Completing The Test; Metering; Pulse-Counter Logic Pcfcnt; Function For Energy Calculation And Demand Handling Etpmmtr - ABB Relion 670 Series Commissioning Manual

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 403-UUS Rev. K
p
EQUATION124 V1 EN-US
in % for single-phase-to-ground faults
p
EQUATION125 V1 EN-US
in % for single-phase-to-ground faults with mutual zero sequence current.
Where:
p
Z
X0
X1
XM
11.13.14.4

Completing the test

Continue to test another function or end the test by changing the TESTMODE setting to Disabled.
Restore connections and settings to the original values, if changed for testing purposes.
11.14

Metering

11.14.1

Pulse-counter logic PCFCNT

The test of the Pulse-counter logic function PCFCNT requires the Parameter Setting tool in PCM600 or
an appropriate connection to the local HMI with the necessary functionality. A known number of pulses
with different frequencies are connected to the pulse counter input. The test should be performed with
settings Operation = Enable or Operation = Disable and the function blocked or unblocked. The pulse
counter value is then checked in PCM600 or on the local HMI.
11.14.2

Function for energy calculation and demand handling ETPMMTR

Prepare the IED for verification of settings as outlined in section "Overview " and section "Preparing for
test" in this chapter.
11.14.2.1

Verifying the settings

Common test equipment can be used to determine the injection of current and voltage and time
measurement.
Verification of EAFACC & ERFACC output
Bay control REC670
Commissioning manual
×
3 Z
=
×
x
100
+ ×
X0 2 X1
×
3 Z
x
-------------------------------------------- - 100
×
=
×
±
X0 2 X1 XM
+
= the expected value of a distance to fault in percent
= set test point on the test set
x
= set zero-sequence reactance of a line
= set positive-sequence reactance of a line
= set mutual zero-sequence impedance of a line
© 2017 - 2021 Hitachi Power Grids. All rights reserved
Section 11
Testing functionality by secondary injection
(Equation 53)
(Equation 54)
SEMOD53588-1 v1
GUID-4FC03017-93BD-4B30-A874-487BF89971D5 v1
GUID-F8F0D384-BC70-48CA-817E-EB9BFBD68A54 v3
M14955-84 v6
M13405-2 v7