Installation sequence
Electrical connection
Plug
Sensor
F16
Room temperature sensor, cooling circuit
Required for separate cooling circuit SKK
Recommended for heating/cooling circuit without mixer A1/HC1
F21
Collector temperature sensor
F23
Solar circuit return temperature sensor
KM BUS (wires interchangeable)
aVG
Use the KM BUS distributor (accessories) if several devices are connected.
KM BUS subscriber (examples):
Extension kit, mixer for heating circuit M2/HC2
Remote control Vitotrol 200A or Vitotrol 300B (set the heating circuit assign-
ment at the remote control)
EA1 extension, AM1 extension
Communication interface Vitocom 100, type GSM2
sVA
Modbus 2 (wires not interchangeable)
Connection for electricity meter of photovoltaic system
J3
Jumper for terminator Modbus 2
Terminator enabled (delivered condition)
Terminator disabled
J4
Jumper for setting master/slave Modbus 2
Heat pump control unit is slave
Heat pump control unit is master (delivered condition)
X18
Modbus 1
Connection for Viessmann appliances, e.g. Vitovent 300-F
Note
If further Viessmann appliances are to be connected to Modbus 1, plug in the
Modbus distributor (accessories) (see "Modbus distributor" installation in-
structions).
X24
Connection for LON communication module (see "LON communication mod-
ule" installation instructions)
X31
Slot for coding card
Swimming pool heating
Note
Swimming pool heating is controlled via the
EA1 extension with KM BUS.
Make connections to EA1 extension only in accord-
ance with Fig. 30.
A filter circuit pump cannot be controlled via the heat
pump control unit.
38
(cont.)
Type
NTC 10 k
Ω
NTC 20 k
Ω
NTC 10 k
Ω