Omron NS7 Series Setup Manual page 191

Programmable terminals
Table of Contents

Advertisement

Errors while Connecting to the Host
Symptoms at
Causes
PT
PT cannot
The settings for
communicate
Ethernet connec-
with the host.
tion, such as node
(An error mes-
number, network
sage is dis-
number, and IP
played.)
address, are not set
correctly.
The protocol set-
tings for the host
and the settings at
the PT do not
match.
The PT is not con-
nected to the host
properly.
For 1:N NT Link
connections, two or
more Units have the
same unit number.
7-3 Troubleshooting and Maintenance
Measures
Set the settings correctly, referring to Section 5 Connecting
to Host via Ethernet or Controller Link.
Set the communications settings using the NS-Designer.
Check that the type, length, and wiring of the connecting
cables meet the specifications.
(Refer to Section 4 Connecting Host to Serial Port.)
Reset so that each Unit has a unique unit number.
(Refer to 6-6 Communications Settings.)