Installation sequence
Electrical connection
Overview of the electrical connections of the heat pump control unit (type BW/BWC 301.B)
F6
F11
F16
F26
X24
F8
F7
F14
F27
F13
F4
F12
F20
X25
193C
193A
193B
X31
Fig. 22
Cross connect PCB: See page 36.
A
F1 Fuse 6.3 A (slow)
Expansion PCB on main PCB: See page 32.
B
Main PCB (230 V~ components)
Information regarding the connection values
The specified output is the recommended connected
load.
The total output of all components connected directly
to the heat pump control unit (e.g. pumps, valves,
message facilities, contactors) must not exceed
1000 W.
If the total output is < 1000 W, the individual rating of
a component (e.g. pump, valve, message facility,
contactor) can be greater than specified. However,
the breaking capacity of the corresponding relay
must not be exceeded.
The stated current indicates the max. switching cur-
rent of the switching contact (observe the total cur-
rent of 5 A).
Controls for external heat source and central fault
messages are unsuitable for safety LV.
28
(cont.)
F3
J4
J3
X3
X2
X1
F1
Main PCB: See next chapter.
C
F3 Fuse 6.3 A (slow)
Controller and sensor PCB: See page 38.
D
Set the required parameters during commissioning:
See page 55 onwards.