Shindaiwa DG25MK Assembly And Instruction Manual page 23

Diesel engine generator
Hide thumbs Also See for DG25MK:
Table of Contents

Advertisement

< Note >
When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
 If using the O terminal, be careful that the currents of each phase are uniform.
 Use proper tools when connecting a load to sufficiently tighten the connection. Failure
to sufficiently tighten the connection will result in cable burnout.
(1) 3-Phase Output Terminal
 For 3-phase load:
 Terminal voltage is 400/440 V [200/220 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
 For 1-phase load:
 Terminal voltage is 230/254 V [115/127 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
 For 1-phase load:
 Terminal voltage is 400/440 V [200/220 V] (50/60Hz).
* The values in brackets are for when set to 200/220V.
Total output capacity
Unit
kVA
kW
R
S
Load
R
S
Load
Load
Load
TOTAL 16/20kVA(16/20kW)
R
S
Load
Load
TOTAL 16/20kVA(16/20kW)
3-phase load
R-S-T
R-O,S-O,T-O
20/25
6.7/8.3
16/20
6.7/8.3
T
O
20/25kVA(16/20kW)
T
O
T
O
Load
1-phase load
R-S,S-T,T-R
11.5/14.4
11.5/14.4
20
Total
20/25
16/20