Contents Introduction .................................. 1 What is the RTU Open controller? ........................1 Safety considerations & handling warning ....................... 3 Communications wiring .............................. 4 Protocol overview ..............................4 BACnet MS/TP ..............................5 To set up the RTU Open for BACnet MS/TP ..................5 Adjusting BACnet MS/TP properties using an Equipment Touch ............
Page 4
Contents FCC Compliance ..............................40 BACnet Compliance............................40 CE Compliance ..............................40 Appendix A: Network Points List for RTU Open ...................... 41 Third party access to BACnet points in a controller ..................41 Network points list for BACnet and Modbus ....................44 Network points list for N2 and LonWorks ......................
Introduction What is the RTU Open controller? The RTU Open controller (part# OPN-RTUM2) is available as an integrated component of a Carrier rooftop unit, or as a field-installed retrofit product. NOTE The RTU Open controller is available in both English or Metric units. The metric version has (-M) appended to the part number.
The BACnet device instance is automatically generated based on the scheme 16101xx, where “16” is the BACnet vendor ID for Carrier Corporation, and xx equals the rotary switch address. EXAMPLE To set the controller’s MS/TP MAC address to 01, point the arrow on the MSB (SW1) switch to 0 and the arrow on the LSB (SW2) switch to 1.
Set the remaining DIP switches as follows: BACnet MS/TP DIP switch settings The following example shows the DIP switches set for 76.8k (Carrier default), and BACnet MS/TP. Connect the BACnet MS/TP network to the controller's J19 Network Comm port. Connect to Net+, Net-, and SHLD.
Done. Click Save. Troubleshooting BACnet MS/TP communication For detailed troubleshooting and a list of supported objects, get the controller's BACnet PICS from the Carrier BACnet PICS website http://www.bacnetinternational.net/catalog/index.php?m=28. You must get your BACnet Object list from the manufacturer. The most common communication problems are the result of not properly following the configuration steps outlined in this manual.
The BACnet device instance is automatically generated based on the scheme 16101xx, where “16” is the BACnet vendor ID for Carrier Corporation, and xx equals the rotary switch address. EXAMPLE To set the controller’s MAC address to 01, point the arrow on the MSB (SW1) switch to 0 and the arrow on the LSB (SW2) switch to 1.
Heat pump units utilizing a reversing valve output for heating and cooling control Heat pump unit (Carrier) with an OEM defrost control board Economizer, CO2, Demand Limiting, and RH control strategies are available for appropriately equipped units ...
Sequence of Operation Dehumidification The RTU Open provides occupied and unoccupied dehumidification on units that are equipped with the Carrier Humidi-MiZer™ option from the factory. This requires a space relative humidity sensor or a humidistat for control. The following conditions must be true for the dehumidification control to operate: ...
Compressor Safety may be configured on Binary Input 3. A compressor safety tripped indicator circuit is available on most Carrier rooftop equipment. A Compressor Safety Alarm is shown on Properties page > Control Program tab > Alarms and indicates that the equipment requires attention.
If it's a Carrier Heat Pump HP Y1/W1 Ctrl, there is only 1 auxiliary heat stage output and the staging is done by the machine itself. The RTU Open control does not take any action.
Configuration > Compressor States value is not set to Two Stages. Airside Linkage Alarm - An RTU Open may act as an air source in a zoned system. Carrier systems use a function called Linkage™ to pass data between a master zone and its air source over an MS/TP network connection. When the RTU Open is part of a linked system, it will indicate an airside linkage alarm if it loses communications with its linkage master or if it receives data from more than 1 master zone.
Page 39
SAV requires the unit’s fan be controlled by a VFD to provide variable speed fan operation. SAV operation is standard on the Carrier 3-stage LC Weather Expert units but can also be used with other 2-stage heat/cool units. To obtain SAV operation on those units, the Fan Control must be set to Variable Speed. In this mode, the fan runs at the lowest speed possible, saving energy and preventing excessive air from being bypassed during heating or cooling operation.
RTU Open prior to installation. Contact your Carrier representative for this .XIF file. LonWorks is an open protocol that requires the use Echelon's Neuron microprocessor to encode and decode the LonWorks packets.