Rs485 Serial Connection - Honeywell Notifier LCD6000N Installation Manual

Lcd remote panel
Table of Contents

Advertisement

RS485 Serial connection

The connection of LDC6000N with the control panel use serial line RS485.
RS-485 line must be installed in "MULTI-POINT" configuration (daisy chain).
Each peripheral must be programmed with an address between 1  16. (refer to TAB.1).
"Multi-Point" configuration (Daisy Chain)
Connect two wires to the RS485
control panel terminal block
(LIN+ and LIN- ) to the
corresponding terminals of the
first device on the line.
Continue wiring from the first
device to the next, and so on.
Install EOL (120-150,0.5W) on
the terminal block on both
control panel and last device of
the line.
Maximum length between control
panel and last device 1,5 km.
Use shielded cable with
appropriate section type
Belden 9574 or 9575
PAGE - 10
NOTIFIER ITALIA
+24V
GND
EOL= 120
7
13
12
22
23
AM-2000
+24V
GND
EOL= 120
11
17
16
30
31
AM-4000
+24V
GND
EOL= 120
CN
CN
1
7
08
09
AM-6000
Typical wiring RS485 with 24Vdc power supply in common
(Control panel user output voltage 24Vdc)
Installation Manual
Doc. M-183.1-LCD6000N-ENG Rev A.2
3
1
2
4
5
1
LCD-6000N
1
2
3
4
5
1
LCD-6000N
5
3
4
1
2
1
2
LCD-6000N
LCD6000N_manu
EOL= 120
3
2
4
5
LCD-6000N
EOL= 120
3
5
2
4
LCD-6000N
EOL= 120
2
3
4
5
LCD-6000N
LCD6000N

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents