NOTE 
The use of silicon sealant may inhibit the effectiveness of some types of leak detection 
equipment. Instrinsically safe components do not have to be isolated prior to working 
on them. 
11) Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without
ensuring that this will not exceed the permissible voltage and current permitted for
the equipment in use. Intrinscially safe components are the only types that can be
worked on while live in the presence of a flammable atmosphere. The test apparatus 
shall be at the correct rating. Replace components only with parts specified by the
manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.
12) Cabling
Check  that  cabling  will  not  be  subject  to  wear,  corrosion,  excessive  pressure,
vibration, sharp edges or any other adverse environmental effects. The check shall
also take into account the effects of aging or continual vibration from sources such
as compressors or fans.
13) Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching
for or detection of refrigerant leaks. A halide torch (or any other detector using a 
naked flame) shall not be used. 
14) Leak detection methods 
The  following  leak  detection  methods  are  deemed  acceptable  for  systems
containing flammable refrigerants. Electronic leak detectors shall be used to detect
flammable refrigerants, but the sensitivity may not be adequate, or may need re‐
calibration.(Detection  equipment  shall  be  calibrated  in  a  refrigerant‐free  area.)
Ensure that the detector is not a potential source of ignition and is suitable for the
refrigerant. Leak detection equipment shall be set at a percentage of the LFL of the
refrigerant and shall be calibrated to the refrigerant employed and the appropriate
percentage of gas (25% maximum) is confirmed. Leak detection fluids are suitable 
for use with most refrigerants but the use of detergents containing chlorine shall be
avoided as the chlorine may react with the refrigerant and corrode the copper pipe‐
work. If a leak is suspected ,all naked flames shall be removed or extinguished. If a
leakage of refrigernat is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated(by means of shut off valves) in a part of the 
system  remote  from  the  leak  .  Oxygen  free  nitrogen(OFN)  shall  then  be  purged 
through the system both before and during the brazing process.
15) Removal and evacuation
When breaking into the refrigerant circuit to make repairs of for any other purpose
conventional procedures shall be used, However, it is important that best practice
is followed since flammability is a consideration. The following procedure shall be
adhered to: 