Patterson-Kelley SOLIS SL-1500 Installation & Owner's Manual

Patterson-Kelley SOLIS SL-1500 Installation & Owner's Manual

Gas fired boiler with control system
Table of Contents

Advertisement

P-K SOLIS
GAS FIRED BOILER
®
w/ NURO
CONTROL SYSTEM
Natural Gas
SL-1500/SL-2000/SL-2500/SL-3000
Part #
2701000090
C.S.A Design-Certified
Complies with ANSI Z21.13/CSA 4.9
Gas-Fired Low Pressure Steam and Hot Water Boilers
ASME Code, Section IV
C.S.A Design-Certified
Complies with ANSI Z21.13/CSA 4.9
Gas-Fired Low Pressure Steam and Hot Water Boilers
WARNING: If the information in these instructions is not followed
exactly, a fire or explosion may result causing property damage,
personal injury or death.
- Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer,
service agency or the gas supplier.
Model Number:
Serial Number:
Start-Up Date:
Patterson-Kelley
155 Burson Street
East Stroudsburg, PA 18301
Telephone: 570.476.7261
Toll Free: 877.728.5351
Fax: 570.476.724
www.pattersonkelley.com
The information in this manual is the property of Patterson-Kelley. The descriptions and specifications contained in this manual were in
effect at the time this manual was approved for publication. While Patterson-Kelley will continue to support earlier model boilers to
within a reasonable time limit, we reserve the right to discontinue models and replacement parts at any time or change specifications or
Released: March 15, 2021
© © © © Patterson-Kelley 2021: All Rights Reserved.
design without notice and without incurring any obligation.
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
INSTALLATION
& O W N E R'S
MANUAL
&

Advertisement

Table of Contents
loading

Summary of Contents for Patterson-Kelley SOLIS SL-1500

  • Page 1 © © © © Patterson-Kelley 2021: All Rights Reserved. The information in this manual is the property of Patterson-Kelley. The descriptions and specifications contained in this manual were in effect at the time this manual was approved for publication. While Patterson-Kelley will continue to support earlier model boilers to &...
  • Page 2 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Safety General OTICE Each safety device must be ™ P-K SOLIS SL-1500, SL-2000, SL-2500 and SL-3000 maintained and checked per the ™ All P-K SOLIS SL-1500, SL-2000, SL-2500 and SL-3000 recommended schedule. Refer to Gas-Fired Boilers must be: Maintenance.
  • Page 3 If any of the provisions of this manual are not fully and completely understood, contact Patterson-Kelley Technical Service at 570.476.7261 or toll free at 877.728.5351. Hazard Warnings...
  • Page 4 CPVC, or other corrosion resistant piping for drainage. Collection and disposal must be in accordance with all applicable regulations. A condensate neutralization kit is available. Please contact your local Patterson-Kelley representative for more information. Burn, Fire and Explosion Hazards Burn, fire, and explosion hazards! Installation must be in strict conformance to all applicable codes and standards including NFPA 54, ANSI Z223.1 and CAN/CSA B.149.
  • Page 5: Table Of Contents

    Inlet Duct Connection to Boiler ....................35 Intake Duct Materials and Sizes ....................35 Category II Installations ......................35 Category IV Installations ......................36 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 6 URNER OMBUSTION HAMBER ....................62 FTER EPAIRS OR AINTENANCE ......................63 EQUENCE OF PERATIONS © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page vi...
  • Page 7 (SL-1500 & SL-2000) ..................96 PPLIANCE ONNECTIONS (SL-2500 & SL-3000) ..................97 PPLIANCE ONNECTIONS © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page vii...
  • Page 8 Gas Fired Boiler Technical Service 1.877.728.5351 ........................98 YDRONICS ATER ........................99 ROPYLENE LYCOL © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page viii...
  • Page 9: Introduction

    • If you cannot reach your gas supplier, or do not fully and completely understand the content, please call the fire department. contact Patterson-Kelley Technical Service at 570.476.7261 or toll free at 877.728.5351. QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ: ™...
  • Page 10 Technical Service 1.877.728.5351 PRECAUTIONS ASSOCIATED WITH HANDLING REFRACTORY LINING MATERIAL • This Patterson-Kelley product contains a Combustion Area lined with REFRACTORY CERAMIC FIBERS (RCFs) similar to many other devices produced in this industry. • RCFs have been identified by the International Agency for Research on Cancer (IARC) as possibly being carcinogenic to Humans.
  • Page 11: Purpose Of This Document

    If you have any questions on the information contained within, or do not fully and completely understand the content, please contact Patterson-Kelley Technical Service at 570.476.7261 or toll free at 877.728.5351.
  • Page 12: Site Preparation

    électrique de la pompe. Fermer plutôt le robinet the service access, increasing the d’admission de gaz à l’extérieur de l’appareil. possibility of injury. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 13: Compliance With Codes

    (b) field installed gas cocks must be “T” handle type, (c) piping of condensate shall conform to the State Plumbing Code, and (d) refer to the Massachusetts Supplement for further details. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 14: Location Setup

    NOTICE! The appliance may be installed on a combustible floor; however, the appliance must NEVER be installed on carpeting. NOTICE! This appliance is certified for INDOOR use only! © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 15: Clearances

    Note: Failure to provide recommended service clearances may make it difficult to perform service on the boiler(s). © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 16: Inlet Air And Exhaust Venting Considerations

    Faulty vent installation can allow toxic fumes to be released into living areas. This may cause property damage, injury, or death. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 17: Category Ii/Iv Flue Gas Exhaust Vent Planning

    SL-1500, SL-2000, (Exhaust Only) 220 ° F (gross) 9.3% SL-2500, SL-3000 +0.01” to +0.4” W.C. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 7...
  • Page 18: Venting Materials For Flue/Exhaust Systems

    NOTE 2: When this material is used for venting, it must be listed to either UL- 1738 or ULC-S636 (depending on the local requirements). Consult the local boiler codes for more information. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 19: Required Clearances

    Improper interconnection of venting systems may result in leakage of flue gases into occupied spaces. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 20 être installées de façon à empêcher l'accumulation de condensat; et si nécessaire, les chaudières de catégories II et IV doivent être pourvues de dispositifs d'évacuation du condensate. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 21: Gas Piping Considerations

    The P-K SOLIS™ boiler’s heat exchanger is made of stainless steel. The heat exchanger requires proper water conditions to remain efficient and function properly. For more information, refer to Patterson-Kelley’s Water Quality Standards for Hydronic Boilers in Multi-Metal Systems in Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal Systems, as this applies to the warranty of your heat exchanger.
  • Page 22: Appliance Connections (Sl-1500 & Sl-2000)

    Gas Fired Boiler Technical Service 1.877.728.5351 Appliance Connections (SL-1500 & SL-2000) All connections must be in compliance with national, state, and local code requirements. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 23: Appliance Connections (Sl-2500 & Sl-3000)

    Gas Fired Boiler Technical Service 1.877.728.5351 Appliance Connections (SL-2500 & SL-3000) All connections must be in compliance with national, state, and local code requirements. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 24: Electrical Connections

    TB2 Terminal 3 = NEUTRAL • TB2 Terminal 4 = GROUND Low Voltage (TB1) Terminal Block High Voltage (TB2) Terminal Block © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 25: Power Requirements (Sl-2500 & Sl-3000)

    208 VAC main voltage. Refer to Section 7.2.4 for proper wiring and configuration of the internal control transformer. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 26 Maximum tightening torque = 13 in-lbs! NOTE: The hot lead terminals can accommodate maximum 12AWG wire. The ground terminal can accommodate maximum 8AWG wire. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 27: High Voltage (Tb2) Terminal Block (Sl1500 & Sl2000)

    #1 and provide additional connection points for auxiliary safety devices. This circuit is energized with 120VAC, so the contacts on any auxiliary safety devices must be rated for minimum 120VAC. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 28 NURO control. The normally-open contacts on this relay have a maximum voltage rating of 240VAC and maximum current capacity of 1/2 Amp. © Patterson-Kelley 2021 Revised: March 15, 2021...
  • Page 29: High Voltage (Tb2) Terminal Block (Sl2500 & Sl3000)

    120VAC. The appliance ships with a factory-installed jumper across Start Interlock #1 and Start Interlock #2 terminals. Remove the jumper(s) if using any auxiliary safety devices. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 30 NURO control. The normally-open contacts on this relay have a maximum voltage rating of 240VAC and maximum current capacity of 1/2 Amp. © Patterson-Kelley 2021 Revised: March 15, 2021...
  • Page 31: Low Voltage (Tb1) Terminal Block

    This analog signal can be used to change the boiler’s operating setpoint/firing rate. Spare Analog Input – TB1-5 and TB1-6 are reserved for future use. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 32 The wireless receiver should be installed at or near the boiler, and the wireless temperature sensor should be installed on the North face of the building and shielded from direct sunlight exposure. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 33: Combustion Air

    3000 SL-2000 2000 4000 1000 SL-2500 2500 5000 1250 SL-3000 3000 6000 1000 1500 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 23...
  • Page 34: Air Inlet Requirements - Canada

    SL-1500 1,500,000 43,226 6,452 SL-2000 2,000,000 53,548 6,452 SL-2500 2,500,000 64,516 6,452 SL-3000 3,000,000 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 24...
  • Page 35: P-K Solis™ Combustion Air Requirements

    For example, joints in PVC or CPVC piping must be cemented. For galvanized duct, wrap each joint and seam with adhesive aluminum tape or other sealant. Patterson-Kelley recommends installing a 1” x 1” or larger bird screen on the exterior termination. Ensure that the screen does not become blocked with snow, ice, insects etc.
  • Page 36: Motorized Combustion Air Dampers

    If the combustion air intake ductwork and the exhaust vent terminate on the same wall of NOTE: the building, they must utilize the same type of termination fitting. Patterson-Kelley recommends including a motorized combustion air damper in each NOTE: appliance’s air intake ductwork. Refer to 3.4.5...
  • Page 37 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 38: Flue Gas / Exhaust Venting

    Vertical vents are allowed to be terminated with a variety of ends, including plain straight pipe, elbow, or vent tee. Horizontal vents must be terminated with an elbow or vent tee. Similarly, a bird screen with 1” x 1” openings is recommended for termination. Patterson-Kelley does not recommend using a vent rain cap of any type.
  • Page 39: Vent Termination

    This is illustrated in the following diagram. Additionally, the boiler vent shall terminate at least 3 ft. above a forced air inlet located within 10 ft. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 40: Venting For Multiple Boilers

    In addition, Patterson-Kelley also recommends the use of motorized combustion air dampers in the combustion air intake ductwork of each individual appliance. When an appliance is offline, its combustion air damper will remain closed which will also help prevent the backflow of flue gases from online appliances.
  • Page 41: Sealed Combustion/Direct Vent Systems

    Allowable termination fittings are either 90° elbows or tees. This boiler may be installed with sidewall vent using room air, see 3.4.1. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 42 • +0.01” W.C. and +0.22” W.C. (Direct Vent / Sealed Combustion) • +0.01” W.C. and +0.4” W.C. (Exhaust Only) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 43 • +0.01” W.C. and +0.22” W.C. (Direct Vent / Sealed Combustion) • +0.01” W.C. and +0.4” W.C. (Exhaust Only) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 44 When terminating on the same vertical axis, the following options are what can be used for venting. Must be a minimum of 36” Must be a minimum of 36” © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 45: Inlet Duct Connection To Boiler

    Category IV vent installations. 120VAC motorized dampers with end limit switches are available for purchase from Patterson-Kelley. Other damper motor voltages are acceptable, provided they do not exceed 240VAC. The Air Damper Interlock circuit for the end limit switch is always 120VAC which is sourced from the boiler itself.
  • Page 46: Category Iv Installations

    CPVC Support Spacing (Feet) Vent Size Sch. 40 Sch. 80 4-1/2 4-1/2 5-1/2 5-1/2 6-1/2 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 36...
  • Page 47: Condensate Drain, Trap & Disposal

    4. The condensate is slightly acidic (3-5 PH), however, local codes may require it to be neutralized prior to entering the drainage system. An optional, field installed, Condensate Neutralization System is available from Patterson-Kelley. 5. All piping from the condensate trap to the suitable drain must remain below the highest point (top of the condensate outlet pipe) on the properly attached condensate assembly.
  • Page 48 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 38...
  • Page 49: Removing An Existing Boiler

    Faire fonctionner le brûleur principal pendant 5 min ensuite, déterminer si le coupe-tirage déborde à l'ouverture de décharge. Utiliser la flamme d'une allumette ou d'une chandelle ou la fumée d'une cigarette, d'un cigare ou d'une pipe. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 50 être modifié pour respecter les valeurs minimales des tableaux pertinents de l'appendice F du National Fuel Gas Code, ANSI Z223.1/ NFPA 54 et (ou) les codes d'installation CAN/CSA-B149.1. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 51: Piping

    Natural Gas Requirement Appliance Size (BTU/Hr) (CFH) 1,500,000 1500 2,000,000 2000 2,500,000 2500 3,000,000 3000 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 41...
  • Page 52: Natural Gas Piping

    If using soap and water or a similar leak test method, make sure to clean off all moisture from the gas pipe fittings prior to placing the appliance into service. © Patterson-Kelley 2021 Revised: March 15, 2021...
  • Page 53: Boiler Water Piping

    & floor drain in accordance with all national, state, and local codes. Heat trace may be required to prevent freezing in un-insulated spaces. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 54: Boiler Inlet And Outlet Connections

    The SL-1500, SL-2000, SL-2500, and SL-3000 boilers require an ASME Section IV relief valve to be installed on the top of the OUTLET (Supply) connection. The spindle of the relief valve must be vertical. The ASME Section IV relief valves are available for purchase from Patterson-Kelley. Low Water Cut-Off The boiler is furnished with a probe-type low water cut-off;...
  • Page 55: Water Quality

    The condensate is acidic (pH between 3.0 and 5.0) and may be corrosive to some building drain systems. A condensate neutralization system may be required and is available from Patterson-Kelley. If the condensate drainage system is exposed to freezing temperatures, it must be field heat traced. The boiler could generate up to one gallon of condensate per 100,000 BTU input.
  • Page 56: Pre-Start Checklist

    The low water cut-out circuit board is located inside the boiler’s front door, toward the top of the control panel and is identified with a yellow label. © Patterson-Kelley 2021 Revised: March 15, 2021...
  • Page 57: Manual Reset High Temperature Limit Test

    “Reset Control”. NOTE Make sure to re-open the main gas cock (external to the boiler) after a successful test. High Gas Pressure Switch © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 58: Fuel/Air Adjustments

    Gas Valve SL-2500 & SL-3000 SL-1500 & SL-2000 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 59: Gas Pressure Adjustment

    NOTICE! For high altitude adjustments (greater than 2,000 feet above sea level), see Appendix B – Boiler Altitude Derate Schedule at the end of this manual. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 60: Adjusting High Fire

    When the boiler is in standby, prepurge, or postpurge the flame signal should read 0V. During main flame, a strong flame signal should read between 8-30V. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 61: Initial Nuro Control Setup And Adjustment

    When the boiler or water heater is powered on, the NURO touchscreen will display an initial Startup Screen then the Local Representative screen. This shows the name, address and phone number of the local Patterson Kelley representative. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 62: Home Screen

    NOTE For more information on any value, please refer to the NURO Boiler Controller: Advanced User’s Guide, Part Number is 1004905979. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 63: Setup Wizard

    220-480 Three Less than 20 2913 2,880,000 SL-3000 3,000,000 220-480 Three Less than 20 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 53...
  • Page 64: Operations

    ANSI Z21.13/CSA 4.9, latest edition. (See "Factory Firetest" label on the rear surface of the boiler). © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 65: Normal Lighting And Shut-Down Procedures

    © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 66: Maintenance

    NOTICE! Proper maintenance schedule and record electrocution, injury, or death. keeping is critical for optimum performance and to maintain the Patterson-Kelley warranty. Label all wires prior to disconnection NOTE: The combustion blower motor is permanently when servicing controls. Wiring errors lubricated and does not require periodic lubrication.
  • Page 67: Semi-Annually

    Use high-calcium (or pure) limestone. 8. Examine the venting system. Refer to the vent manufacturer's instructions for requirements in addition to those listed below. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 68: Maintenance And Inspection Schedule

    This schedule applies when the boiler is in constant use. The section is divided into critical Semi- Annual and Annual Maintenance followed by scheduled routine maintenance. 5.3 Cleaning the Burner & Combustion Chamber Patterson-Kelley recommends cleaning the burner and combustion chamber once annually: Required Replacement Parts NOTE Spare parts and replacement parts can be ordered from Patterson Kelley by calling toll free (877) 728-5351.
  • Page 69 Vacuum cleaner method – Vacuum the burner, being careful not to rub or scrape the fiber mesh. b. Water Flush – Water Only! – Rinse the burner down. Allow time to dry completely. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 70 Gradually tighten the eight (8) M6 nuts using an 11mm socket or wrench in the order as shown in the image below to a torque of 7.4 ft.-lbs © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 71 Double check the tightness of all bolted joints. PRECAUTIONS ASSOCIATED WITH HANDLING REFRACTORY LINING MATERIAL • This Patterson-Kelley product contains a Combustion Area lined with REFRACTORY CERAMIC FIBERS (RCFs) similar to many other devices produced in this industry. • RCFs have been identified by the International Agency for Research on Cancer (IARC) as possibly being carcinogenic to Humans.
  • Page 72: After Repairs Or Maintenance

    NOTE Installation and service must be performed by a qualified installer or service agency that has been trained on the Patterson-Kelley boiler. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 73: Sequence Of Operations

    The NURO control will display graphical and/or text based error descriptions to announce any problems with the boiler. There are two types of lockouts: manual reset lockouts which require the operator to © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 74: Loss Of Power

    Ensure there is no air flow through the boiler when the blower is offline. An excessive negative draft in the flue piping can cause air flow through the offline boiler which may be strong enough to maintain closure of the air switch. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 75: Flame Failure

    When the blockage is removed, the boiler will automatically restart. If no blockage is found, it may be necessary to replace the high exhaust back pressure switch. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 76: Parts/Technical Support

    Technical Service 1.877.728.5351 6 Parts/Technical Support Spare parts and replacement parts can be ordered from Use of Non-Factory Authorized Patterson-Kelley by calling toll free (877) 728-5351. Reach replacement parts are not us by fax at (570) 476-7247. recommended for this equipment.
  • Page 77: Terminal Block Assignments

    4-20mA ANALOG INPUT [+] ENABLE / DISABLE Contact Closure Enables Comfort Heat Operation ENABLE / DISABLE Open Circuit Disables Comfort Heat Operation © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 78: Terminal Block Assignments - High Voltage (Tb2) Terminal Block

    External Interlock Circuit #1 START INTERLOCK #1 START INTERLOCK #2 External Interlock Circuit #2 (In Series w/ #1) START INTERLOCK #2 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 79: Wiring Diagrams

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 6.2 Wiring Diagrams SL-1500 & SL-2000 Natural Gas © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 80 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 70...
  • Page 81 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 SL-2500 & SL-3000 (208-240V) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 71...
  • Page 82 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 72...
  • Page 83 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 SL-2500 & SL-3000 (480V) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 73...
  • Page 84 P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 74...
  • Page 85: Wiring Diagram - Power Box 240V (Sl-2500 & Sl-3000 Only)

    Technical Service 1.877.728.5351 Wiring Diagram – Power Box 240V (SL-2500 & SL-3000 Only) Wiring Diagram – Power Box 480V (SL-2500 & SL-3000 Only) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 86: Boiler Parts Identification (Sl-1500 & Sl-2000)

    Gas Fired Boiler Technical Service 1.877.728.5351 6.3 Boiler Parts Identification (SL-1500 & SL-2000) Main Boiler Assembly (SL-1500 & SL-2000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 87: Nuro Control Panel (Sl-1500 & Sl-2000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 NURO Control Panel (SL-1500 & SL-2000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 77...
  • Page 88: Heat Exchanger Assembly (Sl-1500 & Sl-2000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Heat Exchanger Assembly (SL-1500 & SL-2000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 78...
  • Page 89: Natural Gas Train (Sl-1500 & Sl-2000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Natural Gas Train (SL-1500 & SL-2000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 79...
  • Page 90: Burner & Blower Assembly (Sl-1500 & Sl-2000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Burner & Blower Assembly (SL-1500 & SL-2000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 80...
  • Page 91: Boiler Parts Identification (Sl-2500 & Sl-3000)

    Gas Fired Boiler Technical Service 1.877.728.5351 6.4 Boiler Parts Identification (SL-2500 & SL-3000) Main Boiler Assembly (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved.
  • Page 92: Nuro Control Panel (Sl-2500 & Sl-3000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 NURO Control Panel (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 82...
  • Page 93: Main Power Box (Sl-2500 & Sl-3000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Main Power Box (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 83...
  • Page 94: Heat Exchanger Assembly (Sl-2500 & Sl-3000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Heat Exchanger Assembly (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 84...
  • Page 95: Natural Gas Train (Sl-2500 & Sl-3000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Natural Gas Train (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 85...
  • Page 96: Burner & Blower Assembly (Sl-2500 & Sl-3000)

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 Burner & Blower Assembly (SL-2500 & SL-3000) © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 86...
  • Page 97: K Solis™ Specific Limited Warranty

    Last Updated 12/12/2016 Subject to the terms and conditions herein and the Terms and Conditions of Sale (as defined herein), Patterson-Kelley (“Seller”) warrants to the purchaser of the product (“Buyer”) that the heat exchanger and burner are free of defects in material and workmanship, when...
  • Page 98 No sales representative, agent, or employee of Seller or any reseller in the chain of sale of the product is authorized to make any modification, extension, or addition to this Specific Limited Warranty, unless agreed to in writing by Seller. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 99: Boiler Fire-Test Report

    P-K SOLIS™ Gas Fired Boiler Technical Service 1.877.728.5351 8 Boiler Fire-Test Report © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 89...
  • Page 100: Appendix A - Maintenance Log

    Appendix A – Maintenance Log Hi Fire / Stack Date Action Low Fire Temp © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 90...
  • Page 101: Appendix B - Boiler Altitude Derate Schedule

    Although the appliance’s capacity is reduced due to the lower air density, the combustion tuning should follow the standard combustion guidelines of 3.11. Tune the combustion for the same O and CO levels as discussed in 3.11.2. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 102: Appendix C - Water Quality Standards Quality Standards For Hydronic Boilers In Multi-Metal Systems

    Appendix C – Water Quality Standards Quality Standards for Hydronic Boilers in Multi-Metal Systems Patterson-Kelley boilers are designed to be incorporated into any multi-metal hydronic heating system. All multi-metal hydronic systems require that attention be paid to water treatment. The chemical additives for any multi-metal system must be specifically formulated for use with all the various metals used in that system.
  • Page 103: Appendix D - Best Practices For New & Retrofit Systems

    This strainer is not intended to remove fine particulate matter from the boiler system which will be discussed later in this appendix. 4. Patterson-Kelley recommends installing a water meter on the cold water fill piping. The intention of this device is to periodically monitor the amount of fresh water introduced into the system piping.
  • Page 104 (blended) sample. 11. Within the first three months after startup, Patterson-Kelley recommends collecting a follow-up water sample from the hydronic system. This should be compared to the initial startup sample in order to determine any changes in pH, Alkalinity, conductivity, etc.
  • Page 105: Appendix E - Installation And Quick Reference

    Maximum Inlet Pressure = 14.0” W.C. NOTE: Patterson-Kelley recommends installing an individual lock-up type gas regulator in the gas supply piping to each boiler. For installations where one master lock-up type gas pressure regulator will service multiple boilers, Patterson-Kelley recommends contacting the local regulator representative for application assistance specifying the appropriate lock-up type regulator and gas pipe sizing.
  • Page 106: Appliance Connections (Sl-1500 & Sl-2000)

    Gas Fired Boiler Technical Service 1.877.728.5351 Appliance Connections (SL-1500 & SL-2000) All connections must be in compliance with national, state, and local code requirements. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 107: Appliance Connections (Sl-2500 & Sl-3000)

    Gas Fired Boiler Technical Service 1.877.728.5351 Appliance Connections (SL-2500 & SL-3000) All connections must be in compliance with national, state, and local code requirements. © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx...
  • Page 108 SOLIS™ SL-1500 through SL-3000 boilers. This information is useful to help size an appropriate circulation pump. Keep in mind this pressure drop represents the boiler only, additional consideration is needed for any connecting piping, valves, strainers, couplings, flanges, etc. P-K SOLIS SL-1500 through SL-3000 Boilers: Minimum & Maximum Flow Rates Flow Rate Flow...
  • Page 109 4.1 ft 228 GPM 7.3 ft 285 GPM 10.3 ft 342 GPM 14.8 ft © Patterson-Kelley 2021 Revised: March 15, 2021 2701000090 P-K SOLIS NURO Installation and Released: March 15, 2021 Owners Manual (Rev A).docx All Rights Reserved. Page 99...