4-2 1:N Host Connection
Connecting to CS-series Serial Communications Boards
Serial Communications Boards with RS-232C Port for Use with CS-series CPU Units:
CS1W-SCB21 (Both ports 1 and 2 are RS-232C ports.)
CS1W-SCB41 (Port 1 is an RS-232C port and Port 2 is an RS-422A port.)
Reference
CPU Unit DM Area Settings
Write the settings directly from the Programming Device (Programming Console) or Support
Software (CX-Programmer) to the DM Area (Parameter Area) in the CPU Unit. After writing
the settings, enable the settings by turning ON the power again, restarting the Unit, restarting
the communications port, or executing the CHANGE SERIAL PORT SETUP (STUP) instruc-
tion.
The following table shows the allocated DM Area words and settings. The settings are the
same for RS-232C and RS-422A (CS1W-SCB41 Port 2).
Allocated DM Area words
Port 1
DM32000
DM32001
DM32006
Note: When connecting a single Unit in a 1:N connection, set the value of @ to 1 or higher.
For example, to connect PTs with unit numbers 3 to 6 to Port 1 in 1:N NT Links, set DM32000
to 8200 Hex, DM32001 to 000A Hex, and DM32006 to 0006 Hex.
Serial Communications Boards with RS-422A Port for Use with CS-series CPU Units:
CS1W-SCB41 (Port 2 is an RS-422A port.)
4-24
High-speed 1:N NT Links can be used with Serial Communications Boards and Serial
Communications Units from lot numbers 991220 (December 20, 1999) or later. Boards
and Units with earlier lot numbers cannot be used, so confirm that the lot number is
supported.
Write
value
Port 2
DM32010
8200
1:N NT Link Mode
DM32011
000A
Baud rate (high-speed)
DM32016
@: Largest unit number (1 to 7) of the connected PTs. (See
000@
Settings
note.)