Installing the VVT Bypass Controller
NOTE For proper operation and to prevent damage to the devices, use the same polarity for the actuator's
power and the VVT Bypass Controller's power.
Linked actuators
You can wire up to 4 of the following Belimo actuators to the VVT Bypass Controller's analog output. Link
actuators whose travel times and other parameters coincide.
LMX24-MFT P-10028
NMX24-MFT P-10028
AMX24-MFT P-10028
1
Install the actuators according to the manufacturer's instructions.
2
Wire the actuators to the controller using the diagram below.
3
Set the direction rotation switch on each actuator to CW.
VVT Bypass Controller
Installation and Start-up Guide
45 in.-lb (5 Nm) actuator with 0–10 Vdc control
90 in.-lb (10 Nm) actuator with 0–10 Vdc control
180 in.-lb (20 Nm) actuator with 0–10 Vdc control
Carrier Proprietary and Confidential
14
CARRIER CORPORATION ©2017
All rights reserved