Maintenance - Carrier VVT Bypass Installation And Startup Manual

Hide thumbs Also See for VVT Bypass:
Table of Contents

Advertisement

Point Name/Description
Test and Balance
Zero Cal – Closes the bypass damper and waits for the air source to go to the
Off mode before zeroing out the static pressure sensor. This does not occur if
the static pressure is > .05 in. H
Pressure Sensor Cal – Allows you to calibrate the pressure sensor after the
Zero Cal has been performed. To enter a value here, neither the damper nor
the pressure sensor can be locked, the bypass cannot be in LAT mode and the
damper position must be >0% and <100%. The value entered will be the actual
static pressure measured with an accurate static pressure measuring device.
Damper Full Open – Overrides the damper to its full open position.
Automatic Control – Returns the damper to its normal control routines. This
must be activated when you finish using any of the other Test and Balance
commands.
Damper Full Close – Overrides the damper to its full closed position.
Local Sensor Calibration
Supply Air Temperature – Displays the current supply air temperature.
Supply Air Temp Calibration – A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.

Maintenance

Navigation:
Point Name/Description
Static Pressure – The current supply duct static pressure.
Controlling Pressure Setpoint – The active static pressure setpoint that the bypass
controls to.
Max Duct Pressure Setpoint – The Pressure Control Deadband that is added to the
active static pressure setpoint.
Min Duct Pressure Setpoint – The Pressure Control Deadband that is subtracted from
the active static pressure setpoint.
VVT Bypass Controller
Installation and Start-up Guide
O (.0125 kPa) .
2
i-Vu® / Field Assistant:
Carrier Proprietary and Confidential
Appendix A: VVT Bypass Controller Points/Properties
Properties
Control Program
>
31
Default/Range
R:
-56 to 245°F
(-48.9 to 118.3°C)
R:
-20 to 20 °F
(-11.1 to 11.1 °C)
Maintenance
>
Range
R:
0 to 2.0 in. H
O
2
(0 to .498 kPa
R:
.1 to 2.0 in. H
2
(.025 to .498 kPa)
R:
0 to 2.0 in. H
O
2
(0 to .498 kPa
R:
0 to 2.0 in. H
O
2
(0 to .498 kPa
CARRIER CORPORATION ©2017
All rights reserved
O