Omron E5 J Series Manual page 11

Fuzzy self-tuning temperature controller with advanced pid (2 pid) contr
Table of Contents

Advertisement

E5 J
Set Point Setting ( C or F)
Use the Down and UP Keys to set the set point. A model with event
input allows the change of the set point (SP0 or SP1) that has been
selected.
Alarm 1, 2: al 1 , al 2 ( C or F)
Alarm values can be set with Down and Up Keys. The alarm mode is
factory set to upper-limit alarm (deviation) mode.
The alarm mode can be changed with the alarm mode selector.
An alarm value can be set to the deviation width or absolute value
according to the alarm mode.
Deviation alarm
Upper- and lower-limit
alarm, upper-limit alarm,
lower-limit alarm, upper-
and lower-limit range alarm
Set to the width deviated from
the set point.
Alarm value
10 C/ F
Set point (SP)
100 C/ F
Absolute-value alarm
Absolute-value upper-limit
alarm, absolute-value
lower-limit alarm
Set to the absolute value
based on 0 C/ F.
Alarm value
110 C/ F
0 C/ F
Level 1
E5CJ
O
PV
N
1 2
3
4
o
SV
Output value
Press a
ON/OFF
control
PV
hys
(Hysteresis
1.0
SV
SV
setting)
Press a
SV
SV
SV
Current value
SV
SV
SV
SV
Note: Nothing is displayed in current output model.
E5 J
(Output value display)
O
PID control
N
1 2
3
4
PV
cp
(See note)
20
(Control period setting)
Press a
Models with event input
PV
sp 0
0
(Set point 0 setting SP0)
Press a
PV
sp 1
0
(Set point 1 setting SP1)
Press a
Models with heater burnout alarm
PV
ct
(See note)
(Heater current display)
Press a
PV
hb
(See note)
0.0
(Heater burnout alarm
Set value)
Press a
If the control mode is set to
advanced PID
O
PV
N
1 2
3
4
p
8.0
(Proportional band setting)
Press a
PV
i
233
(Integral time setting)
Press a
PV
d
40
(Derivative time setting)
Press a
When I = 0
PV
ofr
(Manual reset
50.0
SV
value setting)
Press a
11