Specifications - Carrier VVT Bypass Installation And Startup Manual

Hide thumbs Also See for VVT Bypass:
Table of Contents

Advertisement

Specifications

Driver
Power
BACnet port
Rnet port
Local Access port
Inputs
Input resolution
Analog output
Output resolution
Integral airflow sensor
Integral actuator
Battery
Protection
BT485 connector
Status indicators
Environmental operating
range
Storage temperature range
Physical
VVT Bypass Controller
Installation and Start-up Guide
drv_bpopen_x-xx-xxx
24 Vac ±10%, 50–60 Hz
14 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
For communication with the controller network using BACnet ARC156 (156 kbps)
or BACnet MS/TP (9600 bps – 76.8 kbps)
For connecting an Equipment Touch
For system start-up and troubleshooting
1 input for connecting the Duct air temperature sensor (#33ZCSENDAT)
10 bit A/D
1 analog output, 0–10 Vdc (5 mA max)
The controlled device must have a minimum of 2000 Ohms resistance measured
from its input to ground and must share the same ground as the controller.
8 bit D/A
Precision low flow AWM series 0–2 in. H20 (0-.498 kPa), sensitive down to
±0.001 in. H
0 (±.00025 kPa). Barbed tapered airflow connections accept 3/16
2
in. (4.75 mm) I.D. tubing. Allows for readings across the 0–2 in. H
range, accurate to ±5% of full flow at 2 in. H
Brushless DC motor, torque 35 inch-pounds (4 Nm), runtime 205 seconds for 90
degree travel during control, or 25 seconds in high-speed test and balance mode
10-year Lithium CR2032 battery retains the following data for a maximum of
10,000 hours during power outages: control programs, editable properties,
schedules, and trends.
Incoming power and network connections are protected by non-replaceable
internal solid-state polyswitches that reset themselves when the condition that
causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
You attach a BT485 (not included) to a controller at the beginning and end of a
network segment to add bias and to terminate a network segment.
LED's indicate status of communications, running, errors, power, and digital
outputs
0 to 130°F (-18 to 54°C), 0 to 90% relative humidity, non-condensing
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
UL94-5VA plenum rated enclosure for installation in plenum (or other space for
environmental air) in accordance with NEC Section 300.22 (c) and (d)
Carrier Proprietary and Confidential
3
0 (0 - .498 kPa)
2
0 (.498 kPa).
2
CARRIER CORPORATION ©2017
All rights reserved