5-1 Connecting to Host Via Ethernet
Reference
Setting IP Addresses for Ethernet Units
The IP address must also be set for Ethernet Units. Ethernet communications are not possi-
ble if the IP address of the Ethernet Unit is not set.
Set the IP address for the Ethernet Unit from the CPU Bus Unit Setup Area using Program-
ming Devices (SYSMAC-CPT, SYSMAC Support Software, CV Support Software Ver. 2 or
later, FIT20-MF501-V2, FIT10-MF501-V2, FIT20-MC601, or FIT20-MC701). Refer to the
SYSMAC CVM1/CV Series Ethernet Unit Operation Manual (W242) for details on setting
methods.
Ethernet Unit System
Set the system settings for the Ethernet Unit to operate on the Ethernet network as a node.
Set the system settings using a Programming Device (SYSMAC-CPT, SYSMAC Support
Software, CV Support Software Ver.2 or later, FIT20-MF501-V2 、 FIT10-MF501-V2, FIT20-
MC601, or FIT20-MC701).
Reference
5-14
· The node number cannot be set to a value higher than 7E (126 decimal). If the node
number is set to a higher value, an error will occur and the ERH indicator in the dis-
play will light.
· Set the node numbers so that all the nodes in the same network are unique.
· For details on operating the Support Software, refer to the CPU Bus Unit Setup Area
in the SYSMAC Support Software Operation Manual: Networks (W201) and SYSMAC
Support Software Operation Manual: CV Series (W249).
· Turn ON the power to the CPU Unit again after setting the system settings. The sys-
tem settings are not enabled after setting them until the power has been turned ON
again.