high side system pressure. Operation of the LAC occurs
as outdoor temperatures drop below 60ºF. LAC operation
cycles the condenser fan on/off based on outdoor
temperature.
Part Number
8403-060
3 stage Cool; 3 stage Heat; Electronic Programmable/Non-Programmable; HP or Conventional; Auto or Manual
(1120-445)
changeover; Dehumidification Output
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
CS9B-THOA
Humidity Sensor w/ dehumidification; Motion Sensor w/Intelligent Learning Control; BACnet-compatible
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
CS9B-THOCA
Humidity Sensor w/ dehumidification; CO
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover; Humidity
CS9BE-THOA
Sensor w/ dehumidification; Motion Sensor w/Intelligent Learning Control; BACnet-compatible; Ethernet-compatible
3 stage Cool, 3 stage Heat; Programmable/Non-Programmable; HP or Conventional; Auto or Manual Changeover;
CS9BE-THOCA
Humidity Sensor w/dehumidification; CO
Ethernet-compatible
8403-095
1 stage Cool, 2 stage Heat – Heat Pump; 1 stage Cool, 1 stage Heat – Conventional; Programmable/Non-
(T4 Pro)
Programmable Electronic; Auto or Manual changeover
8403-090
2 stage Cool, 3 stage Heat – Heat Pump; 2 stage Cool, 2 stage Heat – Conventional; Programmable/Non-
(T6 Pro)
Programmable Electronic; Auto or Manual changeover
8403-091
1 stage Cool, 1 stage Heat; Non-Programmable; FEMA use
8403-092
2 stage Cool, 3 stage Heat – Heat Pump; 2 stage Cool, 2 stage Heat – Conventional; Programmable/Non-
(T6 Pro Wi-Fi)
Programmable Electronic; Auto or Manual changeover; Wi-Fi
TABLE 2
Humidity Controls
Part Number
8403-038
SPDT switching, pilot duty 50VA @ 24V;
(H600A1014)
Humidity range 20-80% RH
Electronic dehumidistat SPST closes-
8403-047
on-rise; Humidity range 10-90% with
(H200-10-21-10)
adjustable stops
TABLE 3
CO
Controllers
2
Part Number
Predominate Features
Normally Open SPST relay closes-on-rise
24V dual wave length sensor. Default setting
8403-096
950ppm, adjustable to 0-2000ppm
Default off setting 1000ppm, adjustable to
0-200 ppm can be calibrated
Wall Thermostats
2
Predominate Features
Freeze Protection Thermostat
An evaporator freeze protection thermostat is supplied
with all units. The freeze thermostat cuts out compressor
operation if the evaporator begins to freeze up.
TABLE 1
Predominate Features
Sensor; Motion Sensor w/Intelligent Learning Control; BACnet-compatible
2
Sensor; Motion Sensor w/Intelligent Learning Control; BACnet-compatible;
Transformer
VA
55
TABLE 4
Thermostat Wire Size
FLA
Wire Gauge
18 gauge
16 gauge
2.3
14 gauge
12 gauge
Manual 2100-752C
Page
Maximum
Distance
In Feet
60
100
160
250