Commissioning, inspection, maintenance
Commissioning the system
Parameters for instantaneous heating water heater
Parameter
"Electr booster heater"
"Enable instantaneous heating water heater 7900"
"Output for instant. heating water heater at power-OFF 790A" "1" 3 kW
Enabling instantaneous heating water heater for DHW heating
"DHW"
Ó
"Enable electric heaters for DHW heating 6015"
Parameters for swimming pool water heating
Parameter
"System definition"
Ó
"External extension 7010"
"Swimming pool 7008"
Parameters for ventilation
Parameters
"Ventilation"
Ó
"Vitovent enable 7D00"
Other enabling settings, if applicable:
"Ventilation"
Ó
"Enable preheater bank electric 7D01"
"Enable reheater bank hydraulic 7D02"
"Enable humidity sensor 7D05"
"Enable CO2 sensor 7D06"
If necessary, set values:
"Ventilation"
Ó
"Set extract air temperature 7D08" (only in conjunction with
Vitovent 300-F)
"Flow rate reduced ventilation 7D0A"
"Flow rate nominal ventilation 7D0B"
"Flow rate intensive ventilation 7D0C"
62
(cont.)
Ó
Setting
"1"
"2" 6 kW
"3" 9 kW
"1"
Setting
"1" or "3"
"1"
Setting
"1" Vitovent 300-F
"2" Vitovent 200-C
"1"
"1"
"1"
"1"
≙
"100" to "300" (
10 to 30 °C)
Subject to sizing
Ventilation unit service instruc-