Mounting Position - Omron NT612G Series Operation Manual

Programmable terminal
Table of Contents

Advertisement

Installation Environment
2-2-2

Mounting Position

Mounting Location
Ambient Temperature
Operation and Maintenance For safety during operation and maintenance, place the Terminal as far as
Improving Noise Resistance Do not install in a panel with high-voltage devices and install at least 200 mm
• Relative humidity exceeding a range of 35% to 85%.
• Corrosive or inflammable gasses.
• Strong magnetism.
• Excessive dust, salt, or iron dust.
• Direct vibration or shock.
• Direct sunlight.
• Spray from water, oil, or chemicals (the front panel is basically drip-proof).
PTs with LCD display have a field of vision of 20° up, 30° down, and 30° right
and left. Install the Terminal at a height and direction that make it easy for the
operator to see.
The ambient operating temperature range is 5°C to 40°C for liquid crystal
display PTs and 0°C to 50°C for EL display PTs. Take the following factors
into consideration.
• Leave sufficient ventilation space.
• Do not install directly above machinery that puts out a lot of heat (e.g.,
heaters, transformers, high-capacity resistors).
• If the ambient temperature of a PT with LCD display rises above 40%C or
that of a PT with EL display rises above 50%C, set up a fan or air condition-
er.
Control panel
Fan
PT
Louver
possible from high-voltage machinery and power equipment.
from electric power lines. To avoid noise interference from external devices,
separate them with a transformer or noise filter when wiring.
Power line
200 mm min.
PT
200 mm min.
Section 2-2
21