Maintenance

Draining heat pump on the secondary side

1. Close the on-site boiler drain & fill valve.

Checking sensors

Sensor connections to the controller and sensor
PCB: See page 28.
Sensor locations in the heat pump: See diagram 51
on page 65.
Sensor
Outside temperature sensor (F0)
Buffer temperature sensor (F4)
Cylinder temperature sensor, top (F6)
Cylinder temperature sensor, bottom (F7)
Flow temperature sensor, heating circuit with mixer M2/HC2 (F12)
System flow temperature sensor (F13)
Flow temperature sensor, cooling circuit (heating circuit without mixer A1/HC1 or sep-
arate cooling circuit SKK) (F14)
Room temperature sensor for separate cooling circuit (F16)
Boiler water temperature sensor, external heat generator (F20)
Buffer temperature sensor, cooling (F26)
Room temperature sensors
Sensors in the refrigerant circuit
Flow temperature sensor, secondary circuit (F8)
Return temperature, secondary circuit (X25.11/X25.12)
Temperature sensor, air intake (X25.1/X25.2)
Temperature sensor, air discharge (X25.3/X25.4)
Viessmann NTC 10 k
Ω
Outside temperature sensor
200
100
80
60
40
20
10
8
6
-20
-10
0
Temperature in °C
Fig. 52
66
(marked blue)
10
20
30
2. Drain heat pump at drain valve: See Fig. 51.
Further sensors
20
10
8
6
4
2
1
0.8
0.6
0.4
10
30
50
Temperature in °C
Fig. 53
Test element
NTC 10 k
Ω
Pt500A
70
90
110