Honeywell Notifier LCD6000N Installation Manual page 13

Lcd remote panel
Table of Contents

Advertisement

Installation with separate power supply
Connect two wires to the RS485
control panel terminal block (LIN+
and LIN- ) to the corresponding
terminals of the first device on the
line.
Continue wiring from the first device
to the next, and so on.
Install EOL (120-150,0.5W) on the
terminal block on both control
panel and last device of the line.
Maximum length between control
panel and last device 1,5 km.
Use shielded cable with appropriate
section type Belden 9574 or 9575
Typical wiring RS485 with 24Vdc
separate power supply
( LCDs are powered by auxiliary
remote power supply).
Shielded cable and Earth connection
During installation, you need to consider
the consequences of remote ground
connections.
Connecting RS485 circuits, if there is a
ground wire (drain), this MUST NOT
be connected at chassis of the
equipment.
The shield must be connected only at the
control panel. Leave the other tail
disconnected and isolated
LCD6000N
LCD6000N_manu-inst
EOL= 120
7
12
13
AM-2000
EOL= 120
11
17
16
AM-4000
EOL= 120
CN0
7
08
09
AM-6000
Shield:
Connect to the
frame with a M5
lug
Use the location
closest to the
connector on the
chassis
Typical control
RS485 shield and earth wiring
Installation Manual
Doc. M-183.1-LCD6000N-ENG Rev A.2
+24V GND
+24V GND
3
4
5
1
2
1
LCD-6000N
+24V GND
+24V GND
3
4
1
2
5
1
LCD-6000N
+24V GND
+24V GND
3
1
2
4
5
1
LCD-6000N
Shield:
linking together the
two cable socks
A
B
panel wiring
NOTIFIER ITALIA
EOL= 120
3
5
2
4
LCD-6000N
EOL= 120
2
3
4
5
LCD-6000N
EOL= 120
3
5
2
4
LCD-6000N
A
B
Typical wiring of
the last device
PAGE - 11