E5jJ
Precautions
Mounting
The dimensions of the Temperature Controller conform to
DIN 43700. Recommended panel thickness is 1 to 8 mm for the
E5AJ, E5BJ, and E5EJ, and 1 to 4 mm for the E5CJ.
The mounted Temperature Controller must be horizontally level.
Do not install the Temperature Controller in a location exposed to
excessive dust or corrosive gases. Moreover, avoid locations sub-
ject to heavy vibration or shock, water or oil spray, or high tempera-
tures. Any of these conditions will affect product life.
Isolate the Temperature Controller from equipment that generates
strong, high-frequency noises such as high-frequency welders, be-
cause such equipment may prevent proper operation.
E5AJ/E5BJ/E5EJ
Two mounting brackets are provided with the Temperature Control-
ler. Mount one of the brackets to the top and the other one to the bot-
tom of the Temperature Controller. Turn the ratchets of the mounting
brackets clockwise with a Phillips screwdriver until they snap.
Insert the unit back into the case by pushing the unit until it clicks into
place.
E5CJ
Insert the Temperature Controller into the square hole of the panel
and insert an adapter from the backside so that there will be no
space between the Temperature Controller and the panel. Then se-
cure the Temperature Controller with a screw.
Tightening screw
Dismounting
Loosen the screw of the adapter for dismounting.
Connection Example
With Solderless Terminal
Use M3.5 x 8 solderless terminals with the Temperature Controller's
M3.5 self-rising pressure plate screws.
Solder-dipped Leads
Strip 6 to 8 mm of the lead wires and carefully arrange the wire tips.
Do not tighten the terminal screw with excessive force, because do-
ing so many damage them. The terminal block of the Temperature
Controller is constructed so that the lead wires can be connected to
all the terminals from the same direction.
Example: E5CJ
Input Type Connection
To reduce inductive noise influence, the lead wires connecting the
input type to the Temperature Controller must be separated from the
power lines and load lines.
Use the specified compensating conductors for thermocouples.
Use lead wires having a small resistance for platinum resistance
thermometers.
Sequenced Circuits
Several seconds are required until the relay is turned ON after pow-
er has been supplied to the Temperature Controller. Therefore, take
this time delay into consideration when designing sequenced cir-
cuits which incorporate a Temperature Controller.