Foundation

The appliance must be installed level, on a housekeeping pad, to function properly. Ensure the base is
securely connected to the appliance. Use a bubble level and make sure housekeeping pad is level
before installation of appliance. There are five
anchor bolts. Two of these are located inside the cabinet and the other three are outside.
housekeeping pad is recommended to be 4 inches but no less than 1 inch in height on the ST2500-
ST5000. On the ST6000, the housekeeping pad MUST BE 4 inches minimum.
NOTICE! The appliance may be installed on a combustible floor; however, the appliance must
NEVER be installed on carpeting.
Revised: December 8, 2021
Released: December 8, 2021
3/4" holes in the base which may be used for 5/8"
 Patterson-Kelley 2021
All Rights Reserved.
TM
P-K Storm
Gas Fired Boiler
Technical Service 1.877.728.5351
QTY 2: 3/4" Holes
Anchor/Lag Bolts
(FRONT inside
QTY 3: 3/4" Holes
for
Anchor/Lag Bolts
(REAR)
2691000273 P-K Storm ST2500-ST6000
Installation and Owners Manual Rev C.docx
The
for
cabinet)
Page 6