/cooling cir-
cuits:
Central heating demand, heating cir-
cuit M3/HC3
M3
214.4
External hook-up, heating/cooling cir-
cuits:
Central cooling demand, heating cir-
cuit M3/HC3
M3
Note
If heat pump stage 2 is connected, the external hook-
up for heating/cooling circuits is not possible.
(cont.)
Explanation
230 V~ digital input:
230 V~: Central heating demand for heating circuit
M2/HC2 active
0 V: No demand
Breaking capacity 230 V, 0.15 A
230 V~ digital input:
230 V~: Central cooling demand for heating circuit
M2/HC2 active
0 V: No demand
Breaking capacity 230 V, 0.15 A
230 V~ digital input:
230 V~: Central heating demand for heating circuit
M3/HC3 active
0 V: No demand
Breaking capacity 230 V, 0.15 A
230 V~ digital input:
230 V~: Central cooling demand for heating circuit
M3/HC3 active
0 V: No demand
Breaking capacity 230 V, 0.15 A
Installation sequence
31

Advertisement

Table of Contents
loading

Table of Contents