Contents Introduction .................................. 1 What is the RTU Open controller? ........................1 Safety considerations & handling warning ....................... 3 Wiring inputs and outputs ............................4 Communications wiring .............................. 6 Protocol overview ..............................6 BACnet MS/TP ..............................7 To set up the RTU Open for BACnet MS/TP ..................7 Troubleshooting BACnet MS/TP ......................
Page 4
Contents Appendix A: Network Points List for RTU Open ...................... 35 Network points list for BACnet and Modbus ....................35 Network points list for N2 and LonWorks ...................... 43 Appendix B: BACnet Protocol Implementation Conformance Statement ............46 Appendix C: Modbus Protocol Implementation Conformance Statement............47 Appendix D: Johnson N2 Protocol Implementation Conformance Statement ............
Introduction What is the RTU Open controller? The RTU Open controller (part# OPN-RTUM2) is available as an integrated component of a Carrier rooftop unit, or as a field-installed retrofit product. NOTE The RTU Open controller is available in both English or Metric units. The metric version has (-M) appended to the part number.
The BACnet device instance is automatically generated based on the scheme 16101xx, where “16” is the BACnet vendor ID for Carrier Corporation, and xx equals the rotary switch address. EXAMPLE To set the controller’s MS/TP MAC address to 01, point the arrow on the MSB (SW1) switch to 0 and the arrow on the LSB (SW2) switch to 1.
Communications wiring The following example shows the DIP switches set for 76.8k (Carrier default), and MS/TP. Connect the MS/TP network to the controller's J19 port. Connect to Net+, Net-, and SHLD. Wire specifications A dedicated 22 AWG shielded twisted pair wire (EIA 485) ○...
• Heat pump units utilizing a reversing valve output for heating and cooling control • Heat pump unit (Carrier) with an OEM defrost control board • Economizer, CO2, Demand Limiting, and RH control strategies are available for appropriately equipped units •...
Sequence of Operation Dehumidification The RTU Open provides occupied and unoccupied dehumidification on units that are equipped with the Carrier Humidi-MiZer™ option from the factory. This requires a space relative humidity sensor or a humidistat for control. The following conditions must be true for the dehumidification control to operate: •...
Compressor Safety may be configured on Binary Input 3. A compressor safety tripped indicator circuit is available on most Carrier rooftop equipment. A Compressor Safety Alarm is shown on Properties page > Equipment tab > Alarms and indicates that the equipment requires attention.
• If it's a Carrier Heat Pump HP Y1/W1 Ctrl, there is only 1 auxiliary heat stage output and the staging is done by the machine itself. The RTU Open control does not take any action.
Configuration > Compressor States value is not set to Two Stages. Airside Linkage Alarm - An RTU Open may act as an air source in a zoned system. Carrier systems use a function called Linkage™ to pass data between a master zone and its air source over an MS/TP network connection. When the RTU Open is part of a linked system, it will indicate an airside linkage alarm if it loses communications with its linkage master or if it receives data from more than 1 master zone.
RTU Open prior to installation. Contact your Carrier representative for this .XIF file. LonWorks is an open protocol that requires the use Echelon's Neuron microprocessor to encode and decode the LonWorks packets.