Line differential protection RED670
Version 2.2
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 670 Series

  • Page 1 ® Relion 670 SERIES Line differential protection RED670 Version 2.2 Product guide...
  • Page 2: Table Of Contents

    The information in this document is subject to change without notice and should not be construed as a commitment by Hitachi Power Grids. Hitachi Power Grids assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding. ABB is a registered trademark of ABB Asea Brown Boveri Ltd.
  • Page 3: Document Revision History

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Issued: September 2020 Revision: N 1. Document revision history GUID-34B323E4-1319-4D42-80CE-29B0F2D36E2C v4 Table 1. Document revision history Document Date Product revision History revision 2017-07 2.2.0 First release for product version 2.2 2017-10 2.2.1 Ethernet ports with RJ45 connector added.
  • Page 4: Application

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Disturbance recording and fault locator are available to allow independent post-fault analysis after primary 2. Application disturbances. The Disturbance recorder will also show M13635-3 v9 The Intelligent Electronic Device (IED) is used for the remote station currents, as received to this IED, time protection, control and monitoring of overhead lines compensated with measure communication time.
  • Page 5 On request, ABB is available to support the re-configuration The basic delivery includes one binary input module and work, either directly or to do the design checking.
  • Page 6 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration A42 GUID-A3E1E81D-9278-4AC1-8AAA-AD0D56DABE23 v2 RED670 A42 – Single breaker with single or three phase tripping 12AI (6I+6U) WA2_VT VN MMXU WA1_VT Control Control Control S SCBR S SCBR S XCBR VN MMXU 1→0...
  • Page 7 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration B33 GUID-1231CFD6-8CEF-464E-8124-E9F7EFD0FF62 v2 RED670 B33 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control Control 50BF 3I>BF 52PD S SCBR S SCBR S SCBR CC PDSC VN MMXU...
  • Page 8 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration B42 GUID-D1058782-6EAD-4E94-8513-1D3647E67250 v2 RED670 B42 – Multi breaker with single or three phase tripping 12AI (6I+6U) WA1_VT WA1_CT Control Control 52PD Control 50BF 3I>BF S SCBR S SCBR S SCBR CC PDSC VN MMXU...
  • Page 9 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Description of configuration C42 GUID-C82DE474-FDC4-49CF-AF12-445716D9C6B6 v2 RED670 C42 – Single breaker with single or three phase tripping and back-up distance protection 12AI (6I+6U) 21FL DFR/SER DR DRP RDRE LMB RFLO WA2_VT VN MMXU WA1_VT...
  • Page 10: Available Functions

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 3. Available functions GUID-F5776DD1-BD04-4872-BB89-A0412B4B5CC3 v1 The following tables list all the functions available in the IED. Those functions that are not exposed to the user or do not need to be configured are not described in this manual.
  • Page 11: Differential Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Differential protection HZPDIF High impedance differential protection, single 3-A02 3-A02 3-A02 3-A02 phase REFPDIF Restricted earth fault protection, low impedance 0–2 L3CPDIF Line differential protection for 3 CT sets, 2-3 line...
  • Page 12 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ZMRPDIS, Distance measuring zone, quad characteristic ZMRAPDIS separate Ph-Ph and Ph-E settings FRPSPDIS Phase selection, quadrilateral characteristic with settable angle ZMFPDIS High speed distance protection, quad and mho...
  • Page 13: Current Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Back-up protection functions GUID-A8D0852F-807F-4442-8730-E44808E194F0 v16 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Directional phase overcurrent 51_67 protection, four steps EFPIOC Instantaneous residual overcurrent protection...
  • Page 14: Frequency Protection

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) VDCPTOV Voltage differential protection LOVPTUV Loss of voltage check PAPGAPC Radial feeder protection Frequency protection SAPTUF Underfrequency protection 3-E04 3-E04 3-E04...
  • Page 15: Control

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Control and monitoring functions GUID-E3777F16-0B76-4157-A3BF-0B6B978863DE v20 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 2-H05 1-H04 2-H05 1-H04 APC10 Control functionality for a...
  • Page 16: Logic

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103POSCMD IED commands with position and select for IEC 60870-5-103 I103POSCMDV IED direct commands with position for IEC 60870-5-103 I103IEDCMD IED commands for IEC...
  • Page 17 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ANDQT, Configurable logic blocks Q/T INDCOMBSPQT, (see Table 6) INDEXTSPQT, INVALIDQT, INVERTERQT, ORQT, PULSETIMERQT, RSMEMORYQT, SRMEMORYQT, TIMERSETQT, XORQT AND, GATE, INV, Extension logic package (see LLD, OR,...
  • Page 18: Monitoring

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Monitoring CVMMXN Power system measurement CMMXU Current measurement VMMXU Voltage measurement phase-phase CMSQI Current sequence measurement VMSQI Voltage sequence measurement VNMMXU Voltage measurement...
  • Page 19: Metering

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) I103AR Function status auto- recloser for IEC 60870-5-103 I103EF Function status earth-fault for IEC 60870-5-103 I103FLTPROT Function status fault protection for IEC 60870-5-103 I103IED...
  • Page 20 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 3. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 4. Number of function instances in APC10 Function name Function description Total number of instances...
  • Page 21 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 5. Number of function instances in APC15 Function name Function description Total number of instances SCILO Interlocking BB_ES A1A2_BS A1A2_DC ABC_BC BH_CONN BH_LINE_A BH_LINE_B DB_BUS_A DB_BUS_B DB_LINE ABC_LINE AB_TRAFO SCSWI Switch controller SXSWI...
  • Page 22 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 7. Total number of instances for extended logic package Extended configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SLGAPC SRMEMORY TIMERSET VSGAPC Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 23 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Communication GUID-5F144B53-B9A7-4173-80CF-CD4C84579CB5 v18 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC60870-5-103 for SLM...
  • Page 24 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 AGSAL Generic security application component LD0LLN0 IEC 61850 LD0 LLN0 SYSLLN0...
  • Page 25 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) QUALEXP IEC 61850 quality expander Remote communication BinSignRec1_1 Binary signal transfer, receive 3/3/6 3/3/6 3/3/6 3/3/6 3/3/6 BinSignRec1_2 BinSignReceive2 BinSignTrans1_1 Binary signal transfer, transmit...
  • Page 26 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 IEC 61850 or ANSI Function description Line Differential function name RED670 (Customized) ZC1WPSCH Current reversal and weak-end infeed 1-B05 1-B05 1-B05 1-B05 logic for phase segregated communication ZCLCPSCH Local acceleration logic 1-B35 1-B35 1-B35...
  • Page 27: Basic Ied Functions

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Basic IED functions GUID-C8F0E5D2-E305-4184-9627-F6B5864216CA v14 Table 9. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN, Time synchronization SYNCHGPS, SYNCHCMPPS,...
  • Page 28 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 9. Basic IED functions, continued IEC 61850 or function Description name ALTMS Time master supervision ALTIM Time management CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools information COMSTATUS Protocol diagnostic...
  • Page 29 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 measured by one and sometimes by two three-phase current transformer (CT) groups. The voltages at all YNdx ends are also measured if the exact method is selected for charging current compensation. The protected zone is determined by the positions of the CTs at all ends of Autotransformer the protected circuit.
  • Page 30 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Protected zone Comm. Channel Comm. Channel Comm. Channel IEC05000040_2_en.vsd IEC05000040 V2 EN-US Figure 7. Example of application on a three-terminal line with 1½ breaker arrangements The current differential algorithm provides high differential protection can be time-delayed for low sensitivity for internal faults and it has excellent differential currents to achieve coordination with...
  • Page 31 In this versions than 670 1.2.3 must be verified system, a 64 kbits/s or 2 Mbit/s communication channel with ABB. is only needed between the master and each one of the slave IEDs. The Master-Slave condition for the...
  • Page 32 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 protection logic to always release operation for all faults Distance measuring zone, quadrilateral characteristic detected by the differential function. LDRGFC consists (ZMQPDIS) together with Phase selection with load of four sub functions: encroachment (FDPSPDIS) has functionality for load encroachment, which increases the possibility to detect •...
  • Page 33 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Quadrilateral characteristic is available. this matter. Phase selection, quadrilateral characteristic with fixed angle (FDPSPDIS) is designed to accurately Distance measuring zone, quadrilateral characteristic select the proper fault loop in the distance function for series compensated lines (ZMCPDIS) function has dependent on the fault type.
  • Page 34 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Forward operation Operation area Operation area Operation area Reverse No operation area No operation area operation IEC07000117-2-en.vsd IEC07000117 V2 EN-US Figure 13. Load encroachment influence on the offset mho characteristic en05000034.vsd IEC05000034 V1 EN-US Figure 14.
  • Page 35 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Faulty phase identification with load encroachment FMPSPDIS SEMOD153825-5 v7 The ability to accurately and reliably classify different Forward types of fault so that single phase tripping and operation autoreclosing can be used plays an important roll in today's power systems.
  • Page 36 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 the possibility to enlarge the resistive setting of both High speed distance protection ZMFCPDIS is the phase selection and the measuring zones without fundamentally the same function as ZMFPDIS but interfering with the load.
  • Page 37 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 fault type and thereby, reliable fault clearance can be Two current channels I3P1 and I3P2 are available in achieved for faults during power swing. OOSPPAM function to allow the direct connection of two groups of three-phase currents;...
  • Page 38 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Synchrophasor data can be reported to up to 8 clients Automatic switch onto fault logic, voltage and over TCP and/or 6 UDP group clients for multicast or current based ZCVPSOF unicast transmission of phasor data from the IED.
  • Page 39 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 protection being out of service due to communication or directional zero sequence current can be used. Current voltage transformer circuit failure. reversal and weak-end infeed functionality are available. Sensitive directional residual overcurrent and power EF4PTOC has an inverse or definite time delay protection SDEPSDE independent for each step.
  • Page 40 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 CCRBRF provides three different options to select how flow in the power system. There are a number of t1 and t2 timers are run: applications where such functionality is needed. Some 1.
  • Page 41 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 selective tripping of a faulty line. Alternatively, the Overexcitation protection OEXPVPH function can be used solely for signaling of the earth- M13319-3 v9 When the laminated core of a power transformer or fault location to the SCADA system when the power generator is subjected to a magnetic flux density network is allowed to operate for a longer time with an...
  • Page 42 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 phase(s) in which the phase selection function has shedding and remedial action schemes. SAPFRC can operated. discriminate between a positive or negative change of frequency. A definite time delay is provided for operate. For delayed tripping, single pole and three pole delays are separately and independently settable.
  • Page 43 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 and islanding in grid networks. Voltage based delta Fuse failure supervision FUFSPVC supervision (DELVSPVC) is needed at the grid SEMOD113820-4 v13 The aim of the fuse failure supervision function interconnection point. (FUFSPVC) is to block voltage measuring functions at failures in the secondary circuits between the voltage Current based delta supervision DELISPVC...
  • Page 44 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 asynchronous systems are in phase and can be evaluated with an additional supervision of the status connected. The synchronizing feature evaluates voltage value of the control object. The command sequence with difference, phase angle difference, slip frequency and enhanced security is always terminated by a frequency rate of change before issuing a controlled...
  • Page 45 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Hardware switches are however sources for Reservation function QCRSV maintenance issues, lower system reliability and an M13506-3 v5 The purpose of the reservation (QCRSV) function is extended purchase portfolio. The selector switch primarily to transfer interlocking information between function eliminates all these problems.
  • Page 46 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 types of communication schemes for permissive On verification of a weak end infeed condition, the weak underreaching, permissive overreaching, blocking, delta end infeed logic provides an output for sending the based blocking, unblocking and intertrip are available.
  • Page 47 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 logic for weak-end infeed and current reversal, included • Low active power trip with 2 selection modes '1 out of in Current reversal and weak-end infeed logic for 3' and '2 out of 3' residual overcurrent protection (ECRWPSCH) function.
  • Page 48 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Zero sequence overcurrent protection LCZSPTOC Trip matrix logic TMAGAPC GUID-F0C38DA1-2F39-46DE-AFFE-F919E6CF4A57 v2 Zero sequence components are present in all abnormal M15321-3 v14 The trip matrix logic (TMAGAPC) function is used to conditions involving earth.
  • Page 49 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 • PULSETIMER function block can be used, for example, inputs signal are copied to the corresponding quality for pulse extensions or limiting of operation of output. outputs, settable pulse time. •...
  • Page 50 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 certain logic. Boolean, integer, floating point, string be used for monitoring, supervision, interlocking and types of signals are available. other logics. One FXDSIGN function block is included in all IEDs. 16.
  • Page 51 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 The Disturbance report function is characterized by The event recorder information is available for the great flexibility regarding configuration, starting disturbances locally in the IED. conditions, recording times, and large storage capacity. The event recording information is an integrated part of A disturbance is defined as an activation of an input to the disturbance record (Comtrade file).
  • Page 52 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Analog, integer and double indication values are also Circuit breaker condition monitoring SSCBR transferred through the EVENT function. GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v14 The circuit breaker condition monitoring function Generic communication function for Single Point (SSCBR) is used to monitor different parameters of the indication SPGAPC breaker condition.
  • Page 53 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 • Applicable to very long time accumulation (≤ 99999.9 Voltage harmonic monitoring VHMMHAI hours) GUID-868ED1BB-A921-45DE-94C4-0CF23ECD9ADA v1 Voltage harmonic monitoring function VHMMHAI is used • Supervision of limit transgression conditions and to monitor the voltage part of the power quality of a rollover/overflow system.
  • Page 54: Ethernet

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 reverse directions. These energy values are available as The LHMI is used for setting, monitoring and controlling. output signals and also as pulse outputs. Integration of energy values can be controlled by inputs (STARTACC 19.
  • Page 55: Station Communication

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 communication. SCHLCCH is used for communication Substation Automation (SA) bus or Substation over the rear Ethernet ports, RCHLCCH is used for Monitoring (SM) bus. redundant communications over the rear Ethernet ports Available communication protocols are: and FRONTSTATUS is used for communication over the front port.
  • Page 56 SPA communication protocol Supervison status for IEC 60870-5-103 I103SUPERV SEMOD120134-5 v1 A single glass or plastic port is provided for the ABB SPA I103SUPERV is a function block with defined functions protocol. This allows extensions of simple substation for supervision indications in monitor direction. This automation systems but the main use is for Substation FunctionType parameter;...
  • Page 57: Remote Communication

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 as interface for horizontal peer-to-peer communication IED commands for IEC 60870-5-103 I103IEDCMD (over LON only). I103IEDCMD is a command block in control direction with defined IED functions. All outputs are pulsed and 22.
  • Page 58: Hardware Description

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 designed for 64 kbit/s resp 2Mbit/s operation. The transducers. The module has six independent, converter is delivered with 19” rack mounting galvanically separated channels. accessories. Optical Ethernet module M16073-3 v9 The optical Ethernet module (OEM) provides two 23.
  • Page 59 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Transformer input module TRM M14875-3 v10 The transformer input module is used to galvanically separate and adapt the secondary currents and voltages generated by the measuring transformers. The module has twelve inputs in different combinations of currents and voltage inputs.
  • Page 60 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 11. Case dimensions, continued Case size (mm)/ (inches) The G and H dimensions are defined by the 19” rack mounting kit. Mounting alternatives M16079-3 v14 • 19” rack mounting kit •...
  • Page 61: Connection Diagrams

    1446-18 IEC 61850 Ed2 level A1 10175313-INC 20-2185rev1 certificate issued by DNV GL IEC 61850 Ed1 level B1 1KHL050130 certificate issued by ABB Power Grids Switzerland Ltd, System Verification and Validation Center, SVC Baden IEC 60870-5-103 certificate 10021419-OPE/INC 16-2490 issued by DNV GL DNP 3.0 certificate issued by...
  • Page 62: Technical Data

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 26. Technical data General M10993-1 v4 IP11376-1 v3 Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified requirements Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to...
  • Page 63 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Energizing quantities, rated values and limits Analog inputs M16988-1 v11 IP15842-1 v1 Table 12. TRM - Energizing quantities, rated values and limits for protection transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ±...
  • Page 64 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 13. TRM - Energizing quantities, rated values and limits for measuring transformer Description Value Frequency Rated frequency f 50/60 Hz Operating range ± 10% Current inputs Rated current I Operating range (0-1.8) ×...
  • Page 65 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary inputs and outputs M12576-1 v13 IP15844-1 v1 Table 16. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 66 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 18. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20% Power consumption 24/30 V, 50 mA...
  • Page 67 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12318-1 v11 Table 19. IOM - Binary input/output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and signal relays Fast signal relays (parallel reed relay) Binary outputs Max system voltage 250 V AC/DC 250 V DC...
  • Page 68 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12584-1 v11 Table 20. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay) Binary outputs IOM: 10 IOM: 2...
  • Page 69 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD175395-2 v11 Table 21. SOM - Static Output Module data (reference standard: IEC 61810-1): Heavy duty static binary outputs Function of quantity Static binary output trip Max system voltage 250 V DC Number of outputs Impedance open state High impedance...
  • Page 70 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 22. SOM - Static Output module data (reference standard: IEC 61810-1): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Min load voltage 24 V DC Number of outputs Test voltage across open contact, 1 min...
  • Page 71 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12441-1 v11 Table 23. BOM - Binary output module contact data (reference standard: IEC 61810-1) Function or quantity Trip and Signal relays Binary outputs Max system voltage 250 V AC/DC Min load voltage 24V DC Test voltage across open contact, 1 min...
  • Page 72 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 25. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01%/% Operative range Full wave rectified...
  • Page 73 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Type tests according to standards M16706-1 v15 IP15778-1 v1 Table 27. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3 Ring wave immunity test, 100 kHz...
  • Page 74 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 29. Environmental conditions Description Value Operating temperature range -25°C to +55°C (continuous) Short-time service temperature range -40°C to +70°C (<16h) Note: Degradation in MTBF and HMI performance outside the temperature range of -25°C to +55°C Relative humidity <93%, non-condensing...
  • Page 75 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Differential protection M13062-1 v22 Table 33. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 76 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16023-1 v12 Table 35. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF single IED without communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±1.0% of I at I ≤...
  • Page 77 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 35. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF single IED without communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 10 ms sequence function Max.
  • Page 78 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 36. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 64 Kbit/s communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±4.0% of I at I ≤ I ±4.0% of I at I >...
  • Page 79 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 36. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 64 Kbit/s communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 15 ms sequence function Max.
  • Page 80 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 37. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication Function Range or value Accuracy IBase Minimum operate current (20-200)% of ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 81 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 37. Line differential protection L3CPDIF, L6CPDIF, LT3CPDIF , LT6CPDIF with 2 Mbits/s communication , continued Function Range or value Accuracy **Operate time, unrestrained negative Min. = 10 ms sequence function Max.
  • Page 82 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-6746298E-4C29-44C6-AB59-41EBF408A5E4 v4 Table 38. High speed line differential protection for 4 CT sets, 2-3 line ends L4CPDIF with 2 Mbit/s communication Function Range or value Accuracy Minimum operate current (20-200)% of IBase ±1.0% of I at I ≤...
  • Page 83 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-0BD8D3C9-620A-426C-BDB5-DAA0E4F8247F v4 Table 39. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I Operate voltage, phase to neutral...
  • Page 84 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Impedance protection M13842-1 v15 Table 40. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1 Minimum operate current, (10-1000)% of IBase...
  • Page 85 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173239-2 v10 Table 41. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase Minimum operate residual (5-1000)% of current, zone 1 IBase...
  • Page 86 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173242-2 v14 Table 43. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 5 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, (0.005–3000.000) W/phase ±2.0% static accuracy...
  • Page 87 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD153649-2 v8 Table 45. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: ±2.0% static accuracy (1.00–3000.00) W/ Load resistance, forward and phase Conditions: reverse Voltage range: (0.1–1.1) x U (5–70) degrees...
  • Page 88 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-9E13C38A-3B6D-402B-98A6-6CDA20632CE7 v5 Table 47. Phase selection, quadrilateral characteristic with settable angle FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 89 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-6C2EF52A-8166-4A23-9861-38931682AA7D v8 Table 48. High speed distance protection ZMFPDIS, ZMFCPDIS Function Range or value Accuracy Number of zones 5 selectable directions, 2 fixed directions Minimum operate current, Ph- (5-6000)% of IBase ±1.0% of I Ph and Ph-E Positive sequence reactance...
  • Page 90 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E65CE996-C0CE-4620-8E01-A96896E62802 v1 Table 49. Power swing detection, blocking and unblocking ZMBURPSB Function Range or value Accuracy Reactive reach ±2.0% static accuracy (0.10-3000.00) W/phase Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I Angle: at 0 degrees and 85 degrees Resistive reach (0.10–1000.00) W/loop...
  • Page 91 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BACA37F7-E945-40BC-BF9D-A65BFC96CA91 v9 Table 53. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase and (10 - 90)% of UBase ±0.5% of U UPN< phase-to-neutral undervoltage, UPP< Reset ratio, undervoltage <...
  • Page 92 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v2 Table 54. Phase preference logic PPL2PHIZ Function Range or value Accuracy Operate value, phase-to-phase and (10 - 90)% of UBase ±0.5% of U UPN< phase-to-neutral undervoltage, UPP< Reset ratio, undervoltage <...
  • Page 93 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Wide area measurement system GUID-F0BAEBD8-E361-4D50-9737-7DF8B043D66A v5 Table 56. Protocol reporting via IEEE 1344 and IEC/IEEE 60255-118 (C37.118) PMUREPORT Influencing quantity Range Accuracy Signal frequency ± 0.1 x f ≤ 1.0% TVE Signal magnitude: Voltage phasor (0.1–1.2) x U...
  • Page 94 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Current protection M12336-1 v14 Table 57. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 95 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12342-1 v22 Table 58. Directional phase overcurrent protection, four steps OC4PTOC Function Range or value Accuracy lBase Operate current, step 1-4 (5-2500)% of ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 96 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12340-2 v9 Table 59. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 97 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M15223-1 v18 Table 60. Directional residual overcurrent protection, four steps EF4PTOC Function Range or value Accuracy Operate current, step 1-4 (1-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 98 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E83AD807-8FE0-4244-A50E-86B9AF92469E v6 Table 61. Four step directional negative phase sequence overcurrent protection NS4PTOC Function Range or value Accuracy lBase Operate current, step 1 - 4 (1-2500)% of ±1.0% of I at I £...
  • Page 99 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD173350-2 v16 Table 62. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of IBase Operate level for 3I ·cosj directional ±1.0% of I at I £ I residual overcurrent ±1.0% of I at I >...
  • Page 100 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12352-1 v15 Table 63. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: IEC 60255-149, ±5.0% or ±200 ms whichever is greater...
  • Page 101 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12353-1 v15 Table 64. Breaker failure protection CCRBRF Function Range or value Accuracy lBase Operate phase current (5-200)% of ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >...
  • Page 102 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD175152-2 v11 Table 67. Directional underpower protection GUPPDUP Function Range or value Accuracy SBase Power level (0.0–500.0)% of ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 103 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-7EA9731A-8D56-4689-9072-D72D9CDFD795 v8 Table 70. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 104 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BCCA5F2D-9FF7-4188-9B5D-DA05E8E80CC0 v1 Table 71. Average Power Transient Earth Fault Protection APPTEF Function Range or value Accuracy Minimum operate level for residual (5-80)% of UBase ±0.5% of Ur overvoltage 3Uo> start condition "UN>" Reset ratio for residual overvoltage 3Uo>...
  • Page 105 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Voltage protection M13290-1 v15 Table 72. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U UBase Absolute hysteresis (0.0–50.0)% of ±0.5% of U UBase...
  • Page 106 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M13304-1 v15 Table 73. Two step overvoltage protection OV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 and 2 (1.0-200.0)% of ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 107 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M13317-2 v15 Table 74. Residual overvoltage protection, two steps ROV2PTOV Function Range or value Accuracy UBase Operate voltage, step 1 - step 2 (1.0-200.0)% of ± 0.5% of U at U ≤ U ±...
  • Page 108 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD166919-2 v7 Table 76. Voltage differential protection VDCPTOV Function Range or value Accuracy UBase Voltage difference for alarm and trip (2.0–100.0) % of ±0.5% of U Under voltage level (1.0–100.0) % of UBase ±0.5% of U Independent time delay for voltage...
  • Page 109 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Frequency protection M13360-1 v16 Table 79. Underfrequency protection SAPTUF Function Range or Value Accuracy Operate value, start function, at (35.00 - 75.00) Hz ±2.0 mHz symmetrical three phase voltage, StartFrequency Reset hysteresis 10.0 mHz fixed ±2.0 mHz...
  • Page 110 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M14964-1 v13 Table 80. Underfrequency protection SAPTOF Function Range or Value Accuracy Operate value, start function, (35.00 - 90.00) Hz ±2.0 mHz at symmetrical three phase voltage, StartFrequency 10.0 mHz fixed ±2.0 mHz Reset hysteresis Start time measurement with...
  • Page 111 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Multipurpose protection M13095-2 v11 Table 82. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1- phase2, phase2-phase3, phase3- phase1, MaxPh-Ph, MinPh-Ph, UnbalancePh-Ph...
  • Page 112 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 82. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Start undervoltage, step 1 - 2 (2.0 - 150.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 113 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 82. General current and voltage protection CVGAPC, continued Function Range or value Accuracy Impulse margin time 15 ms typically Undervoltage: Critical impulse time 10 ms typically at 1.2 x U to 0.8 x Impulse margin time 15 ms typically...
  • Page 114 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Secondary system supervision M12358-1 v10 Table 83. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90% Block current...
  • Page 115 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5 Table 85. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur Reset ratio <110% Operate time, block of main fuse failure at 1 x U Min.
  • Page 116 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Control M12359-1 v15 Table 88. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase ±0.5% of U at U ≤...
  • Page 117 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12379-1 v13 Table 89. Autorecloser SMBRREC Function Range or value Accuracy Dead time: shot 1 “t1 1Ph” (0.000-120.000) s ±0.2% or ±35 ms shot 1 “t1 2Ph” whichever is greater shot 1 “t1 3Ph “...
  • Page 118 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Scheme communication M16038-1 v14 Table 90. Scheme communication logic with delta based blocking scheme signal transmit ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking DeltaBlocking Operate voltage, Delta U (0–100)% of UBase...
  • Page 119 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16039-1 v16 Table 92. Current reversal and weak-end infeed logic for distance protection ZCRWPSCH Function Range or value Accuracy Detection level phase-to- (10-90)% of UBase ±0.5% of U neutral voltage Detection level phase-to-phase (10-90)% of UBase ±0.5% of U...
  • Page 120 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M16051-2 v11 Table 96. Current reversal and weak-end infeed logic for residual overcurrent protection ECRWPSCH Function Range or value Accuracy Operate mode of WEI logic Echo Echo & Trip Operate voltage 3U0 for WEI (5-70)% of UBase ±0.5% of U trip...
  • Page 121 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Direct transfer trip GUID-B5714FAE-A87D-4C2D-A167-6CB3522CE1D5 v5 Table 97. Low active power and power factor protection LAPPGAPC Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ±1.0% of S Reset ratio, low active power <105% Operate value, low power factor...
  • Page 122 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C99E063D-B377-40D5-8481-9F46D4166AED v3 Table 100. Carrier receive logic LCCRPTRC Function Range or value Accuracy Operation mode 1 Out Of 2 2 Out Of 2 Independent time delay (0.000-60.000) s ±0.2% or ±35 ms whichever is greater GUID-122A206E-27D2-4D15-AD5A-86B68F1ED559 v6 Table 101.
  • Page 123 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-0E964441-43DE-43B6-B454-485FBBF66B5C v5 Table 103. Negative sequence overcurrent protection LCNSPTOC Function Range or value Accuracy Operate value, negative sequence (3 - 2500)% of IBase ±1.0% of Ir at I ≤ I overcurrent ±1.0% of I at I >...
  • Page 124 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C4ACE306-2A54-483D-B247-A479D48CBF5F v5 Table 105. Three phase overcurrent LCP3PTOC Function Range or value Accuracy Operate value, overcurrent (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 125 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Logic M12380-1 v15 Table 107. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Program Trip action, 3 phase, 1ph/2ph, 1ph/2ph/3ph Minimum trip pulse (0.000-60.000) s ±0.2% or ±15 ms whichever is greater length , tTripMin tWaitForPHS...
  • Page 126 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2 Table 113. Number of INDCALH instances Function Quantity with cycle time 3 ms 8 ms 100 ms INDCALH GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3 Table 114. Number of AND instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 127 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-BE6FD540-E96E-4F15-B2A2-12FFAE6C51DB v2 Table 120. Number of RSMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms RSMEMORY GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2 Table 121. Number of SRMEMORY instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 128 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-77FEBE9B-0882-4E85-8B1A-7671807BFC02 v2 Table 127. Number of INVALIDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms INVALIDQT GUID-F25B94C6-9CC9-48A0-A7A3-47627D2B56E2 v1 Table 128. Number of INVERTERQT instances Logic block Quantity with cycle time 3 ms 8 ms...
  • Page 129 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-1C381E02-6B9E-44DC-828F-8B3EA7EDAA54 v1 Table 134. Number of XORQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms XORQT GUID-19810098-1820-4765-8F0B-7D585FFC0C78 v8 Table 135. Number of instances in the extension logic package Logic block Quantity with cycle time 3 ms...
  • Page 130 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2 Table 139. Number of ITBGAPC instances Function Quantity with cycle time 3 ms 8 ms 100 ms ITBGAPC GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4 Table 140. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC Function Cycle time (ms) Range or value...
  • Page 131 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Monitoring M12386-1 v16 Table 144. Power system measurement CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U ≤ 50 V ±0.2% of U at U >...
  • Page 132 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-ED634B6D-9918-464F-B6A4-51B78129B819 v6 Table 147. Voltage measurement phase-earth VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V Phase angle (5 to 175) V ±0.5 degrees at U ≤...
  • Page 133 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12760-1 v12 Table 151. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 200, first in - first out Time tagging resolution 1 ms See table...
  • Page 134 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v9 Table 153. Insulation supervision for liquid medium function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Oil lockout level 1.00-100.00 ±10.0% of set value or 0.2 whichever is greater Temperature alarm level...
  • Page 135 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12700-1 v5 Table 156. Event list Function Value Buffer capacity Maximum number of events in the list 5000 Resolution 1 ms Accuracy Depending on time synchronizing M13765-1 v6 Table 157. Indications Function Value Buffer capacity...
  • Page 136 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3 Relion® 670 series can store up to 10240 security events. Table 161. Event counter with limit supervision L4UFCNT Function Range or value Accuracy Counter value 0-65535 Hitachi Power Grids ©...
  • Page 137 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 161. Event counter with limit supervision L4UFCNT , continued Function Range or value Accuracy Max. count up speed 30 pulses/s (50% duty cycle) GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1 Table 162. Running hour-meter TEILGAPC Function Range or value Accuracy...
  • Page 138 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-2068BBA0-9026-48D0-9DEB-301BCB3C600C v2 Table 165. Voltage harmonic monitoring VHMMHAI (50/60 Hz) Function Range or value Accuracy Fundamental Harmonic Frequency (0.95 - 1.05) X f 2nd order to 5th order (0.1 - 0.5) X U ±...
  • Page 139 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Metering M13404-2 v5 Table 166. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of (1–3600) s counter value SEMOD153707-2 v5 Table 167.
  • Page 140 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Station communication M15031-1 v9 Table 168. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0 Communication speed for the IEDs...
  • Page 141 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 M12589-1 v5 Table 173. SLM – LON port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000 ft typically *) Plastic fiber: 7 dB (10m/35 ft typically *) Fiber diameter Glass fiber: 62.5/125 mm...
  • Page 142 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 177. SFP - Galvanic RJ45 Quantity Rated value Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for communication using any protocol Standard IEEE 802.3u 100BASE-TX Type of cable...
  • Page 143 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Remote communication M12756-1 v13 Table 179. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Multi-mode fiber Single-mode fiber Single-mode fiber glass 62.5/125 µm...
  • Page 144 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Hardware M11778-1 v7 SEMOD53385-1 v1 Table 181. Case Material Steel sheet Front plate Stainless steel with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) M12327-1 v5 Table 182.
  • Page 145 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3 Because of limitations of space, when ring lug terminal is ordered for Binary I/O connections, one blank slot is necessary between two adjacent I/O modules. Please refer to the ordering particulars for details.
  • Page 146 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Basic IED functions M11963-1 v5 Table 189. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out M12331-1 v9 Table 190. Time synchronization, time tagging Function Value Time tagging accuracy of the synchrophasor data...
  • Page 147 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD141136-2 v10 Table 194. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 148 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Inverse characteristic M12388-1 v23 Table 195. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms whichever is greater æ...
  • Page 149 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 197. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is greater æ...
  • Page 150 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 198. IEC Inverse time characteristics for Line differential protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater æ...
  • Page 151 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 200. RI and RD type inverse time characteristics for Line differential protection Function Range or value Accuracy RI type inverse characteristic 0.05 ≤ k ≤ 1.10 IEC 60255-151, ±5.0% or ±40 ms whichever is greater ×...
  • Page 152 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 202. IEC Inverse time characteristics for Line Differential protection Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ± 5.0% or ± 40 ms whichever is greater æ...
  • Page 153 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-19F8E187-4ED0-48C3-92F6-0D9EAA2B39BB v4 Table 204. ANSI Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 ANSI/IEEE C37.112 , 1.5 x I ≤...
  • Page 154 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 205. IEC Inverse time characteristics for Sensitive directional residual overcurrent and power protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 2.00 IEC 60255-151, ±5.0% 1.5 x I ≤...
  • Page 155 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 GUID-2AE8C92E-5DA8-487F-927D-8E553EE29240 v2 Table 207. ANSI Inverse time characteristics for Voltage restrained time overcurrent protection Function Range or value Accuracy Operating characteristic: 0.05 ≤ k ≤ 999.00 ANSI/IEEE C37.112 , ± 5.0% or ±40 ms whichever is greater æ...
  • Page 156 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 SEMOD116978-2 v10 Table 209. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 157 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 210. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 158 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 211. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps ±5.0% or ±45 ms whichever is greater of 0.01 æ...
  • Page 159: Ordering For Customized Ied

    Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 27. Ordering for customized IED GUID-79B6B8D2-5EE1-4456-A767-5820B9FA61D7 v13 Table 212. General guidelines Guidelines Carefully read and follow the set of rules to ensure problem-free order management. Please refer to the available functions table for included application functions. PCM600 can be used to make changes and/or additions to the delivered factory configuration of the pre-configured.
  • Page 160 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 216. Differential protection Position Table 217. Differential functions Function Function Ordering no Position Available Selected Notes and identification rules High impedance differential protection, single phase HZPDIF 1MRK005904-HB 00-03 Restricted earth fault protection, low impedance REFPDIF 1MRK005904-LD Line differential protection for 3 CT sets, 2-3 line ends...
  • Page 161 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 219. Impedance functions, alternatives Function Function Ordering no Position Available Selected Notes and identification rules Note: One and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative. Alternative 1 Distance protection, quadrilateral Distance protection zone, quadrilateral characteristic ZMQPDIS,...
  • Page 162 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 220. Current protection Position Table 221. Current functions Function Function Ordering no Position Available Selected Notes and identification rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AD Directional phase overcurrent protection, four steps OC4PTOC 1MRK005910-BC Instantaneous residual overcurrent protection...
  • Page 163 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 227. Multipurpose protection Position Table 228. Multipurpose functions Function Function Ordering no Position Available Selected Notes and rules identification General current and voltage protection CVGAPC 1MRK005915-AA Table 229. General calculation Position Table 230.
  • Page 164 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 236. Scheme communication functions Function Function Ordering no Position Available Selected Notes and identification rules Scheme communication logic with delta based blocking ZCPSCH 1MRK005920-AA scheme signal transmit Phase segregated scheme communication logic for distance ZC1PPSCH 1MRK005920-BA protection...
  • Page 165 Additional local HMI user dialogue language No additional HMI language HMI language, English US 1MRK002920-UB Selected Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Table 244. Casing selection Casing Ordering no Selection Notes and rules 1/2 x 19"...
  • Page 166 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 248. Analog system selection Analog system Ordering no Selection Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 12I 1A, 50/60Hz, compression terminals...
  • Page 167 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 249. Maximum quantity of I/O modules, with compression terminals When ordering I/O modules, observe the maximum quantities according to the tables below. Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also be freely placed.
  • Page 168 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 251. Binary input/output module selection Binary input/ Ordering no Selection Notes and rules output modules Slot position (front view/rear view) 1/2 case with 1 █ █ █ 3/4 case with 1 █...
  • Page 169 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 251. Binary input/output module selection, continued Binary input/ Ordering no Selection Notes and rules output modules IOM 8 inputs, RL 1MRK000173-BE 110-125 VDC, 50mA, 10+2 output relays IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC, 50mA, 10+2...
  • Page 170 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Table 252. Station communication, remote end serial communication and time synchronization selection Station communication, remote end Ordering no Selection Notes and rules serial communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 █...
  • Page 171: Ordering For Pre-Configured Ied

    Line differential protection, Multi breaker, 1/3 phase tripping, 2-3 line ends 1MRK004810-HG Line differential protection, Single breaker, 1/3 phase tripping, with distance 1MRK004810-KG protection ACT configuration ABB standard configuration Selection for position #2 Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 172 No additional HMI language HMI language, English US 1MRK002920-UB Selection for position #4 Additional 2nd languages are continuously being added. Please get in touch with local ABB sales contact. Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 173 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Casing Ordering no Notes and rules 1/2 x 19" rack casing, 1 TRM 1MRK000151-VA 3/4 x 19" rack casing, 1 TRM 1MRK000151-VB 3/4 x 19" rack casing, 2 TRM 1MRK000151-VE 1/1 x 19"...
  • Page 174 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Analog system Ordering no Notes and rules When more than one TRM is selected, the connector type on both TRMs must be the same (A compression or B ring lug). Slot position (front view/rear view) No Transformer input module included TRM 9I 1A + 3U 110/220V, 50/60Hz, compression terminals...
  • Page 175 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. Slot position (front view/rear view)
  • Page 176 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Binary input/ Ordering no Notes and rules output modules For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used. Note: 1 BIM required in position P3 and 1 BOM required in position P4. IOM 8 inputs, RL 1MRK000173-CE 220-250 VDC,...
  • Page 177 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Station communication, remote end serial Ordering no Notes and rules communication and time synchronization Slot position (front view/rear view) Available slots in 1/2, 3/4 and 1/1 case with 1 █ █...
  • Page 178: Ordering For Accessories

    (ordering number RK926 315- IEDs is described in 1MRK 512 001-BEN and 1MRK BE). 001024-CA. Please refer to the website: Multi-breaker/Single or Three Phase trip with external www.abb.com/protection-control for detailed neutral on current circuit (ordering number RK926 315- information. BV).
  • Page 179 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Protection cover M15040-3 v8 Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC Protective cover for rear side of terminal, 6U, 3/4 x 19”...
  • Page 180 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 Specify additional quantity of IED Connect USB flash drive requested . Quantity: 1MRK 002 290-AE Hitachi Power Grids © Copyright 2017 Hitachi Power Grids. All rights reserved...
  • Page 181 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 User documentation Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 376-UEN ANSI Quantity: 1MRK 505 376-UUS Technical manual Quantity: 1MRK 505 377-UEN ANSI Quantity: 1MRK 505 377-UUS Commissioning manual Quantity: 1MRK 505 378-UEN...
  • Page 182 Line differential protection RED670 1MRK 505 379-BEN N Version 2.2 ANSI Quantity: 1MRK 511 398-UUS Cyber security deployment guideline Quantity: 1MRK 511 399-UEN Application guide, Communication set-up Quantity: 1MRK 505 382-UEN Reference information M2175-3 v4 For our reference and statistics we would be pleased to be provided with the following application data: Country: End user: Station name:...
  • Page 184 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://www.abb.com/protection-control © Copyright 2017 Hitachi Power Grids. All rights reserved.