H7CX (Counter Function)
Output
K-2
Reset/
mode
reset 1
setting
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
D
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
L
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
H
Reset/
reset 1
999999
Set
value 2
Set
value 1
0
−99999
OUT1
OUT2
Note:
1. Counting cannot be performed during reset/reset 1 input.
2. If reset/reset 1 is input while one-shot output is ON, one-shot output turns OFF.
3. If the count is reached while one-shot output is ON, the one-shot output is newly generated.
Input mode
UP/DOWN A, B, C
H7CX (Counter Function)
(The one-shot output time
can be set in the range 0.01
to 99.99 s.)
One-shot
Instantaneous
Self-holding
output
(equals) output
output
Operation after count
completion
The display continues to increase/
decrease until the overflow or un-
derflow value is reached. One-shot
output only.
The display continues to increase/
decrease until the overflow or un-
derflow value is reached. The out-
puts are ON while the count is
equal.
The display continues to increase/
decrease until the overflow or un-
derflow value is reached.
OUT1 is held while the present val-
ue is less than or equal to set value
1. OUT2 is held while the present
value is greater than or equal to set
value 2.
The display continues to increase/
decrease until the overflow or un-
derflow value is reached.
OUT1 is held while the present val-
ue is greater than or equal to set
value 1. OUT2 is held while the
present value is greater than or
equal to set value 2.
Note:
H mode is available for 2-stage
models only.
21