Annually Or 2500 Run Hours (Whichever Comes First) - Patterson-Kelley P-K STORM ST-5000 Installation & Owner's Manual

Gas fired boiler w/ nuro™ control system natural gas
Hide thumbs Also See for P-K STORM ST-5000:
Table of Contents

Advertisement

Annually or 2500 Run Hours (Whichever Comes First)

In addition to the recommended monthly and semi-annual service:
NOTE: Patterson-Kelley recommends cleaning the heat exchanger at least
once annually. Some of the items listed under this section are easily
accessible during that procedure. Patterson-Kelley recommends annual
maintenance and cleaning of the heat exchanger to be done simultaneously.
Please refer to Section
NOTE:
This section recommends replacing parts of the boiler. Refer to section
6
for Parts/Technical Support. Spare parts and replacement parts can be
ordered from Patterson-Kelley by calling toll free (877) 728-5351. Reach us by
fax at (570) 476-7247.
1. Inspect and clean the inlet screen (if applicable) of any accumulated dust or lint. If using an air
filter, inspect and replace (if necessary). Patterson-Kelley suggests replacing air filters at least
once per year.
For the following points 2 through 4, refer to
2. ST2500-ST5000
a. Replace the ignition electrode and ionization rod (flame rod). Replace the gaskets for
each as well. Note the geometry of the ignition electrode and the ionization rod (flame
rod): if the spacing between the rods (after replacement) and the burner does not match
factory recommendation, please consult Patterson-Kelley for correction actions. Refer to
the following images for proper factory spacing -- dimensions are in millimeters:
Revised: December 8, 2021
Released: December 8, 2021
5.2
for more information.
5.2.
 Patterson-Kelley 2021
All Rights Reserved.
TM
P-K Storm
Gas Fired Boiler
Technical Service 1.877.728.5351
14
2691000273 P-K Storm ST2500-ST6000
Installation and Owners Manual Rev C.docx