Installation of the Exhaust and Air Intake System
z Insert the vent pipe into the terminal body far enough
so that distance between the termination tee and the
wall is about 10" (Fig. 10).
z Secure both ends of the exhaust pipe through the
terminal body using the furnished locking collars.
(Fig. 10, Item. 1). Rotate collars downward and
secure set screw on locking collars (Fig. 11, Item. 2).
z Seal the space between vent pipe and locking collars
with silicone (Fig. 11, Item. 1).
A venting system that exits the structure through a
sidewall or the like, shall terminate at least 12 inches
above the ground.
The installation of a screened termination tee is
required to ensure trouble free operation and prevent
entry of foreign objects into the vent system.
The termination of the system shall be located at least
12 inches above the maximum snow line in geographic
areas where snow accumulates.
No changes or modifications are allowed in the venting
system. All components must be installed in their
original condition.
The termination shall not terminate less than 7 ft above
a paved sidewalk or driveway.
The termination shall be at least 6 ft away from the
combustion air intake of any other appliance.
Room air only:
The termination shall be at least 3 ft away from gas utility
meter, service regulator or the like (for room air
applications only).
The termination shall terminate at least 4 ft below, 4 ft
horizontally from, or 1 ft above any door, window, or
gravity air inlet into any building.
We reserve the right to make any changes due to technical modifications!
Installation, Operation and Maintenance Manual Sealed Combustion Gas Boiler Logano GA244 • Issue 02/2004
1
2
Fig. 10 Positioning of the termination tee
Item. 1: Locking collars
Item. 2: 4" Air intake connection
Fig. 11 Vent pipe locking collars
Item. 1: Seal space with beads of silicone
Item. 2: Set screws